Application of thermal battery in the ice storage

air-conditioning system as a subcooler

Ming-Chao Huang

a

, Bo-Ren Chen

b

, Ming-Jer Hsiao

a

, Sih-Li Chen

b,

*

aDepartment of Electrical Engineering, Nan-Kai Institute of Technology, No.568 Chung Cheng Road, Tsao Tun,

Nan Tou, Taiwan 54243, ROC

bDepartment of Mechanical Engineering, National Taiwan University, No.1, Sec.4 Roosevelt Road, Taipei, Taiwan 10617, ROC

Received 23 March 2006; received in revised form 4 July 2006; accepted 24 July 2006 Available online 22 November 2006

Abstract

This article experimentally investigates the thermal performance of a thermal battery used in the ice storage air-conditioning system as a subcooler. The thermal battery utilizes the superior heat transfer characteristics of two-phase closed thermosyphon and eliminates the drawbacks found in convectional energy storage systems. Experimental investigations are first conducted to study the thermal behavior of thermal battery under different charge temperatures (5C to9C) in which water is used as the energy storage material. This study also examines the thermal performance of the subcooled ice storage air conditioner under different cooling loads. Experimental data of temperature variation of water, ice fraction, refrigerant mass flow rate and coef-ficient of performance (COP) are obtained. The results show that supercooling phenomenon appears in the water and it can be ended when the charge temperature is lower than6C. The system gives 28% more cooling capacity and 8% higher COP by the contribution of the thermal battery used as a subcooler.

Ó 2006 Elsevier Ltd and IIR. All rights reserved.

Keywords: Air conditioning; Thermal storage; Ice tank; Experiment; Subcooling

Syste`me de conditionnement d’air utilise´ en tant que

sous-refroidisseur: application de l’accumulation de glace

Mots cle´s : Conditionnement d’air ; Accumulation thermique ; Bac a` glace ; Expe´rimentation ; Sous-refroidissement

1. Introduction

Ice storage air-conditioning system[1,2]is an important element of many energy conservation programs in industry

and in commercial applications. Most of the ice storage sys-tems utilize an active control method to store or release ther-mal energy. In the system design of therther-mal storage, a pump is included to transfer thermal energy from a high-temperature heat source to the thermal storage tank via flowing working fluid. To utilize the storage energy, an electromagnetic valve is used under control to change the flow path of the working fluid, so that the energy stored in the tank is released for use later. There are two drawbacks found in such systems. First,

* Corresponding author. Tel.:þ886 2 23631808; fax: þ886 2

23631755.

E-mail address:slchen01@ntu.edu.tw(S.-L. Chen).

0140-7007/$35.00Ó 2006 Elsevier Ltd and IIR. All rights reserved.

doi:10.1016/j.ijrefrig.2006.07.027

(2)

the thermal storage shall be unusable in case of pump or electromagnetic valve failure. Second, the charge and dis-charge function of the conventional storage systems basically relies on the system piping design, and therefore only two functions, energy store and energy release, are available in its operating modes.

The present article provides a new ice storage design e thermal battery [3]in which a passive type of control is adopted to eliminate drawbacks in the convectional ice stor-age systems. The thermal battery, as shown inFig. 1, mainly includes an energy storage tank and a two-phase closed ther-mosyphon. The energy storage tank is filled with water. The thermosyphon includes three parts, namely, a group of parallel-fin tubes vertically disposed inside the energy storage tank, charge heat exchanger and discharge heat exchanger in a double-pipe type separately located at the upper and lower regions, respectively inside the storage tank. An adequate amount of working fluid (R-22) is filled in the thermosyphon.

Fig. 2a shows the function in which the system operates to store thermal (cold) energy. When low-temperature fluid

flows into the charge heat exchanger, thermal energy con-tained in the water is transferred to the working fluid inside the parallel-fin tubes. The liquid working fluid undergoes film evaporation and absorbs thermal energy to solidify the water as ice in the storage tank. The vapor flows upward due to its buoyancy to the charge heat exchanger. As the thermal energy is transferred to the low-temperature fluid, the vapor working fluid undergoes film condensation on the outside surface of the charge heat exchanger. Then the condensate flows along the wall of parallel-fin tubes to complete the charge cycle.

Fig. 2b illustrates the manner in which the system oper-ates to release cold energy. When high-temperature fluid flows into the discharge heat exchanger, the ice inside the storage tank will absorb thermal energy to cool the high-temperature fluid. The liquid working fluid in the thermosy-phon absorbs thermal energy from the high-temperature fluid through the discharge heat exchanger and gets boiled to produce vapor working fluid. The vapor flows upward and undergoes film condensation on the inner wall of the vertical fin tubes to release thermal energy to melt the ice. Then, the condensed working fluid flows downward and returns to the discharge heat exchanger to complete the discharge cycle.

The above-described charge and discharge operation modes work separately at different times. The third opera-tion mode combines the above two operaopera-tion modes, that is, the thermal battery also allows the operation of energy storage and energy release at the same time. As shown in

Fig. 3a, when the cold energy supplied by the low-temperature flowing fluid is higher than that to be absorbed by the high-temperature flowing fluid, the thermal battery transfers the cold energy from the low-temperature fluid to the high-temperature fluid. Extra cold energy is stored inside the Nomenclature

COP coefficient of performance of the system with subcooler (dimensionless)

Cp specific heat (kJ kg1C)

H water level height (m)

he latent heat of water (kJ kg1)

h enthalpy (kJ kg1)

Lx thermal battery width (m)

Ly thermal battery length (m)

M total mass of the energy storage material (kg)

m mass (kg)

P pressure (MPa)

_

Qa cooling capacity (kW)

_

Qb cold storage rate (kW)

_

Ql cooling load (kW)

r mass flow ratio of the refrigerant (dimensionless) T temperature (C) Greek symbol r density (kg m3) Subscripts a outdoor unit b thermal battery

c charge heat exchanger

d discharge heat exchanger

e energy storage material

i inlet

l cooling load

n level no. of water

o outlet

s solid

t time

w water

Charge heat exchanger

Discharge heat exchanger Energy storage material

Fin tube Working fluid Energy storage tank

(3)

thermal battery. The heat transfer mechanisms in this case include film condensation in the charge heat exchanger, film evaporation along the thermosyphon tubes, pool boiling in the discharge heat exchanger, and ice formation along the fins.Fig. 3b shows that as the energy supplied by the low-temperature flowing fluid is not sufficient to cool the high-temperature fluid, cold energy can be released from the ther-mal battery to provide the high-temperature fluid to meet its need. The heat transfer mechanisms are similar to the above case except that film condensation occurs along the thermo-syphon tubes and ice melts around the fins. When the cold energy supplied by the low-temperature fluid is equal to the energy absorbed by the high-temperature fluid, the ther-mal energy will be transferred directly from the discharge heat exchanger to the charge heat exchanger, as shown in

Fig. 3c, through film condensation and pool boiling. Chieh et al.[3]experimentally and theoretically studied the thermal behavior of the thermal battery during cold stor-age process. The charge and discharge heat exchangers are located at outside of the storage tank. As the system operates in charge or discharge mode, the heat exchanger combines the fin tubes as a two-phase closed loop thermosyphon. It shows that different heat transfer mechanisms including nucleate boiling, geyser boiling and natural convection are

identified in different experimental systems with various working fluid fill levels. Higher working fluid fill level provides greater surface area for nucleate boiling. However, it decreases the effective condenser area for the discharge process. In this study, the charge and discharge heat ex-changers are modified as a two-phase closed thermosyphon. The charge and discharge heat exchangers with double-pipe types are located at the upper and lower regions inside the storage tank, respectively. As the thermal battery stores or releases cold energy, the heat exchangers connect the fin tubes to form a two-phase closed thermosyphon, which en-hances the effective film condensation and film evaporation areas and provides a more compact storage tank.

2. Subcooled ice storage air-conditioning system

Fig. 4 shows an ice storage air-conditioning system, which adopts the thermal battery as a subcooler. The system consists of an outdoor unit, a thermal battery, a plate heat exchanger, a fan-coil unit, a pressure-reducing valve, two expansion valves, and two solenoid valves. The outdoor unit includes a compressor and a condenser. The outdoor unit outlet connects to the inlet of charge and discharge heat exchangers individually. The outlet of charge heat

Film Condensation Film Evaporation Low-temperature Fluid Ice Formation Film Condensation Pool Boiling High-temperature Fluid Ice Melting (a) (b)

Fig. 2. Thermal storage in the thermal battery (a) charge mode, (b) discharge mode.

Film Evaporation Pool Boiling Film Condensation Film Condensation Pool Boiling Film Condensation Adiabatic Falling Film Pool Boiling Film Condensation (a) (b) (c)

Fig. 3. Thermal storage in the thermal battery for the case of supplied cold energy (a) greater than the absorbed energy, (b) less than the absorbed energy, and (c) equal to the absorbed energy.

(4)

exchanger joins the outdoor unit inlet to form a loop. The discharge heat exchanger combines the plate heat exchanger and the outdoor unit to form another loop.

The cooling energy provided by the outdoor unit is trans-ferred from the plate heat exchanger to the fan-coil unit by water circulation. The pressure-reducing valve is installed in the outlet of refrigerant side of the plate heat exchanger to reduce the pressure of the refrigerant leaving from the plate heat exchanger. One expansion valve is set at the charge heat exchanger inlet and the other is set in the outlet of the discharge heat exchanger. The solenoid valves are set at the inlet of the charge and discharge heat exchangers of the thermal battery, respectively, to control the direction of the refrigerant leaving the outdoor unit.

Fig. 5illustrates the pressureeenthalpy diagram of the subcooled ice storage air-conditioning system, in which the system operates in three modes: charge, discharge, and simultaneous charge and discharge modes. When the

T2,P2 T3,P3 T6 Twi Two T10 T11 T12 T4 P7,T7 T8 T5 Tr T1,P1 T9 1 2 3 4 5 6 7 8 9 Compressor Condenser Thermal Battery Solenoid Valve No.1 Solenoid Valve No.2 Expansion Valve Pressure Reducing Valve

Plate Heat Exchanger

Fan Coil Unit Expansion Valve Flow Meter Water Pump Personal Computer Recorder Thermocouple Pressure Gage Power Meter Outdoor Unit

Fig. 4. Schematic of subcooled ice storage air-conditioning system and measurement apparatus.

3 6 h

2

4 8 Subcooling 5 9 P 7 1 d m c m

Fig. 5. Pressureeenthalpy diagram of subcooled ice storage air-conditioning system.

(5)

solenoid valve no. 1 is opened, the system operates in the charge mode. The refrigerant leaves the condenser at state 3, and then undergoes expansion process. The refrigerant leaves the expansion valve as low temperature, low quality vapor, and then enters the thermal battery to store the cold energy. The refrigerant leaves the thermal battery at state 5 as a saturated vapor, and returns to the compressor to com-plete the charge cycle at state 1.

By opening the solenoid valve no. 2, the system operates in the discharge mode. The refrigerant leaves the condenser at state 3 as high-temperature saturated liquid, and is sub-cooled by the thermal battery. The refrigerant leaves the thermal battery at state 6 and undergoes expansion process to be low temperature, low quality vapor. Then the vapor en-ters the plate heat exchanger and absorbs the cooling load of the room and undergoes a pressure-reducing process. Then the refrigerant returns to the compressor at state 9 as a super-heated vapor to complete the discharge cycle.

The simultaneous charge and discharge modes are initi-ated when both the solenoid valves nos.1 and 2 are opened. In such event, the system can manage the energy automati-cally based on the cooling capacity and the cooling load. When the cooling capacity of outdoor unit is greater than the cooling load, most of the refrigerant leaving from out-door unit will pass the charge heat exchanger to store cold energy. The remaining refrigerant flows into the discharge heat exchanger and absorbs energy from the charge heat ex-changer to cool the refrigerant. If the cooling capacity is less than the required load, small portion of refrigerant will flow into the charge heat exchanger to cool the refrigerant inside the discharge heat exchanger and most of the refrigerant will pass the discharge heat exchanger to absorb the stored cold energy in the storage tank. If the cooling capacity is equal to the load, all refrigerant will pass the discharge heat ex-changer and supply the cold energy to meet the load require-ment without using the stored energy in the thermal battery. The thermal battery can shift the need of thermal energy from high cooling load to the low one. The designer can choose the capacity of outdoor unit to meet the average cool-ing load rather than the maximum load. Besides, the outdoor unit can operate at full load all the time due to the energy management of the thermal battery. This gives the best performance of the outdoor unit, and contributes to reduce the power consumption under the same cooling load [4]. The thermal battery subcools the discharged refrigerant of the outdoor unit before the refrigerant undergoes expansion process and let the air-conditioning system to provide more cooling capacity and higher COP than the system without the thermal battery.

3. Experimental investigations

In this paper, two experiments are developed to discuss the thermal performance of the ice storage air-conditioning system using thermal battery as a subcooler. In the first experiment, the thermal behavior of the energy storage

material, water, in the thermal battery under different charge temperatures is investigated. Applying the result from the first experiment, the thermal performance of the subcooled ice storage air-conditioning system operating in simulta-neous charge and discharge modes under various cooling loads is experimentally described. This study also examines the variation of the refrigerant mass flow rate of the charge and discharge heat exchangers of the thermal battery.

Water is used as the energy storage material in the present article because of the advantages of water, such as high latent heat, stable chemical property, easy acquisition and compatibility with the material of the air-conditioning sys-tem. However, one of the most serious problems with the use of water is the supercooling phenomenon occurring in the solidification of water during the charge process [5]. To store the thermal energy in the form of latent heat, the charge temperature of the thermal battery must be lower than the water nucleation temperature. This tends to cause a decline in the COP of the air-conditioning system. In order to ensure the latent energy storage, the highest charge temperature, which can induce the nucleation process of the water, will be experimentally obtained in this study.

Fig. 4demonstrates the schematic of the experimental ap-paratus used in the experiment. The thermal battery comprises a storage tank, fin tubes and two double-pipe heat exchangers. The storage tank is made of 3 mm thick stainless steel plates. In the storage tank, 12 rows of copper fin tubes with 18 fins per inch are mounted. Twelve double-pipe heat exchangers, con-nected at the top and bottom of the storage tank, combine the fin tubes to form the two-phase closed thermosyphon. The length, width, and height of the thermal battery are 0.85 m, 1.38 m, and 0.745 m, respectively. Three hundred and sixty kilogram of pure water is used inside the storage tank, and working fluid of the thermosyphon is R-22. Insulation mate-rial at the outside of the storage tank prevents heat losses dur-ing the experiment. The nominal cooldur-ing capacity of the outdoor unit is 15.5 kW, and the refrigerant of the outdoor unit is also R-22. This study sets the room temperature at 25C and water flow rate of the water pump at 95 lpm.

Fig. 4also shows the measuring apparatus used in this study. The primary property of measurement point is the enthalpy, which can be obtained by the measured tempera-ture and pressure. Temperatempera-ture measurement utilizes T-type thermocouples includes nine measurement locations for the refrigerant, in which, T1, T2 and T3 for the inlet

and outlet of the compressor and the outlet of the condenser, respectively; T4, T5 and T6for the inlet and outlet of the

charge heat exchanger and the outlet of discharge heat exchanger, respectively; T7 and T8for inlet and outlet of

the plate heat exchanger, respectively; T9for outlet of the

pressure-reducing valve. The water temperature distribu-tions are measured from T10, T11and T12. The water

temper-ature of the inlet and outlet of the plate heat exchanger at water side are obtained by two thermocouples Twiand Two.

Four pressure gages within 3% accuracy determine the refrigerant pressure set at the same location of T1, T2,T3

(6)

and T7. This article assumes that the pressure at the points 1,

4, 5 and 9 are equal, since the pressure loss caused by the piping friction is negligible. For the same reason, the pres-sure at the points 3 and 6 are equal, so do the points 7 and 8. The water flow rate of the plate heat exchanger is mea-sured by flow meter. All the data are collected by a recorder and calculated by a personal computer.

The energy balance equation of the ice storage air-conditioning system can be expressed as:

_

Qa¼ _Qbþ _Ql ð1Þ

The cooling capacity provided by the outdoor unit, _Qa, is equal to the cold storage rate in the thermal battery, _Qb, and cooling load of the room, _Ql. Cold storage rate can be ob-tained from the temperature drop of the water, DTn;t, and mass of the ice,ms, as shown by the following equation

_ Qb¼ 1 Dt (" X12 n¼10 MnCpDTn;t # þ ðms;tþDt ms;tÞhe ) ð2Þ where DTn;t¼ ðTn;t Tn;tþDtÞ ð3Þ

The first term in the RHS of Eq.(2)is the sensible cold storage rate and the second term indicates the latent heat storage rate. The mass of ice,ms,t, can be calculated from

the water level height,Hw, in the storage tank.

ms;t¼ LxLyðHw;t Hw;t¼0Þ  rsrw rw rs  ð4Þ The ice fraction, b, is defined as the mass ratio of ice to water,

b¼ms

M ð5Þ

The cooling load _Ql may be evaluated from the water temperature difference between inlet and outlet of the plate heat exchanger

_

Ql¼ _mwðTwi TwoÞ ð6Þ

The refrigerant mass flow rate of the discharge heat exchanger, _md, may be obtained as

_ md¼ _ Ql h8 h7 ð7Þ The refrigerant mass flow rate of the charge heat ex-changer, _mc, can be determined from the energy balance in the thermal battery,

_ mc¼ _ Qb _mdðh3 h6Þ h5 h4 ð8Þ According to the uncertainty analysis proposed by ISO standard [6], the uncertainties in percentage of cooling

capacity, cooling load and cold storage rate of the thermal battery are7.6%, 4.3% and 4.7%, respectively. 4. Results and discussion

Fig. 6shows temperature distribution of water in the stor-age tank during charge process for different charge temper-atures (5C,7C and9C). During the experiment, water is cooled from sensible heat storage to latent heat stor-age. In the form of sensible energy storage water at different levels has almost the same temperature profiles, which means thermal stratification does not appear in the storage tank. This is due to the fact that film evaporation occurs inside the thermosyphon and keeps the water temperature uniform. It also means that the thermal energy coming from the charge heat exchanger can be spread to and stored in water by the superior heat transfer rate of film evapora-tion. This makes the system store cold energy more effi-ciently, and enhances charge density of the thermal battery.

Fig. 6also indicates that the nucleation occurs for the cases of7C and9C, while the supercooling appears when the charge temperature is 5C. For the cases of 5C, the temperature of water is cooled from 21C to 0C, which stores the energy by sensible heat. As further cooling occurs, freezing does not occur at the water freezing temperature (0C). Water below 0C is called supercooled and is a state of meta-stable. In this case thermal energy can only be stored in the form of sensible heat. To store the en-ergy in the form of latent heat, the entrance temperature of the flowing fluid must be lower than the water nucleation temperature (about 6C). For the case of 7C and 9C, the ice nucleation occurs and thin plate-like crystal grows into the supercooled region. During the crystal growth process, latent heat released from the crystal is consumed by supercooled water. The water temperature returns to its freezing temperature. As the charge process is continued, the solid ice will form around the fin tubes and the cold is stored by latent energy.

Fig. 7illustrates the ice fraction variation for different charge temperatures. For the case of 9C, water stores the cold energy in the form of sensible energy, such that the ice fraction is zero during the first half hour until the nu-cleation is induced and the ice fraction is initiated. As more cold energy is stored in the thermal battery, the ice fraction increases gradually, so does the thickness of the ice covering on the outside of the fin tubes. This causes greater thermal resistance and delays the ice formation. The total time required for complete ice formation is about 4 h when the charge temperature is9C. For the case of 7C, the nucleation occurs at 45 min after the experiment began and the total time required for complete ice growth is 6 h. In the case of5C, the ice fraction maintains zero during all experimental period. Only sensible energy storage can be observed in this case. Therefore it is necessary to control the charge temperature lower than6C to ensure that cold is stored by latent heat.

(7)

Fig. 8shows the variation of the cooling load, the outdoor unit cooling capacity and cold storage rate of the thermal battery when the subcooled ice storage air-conditioning sys-tem operates in simultaneous charge and discharge modes. The present experiments can be divided into three regions. In region I, the cooling load is less than the cooling capacity, extra cold energy is stored by the thermal battery, such that the cold storage rate in the thermal battery is positive. In re-gion II, the cooling load is greater than the cooling capacity, thermal battery releases the stored energy to supply the need of cooling load, and the cold storage rate is negative. In re-gion III, the cooling load is smaller than the cooling capacity and the cold storage rate of the thermal battery becomes to be positive again.

The cooling capacity supplied by the outdoor unit is maintained almost constant and equals to the nominal capac-ity of the outdoor unit (15.5 kW) during the first ten hours of

the experiment. This indicates that the thermal battery can automatically manage the charge and discharge of the cold energy and let the outdoor unit operates at full load, in which the outdoor unit gives the best performance. After 18 h, the decreasing cooling capacity results from the low cooling load and cold storage rate caused by greater thickness of the ice formation on the outside of fin tubes. The maximum cooling capacity of the subcooler ice storage air-conditioning system is 19.8 kW, which is 28% higher than the nominal capacity of the outdoor unit.

Fig. 9demonstrates variation of the room temperature, the water temperature and the ice fraction of the thermal bat-tery. Since the thermal battery stores cold energy in region I, water temperature drops to its nucleation temperature at 10 h and then the ice forms. In region II, thermal battery releases the stored energy, and the ice melts initially. The ice melts completely at 12 h, then water supplies the cold in the

0 1 2 3 4 5 6 7 Time (hr) -10 -5 0 5 10 15 20 25 (a) (b) (c) T10 T11 T12 ESM Temperature T10 T11 T12 ESM Temperature T10 T11 T12 ESM Temperature Charge Side Temperature : -5°C

ESM initial temperature : 21°C

0 1 2 3 4 5 6 7 Time (hr) -10 -5 0 5 10 15 20 25 Temperature (ºC) Temperature (ºC) Temperature (ºC)

Charge Side Temperature : -7°C ESM initial temperature : 21°C

0 1 2 3 4 5 6 7 Time (hr) -10 -5 0 5 10 15 20 25

Charge Side Temperature : -9°C ESM initial temperature : 21°C

(8)

form of sensible energy to the need of cooling load. Water temperature increases gradually and reaches to its maximum of 22.5C at the end of region II. In region III, the water tem-perature drops gradually till the nucleation occurs at 18 h. Then the extra cold energy is stored in the form of latent energy and the ice fraction increases. The room temperature is maintained at 25 0.3C during the experiment period. This indicates that the proposed subcooled ice storage air-conditioning system can give a constant temperature environment.

Fig. 10depicts the variation of cooling load and refriger-ant mass flow rate of the charge and discharge heat ex-changers of the thermal battery. The charge and discharge refrigerant mass flow rates show similar trend with the cold storage rate and the cooling load, respectively as shown inFig. 8. In region I, more and more refrigerant flows into the discharge heat exchanger rather than the charge heat ex-changer as the cooling load is increasing. In region II, almost all the refrigerant passes the discharge heat exchanger since the cooling load is greater than the cooling capacity. In region III, lower cooling load induces decreasing refrigerant

I II III Time -6 -3 0 3 6 9 12 15 18 21 24

Energy Transfer Rate (kW)

Cooling Load Cooling Capacity Cold Storage Rate

8:00 11:00 14:00 17:00 20:00 23:00

Fig. 8. Cooling load, cooling capacity and cold storage rate of the thermal battery. I II III Time -10 -5 0 5 10 15 20 25 30 Temperature (ºC) 0 0.2 0.4 0.6 0.8 1 Ice Fraction Room Temperature ESM Temperature Ice Fraction 8:00 11:00 14:00 17:00 20:00 23:00

Fig. 9. Variation of the room temperature, the water temperature and the ice fraction of the thermal battery.

0 1 2 3 4 5 6 7 Time (hr) 0 0.2 0.4 0.6 0.8 1

Ice Fraction Charge Side Temperature -5°C -7°C -9°C

Fig. 7. Ice fraction variations under different charge temperatures.

8:00 11:00 14:00 17:00 20:00 Time 0 0.02 0.04 0.06 0.08 0.1 0.12

Refrigerant Mass Flow Rate (kg/sec)

Discharge Heat Exchanger Charge Heat Exchanger

23:00

Fig. 10. Charge heat exchanger and discharge heat exchanger of refrigerant flow rate and the cooling load.

(9)

flow rate of the discharge heat exchanger. The charge refrigerant mass flow rate is related to the variation of the cold storage rate. It shows that the proposed ice storage air-conditioning system can manage the cold storage by ad-justing the distribution of the refrigerant flow from cooling capacity and cooling load without any electrical controller included.

Fig. 11shows the COP of the subcooled ice storage air-conditioning system and the mass flow ratio of the refriger-ant, which are calculated from the experimental data of

Fig. 10. Since the system operates in simultaneous charge and discharge modes, the COP of the system can be expressed as

COP¼ð1  rÞðh5 h4Þ þ rðh8 h7Þ ðh2 h1Þ

ð9Þ wherer is the mass flow ratio of the refrigerant,

r¼ md

mcþ md

ð10Þ As seen inFig. 11, the mass flow ratio of the refrigerant lies in the range between 0 and 1, depending on the cooling load and the cooling capacity. At region I the cooling capac-ity of the system is greater than the cooling load. Extra cold energy is stored in the thermal battery. The mass flow ratio increases from 0.41 to 0.93 as the cooling load changes from 6.2 kW to 15.0 kW. At this stage the subcooled ice stor-age air-conditioning system operates with a constant COP of 4.8. At region II since the cooling load is higher than the

cooling capacity, most of the refrigerant enters the discharge heat exchanger of the thermal battery. The mass flow ratio of the refrigerant changes from 0.93 to 0.96. The COP shows a similar trend with the cooling load, the best of which is 6.1. As the cooling load is decreasing at region III, most re-frigerant flows through the charge heat exchanger of thermal battery. The charging process decreases the evaporating pressure of the system in order to solidify the water inside the storage tank, which lowers the system COP to 3.5 at the end of the experiment. The mean COP of the system cov-ering from region I to III is 4.5. If the system is operated without the subcooler, the COP of the system is 3.9 at the conditions of 50C condensing temperature and 5C evap-orating temperature. For the case of ice storage, the system COP is 3.1 while the condensing and evaporating tempera-tures are 50C and7C, respectively. It is obvious that the subcooled ice storage air-conditioning system benefits not only greater cooling capacity but also better performance by adopting the thermal battery as the subcooler.

5. Conclusions

This paper provides a thermal battery allowing operation of charge, discharge and simultaneous charge and discharge modes. Application of thermal battery as a subcooler in the ice storage air-conditioning system is demonstrated. The subcooled ice storage air-conditioning system can automat-ically adjust the refrigerant mass flow rates at the charge and discharge heat exchangers, depending upon the energy con-tents of charge and discharge sides. In addition to providing an enhanced COP technology through subcooling of high-temperature condensate refrigerant, it also balances the cooling load to permit the outdoor unit operating at full-load condition.

References

[1] ASHRAE, ASHREA Handbook e HVAC Systems and Equip-ment, ASHRAE Inc., Atlanta, 2004.

[2] ASHRAE, ASHREA Handbook e HVAC Applications, ASHRAE Inc., Atlanta, 2003.

[3] J.J. Chieh, S.J. Lin, S.L. Chen, Thermal performance of cold storage in thermal battery for air conditioning, Int J Refrigera-tion 27 (2004) 120e128.

[4] S.K. Wang, Handbook of Air Conditioning and Refrigeration, McGraw-Hill, 1993.

[5] S.L. Chen, T.S. Lee, A study of supercooling phenomenon and freezing probability of water inside horizontal cylinders, Int J Heat Mass Transfer 41 (1998) 769e783.

[6] Guide to Expression of Uncertainty in Measurement, ISO, 1995 (corrected and reprinted).

Time 1 3 4 5 6 7 COP 0 0.2 0.4 0.6 0.8 1

Mass flow ratio

Mass flow ratio COP

I II III

8:00 11:00 14:00 17:00 20:00 23:00

Fig. 11. COP of the subcooled ice storage air-conditioning system and the mass flow ratio of the refrigerant.

數據

Fig. 2a shows the function in which the system operates to store thermal (cold) energy
Fig. 2. Thermal storage in the thermal battery (a) charge mode, (b) discharge mode.
Fig. 5 illustrates the pressureeenthalpy diagram of the subcooled ice storage air-conditioning system, in which the system operates in three modes: charge, discharge, and simultaneous charge and discharge modes
Fig. 6 shows temperature distribution of water in the stor- stor-age tank during charge process for different charge  temper-atures (5  C, 7  C and 9  C)
+4

參考文獻

相關文件

When the relative phases of the state of a quantum system are known, the system can be represented as a coherent superposition (as in (1.2)), called a pure state; when the sys-

For ex- ample, if every element in the image has the same colour, we expect the colour constancy sampler to pro- duce a very wide spread of samples for the surface

You are given the wavelength and total energy of a light pulse and asked to find the number of photons it

好了既然 Z[x] 中的 ideal 不一定是 principle ideal 那麼我們就不能學 Proposition 7.2.11 的方法得到 Z[x] 中的 irreducible element 就是 prime element 了..

Wang, Solving pseudomonotone variational inequalities and pseudocon- vex optimization problems using the projection neural network, IEEE Transactions on Neural Networks 17

volume suppressed mass: (TeV) 2 /M P ∼ 10 −4 eV → mm range can be experimentally tested for any number of extra dimensions - Light U(1) gauge bosons: no derivative couplings. =>

Define instead the imaginary.. potential, magnetic field, lattice…) Dirac-BdG Hamiltonian:. with small, and matrix

incapable to extract any quantities from QCD, nor to tackle the most interesting physics, namely, the spontaneously chiral symmetry breaking and the color confinement.. 