Effect of number of tube rows on the air-side performance of crimped spiral

fin-and-tube heat exchanger with a multipass parallel and counter cross-flow

configuration

Parinya Pongsoi

a

, Santi Pikulkajorn

b

, Chi-Chuan Wang

c

, Somchai Wongwises

a,d,⇑

a

Fluid Mechanics, Thermal Engineering and Multiphase Flow Research Lab. (FUTURE), Department of Mechanical Engineering, King Mongkut’s University of Technology, Thonburi, Bangmod, Bangkok 10140, Thailand

b

Somchai Industry Co., Ltd., Bangkok 10150, Thailand

c

Department of Mechanical Engineering, National Chiao Tung University, Hsinchu 300, Taiwan

d

The Royal Institute of Thailand, Academy of Science, Sanam Suea Pa, Dusit, Bangkok 10300, Thailand

a r t i c l e

i n f o

Article history: Received 11 March 2011

Received in revised form 23 June 2011 Accepted 23 June 2011

Available online 21 October 2011 Keywords: Crimped fin Heat transfer Heat exchanger Air–water Extended surface

a b s t r a c t

The air-side performance of crimped spiral fin and tube heat exchangers at high Reynolds number (3000– 13,000) is investigated in this study. The test heat exchangers have a new type of multipass parallel and counter cross-flow water flow arrangement which is a combination of parallel cross-flow and counter cross-flow. The test samples are made from copper and aluminium with different number of tube rows (Nrow= 2, 3, 4 and 5). The effects of number of tube rows and fin material on the heat transfer and friction

characteristics are studied. The results show that no significant effect for either number of tube rows or fin materials on the heat transfer performance is found at high Reynolds number. In addition, the corre-lation of the air-side performances of this type of the heat exchangers at high Reynolds number is devel-oped for industrial applications.

Ó 2011 Elsevier Ltd. All rights reserved.

1. Introduction

The heat exchanger is a basic component that is used for ther-mal systems in many industrial processes involving heat transfer. The most favourable type of heat exchanger used in industrial applications is the fin-and-tube heat exchanger. It is very impor-tant to consider the heat transfer rate, which is normally limited by the thermal resistance on the air-side of the heat exchanger. One way to augment the heat transfer rate on the air-side of the heat exchanger is to improve the fin geometry. However, this method may lead to the need for increased fan power because of the penalty associated with the pressure drop. Many researchers had studied the effect of the plate fin geometry, such as plain fin, slit fin, wavy fin, louvered fin, compounded fin, etc., on the heat transfer performance and frictional characteristic. On the other hand, there are only few researches on the crimped spiral fin-and-tube heat exchanger as found in[1–4].

Nuntaphan et al.[1]studied the air-side of crimped spiral fin heat exchanger to analyse the effect of tube diameter, fin spacing, transfer tube pitch, and tube arrangement and proposed correla-tions between heat transfer and friction characteristics in the case of low Reynolds numbers. Moreover, heat exchangers using crimped spiral finned tubes were investigated by Srisawad and Wongwises[2]who focused on the air-side performance of heli-cally coiled crimped spiral finned tube heat exchangers in dry-sur-face conditions. Pongsoi et al.[3]studied the effect of fin pitch on the air-side heat transfer characteristics of crimped spiral fin-tube heat exchangers having multipass parallel and counter cross-flow under sensible heating conditions and purpose the

e

–NTU relation equation for this new water flow arrangement. Tang et al.[4] stud-ied the air-side heat transfer and friction characteristics of five kinds of fin-and-tube heat exchangers i.e. crimped spiral fin, plain fin, slit fin, fin with delta-wing longitudinal vortex generators, and mixed fin. The number of tube rows (Nrow) was 12. The diameter of

tubes (do) was 18 mm. Reynolds number was varied from 4000 to

10,000. According to their results, although the crimped spiral fin gave high pressure drop, it provided higher air-side heat transfer performance than several types of heat exchangers.

According to these literatures, crimped spiral fin is proved to be quite reliable in industrial applications. The crimped spiral fin 0017-9310/$ - see front matter Ó 2011 Elsevier Ltd. All rights reserved.

doi:10.1016/j.ijheatmasstransfer.2011.09.064

⇑ Corresponding author at: Fluid Mechanics, Thermal Engineering and Multi-phase Flow Research Lab. (FUTURE), Department of Mechanical Engineering, King Mongkut’s University of Technology, Thonburi, Bangmod, Bangkok 10140, Thailand. Tel.: +66 24709115.

E-mail address:Somchai.won@kmutt.ac.th(S. Wongwises).

Contents lists available atSciVerse ScienceDirect

International Journal of Heat and Mass Transfer

j o u r n a l h o m e p a g e : w w w . e l s e v i e r . c o m / l o c a t e / i j h m t

(2)

features a sine-shaped fin which gives rise to a higher heat transfer rate on the air-side through the increase in the contact surface be-tween the fin base and tube. However, up to now, none of the experimental investigations found in the literature had reported the effect of the number of tube rows on the air-side performance of crimped spiral fin-and-tube heat exchangers. Upon the forego-ing studies, Nuntaphan et al.[1]is the only experimental work that examined the effect of fin geometry and tube arrangement on the

air-side performance of crimped spiral fin-and-tube heat

Nomenclature

Amin minimum free flow area, m2

Ao total surface area, m2

Ap cross-sectional or profile area of fin, m2

Al aluminium material

C⁄ capacity rate ratio, dimensionless

Cu copper material

f Fanning friction factor, dimensionless

Gc mass flux of the air based on minimum free flow area, kg/m2s

h heat transfer coefficient, W/(m2K)

j Colburn factor, dimensionless

NTU number of transfer units, dimensionless

Nu Nusselt number, dimensionless

Pr Prandtl number, dimensionless

DP pressure drop, Pa

Redo Reynolds number based on tube outside diameter (do)

U overall heat transfer coefficient, W/(m2K)

Vfr air frontal velocity, m/s

Vmax maximum velocity across heat exchanger, m/s

ec heat exchanger effectiveness for multipass counter

cross-flow

ep heat exchanger effectiveness for multipass parallel

cross-flow

epc heat exchanger effectiveness for multipass parallel and

counter cross-flow

g

f fin efficiency, dimensionless

/ combination of terms, dimensionless

Water inlet

= Frontal area, L H (mm) = Tube outside diameter (mm) = Longitudinal tube pitch (mm) = Transverse tube pitch (mm)

T L o fr P P d A × 2 Inlet Outlet L Water inlet Water outlet L= 340 mm H = 36 0 m m L P o d T P T P Water outlet Air flow Inlet Outlet Inlet Outlet Air flow Outlet Inlet L P

)

2

(

N

row

=

(

N

row

=

3

)

(

N

row

=

4

)

(

N

row

=

5

)

)

2

(

N

row

=

Fig. 1. Geometric details of multipass parallel-and-counter cross flow heat exchangers and water flow circuit inside the heat exchanger. Nrow= 2, 3, 4 and 5 ( and  signs

indicates that water flows into or out of the paper, respectively). Table 1

Experimental conditions.

Inlet-air-dry bulb temperature,oC 31.5 ± 0.5

Inlet-air frontal velocity, m/s 2–6 or Redo(3000–13,000)

Inlet-water temperature,o

C 55–70

(3)

exchangers. However, their tests were conducted at a very low air frontal velocity (0.5–1.5 m/s) which limited the applicability of the test results. In practice, especially in industrial service, the opera-tion velocity is normally much higher as reported by Xie et al.

[5]. Therefore, it is the main purpose of this study is to extend the applicable range (Vfr up to 6 m/s) of the crimped spiral

fin-and-tube heat exchangers subject to the influence of the number of tube rows and fin materials. Moreover, the test samples are of this study is of large diameter tubes (about 16 mm) which are very popularly used in ventilator and fan-coil units[6,7].

2. Data reduction

This present work is conducted by using the experimental appa-ratus of Wongwises and Chokeman[8], including the test section, air supply, water loop, instrumentation, and data acquisition. Air and hot water are used as working fluids. Detailed descriptions of the relevant components can be seen from the previous study.

In the experiment, the inlet water temperature and the water flow rate are fixed while varying the air flow rate. Tests are then conducted at the steady state with tested conditions being tabu-lated inTable 1.

The tests heat exchangers are of fin-and-tube configurations with copper tube being finned with either copper or aluminium.

The water-side circuitry arrangement and detailed dimensions of the tested fin-and-tube heat exchangers are shown inFig. 1. Photos of the crimped spiral fin pattern are shown inFig. 2. The geometric parameters of the heat exchangers are summarized in Table 2. Tests are performed under steady state condition, and the overall resistance can be obtained from the UA product of transfer units (

e

–NTU), yet the total resistance is the sum of the individual resis-tances as follows: 1 UA¼ 1 hiAi þlnðdo=diÞ 2

p

ktL þ 1

g

ohoAo ð1Þ The

e

–NTU relationships with one fluid mixed and one fluid un-mixed in cross-flow was employed to determine the overall heat transfer coefficient. From Fig. 1, the present mixed circuitry arrangement is a combination of parallel and counter cross-flow. Therefore, the

e

–NTU relationships developed by Pongsoi et al.

[3]is selected to calculate the heat exchanger effectiveness. This relation combines both effect of parallel and counter cross-flow configuration of water flow arrangement from[9–11], as shown in Eqs.(2)–(9):

For multipass parallel cross-flow with Nrow= 2, 3, 4 and 5: ðNrow¼ 2Þ;

e

P 1  K 2   1  e2K=C A   ; K ¼ 1  eNTUAðCA=2Þ ð2Þ

Fig. 2. The photos of the tested crimped spiral fin and tube heat exchangers and schematic diagram of crimped spiral fin.

Table 2

Detailed geometric parameters of the test samples.

No. Fin type di(mm) do(mm) df(mm) PL(mm) PT(mm) ft(mm) nt Nrow fp(mm) Fin material

1, 2 Crimped 13.5 16.35 35.0 35 40 0.5 9 3, 4 6.3 Cu

3–6 Crimped 13.5 16.35 35.0 35 40 0.5 9 2, 3, 4, 5 6.3 Al

df= outside diameter of fin; di= tube inside diameter; do= tube outside diameter; fp= fin pitch; ft= fin thickness; PL= longitudinal tube pitch; PT= transverse tube pitch;

(4)

ðNrow¼ 3Þ;

e

P¼ 1  1  K 2  2 e3K=C A  K 1 K 4þ K CA 1 K 2     eK=CA; K ¼ 1  eNTUAðCA=3Þ ð3Þ ðNrow¼ 4Þ;

e

P¼ 1  K 2 1  K 2þ K2 4 !  K 1 K 2   1 þ 2K C A 1 K 2     e2K=C A 1 K 2  3 e4K=C A; K ¼ 1  eNTUAðCA=4Þ

ð4Þ

ðNrow¼ 5 or 1Þ;

e

P¼1  e NTUAð1þCAÞ 1 þ CA ð5Þ For multipass counter cross-flow with Nrow= 2, 3, 4 and 5:

ðNrow¼ 2Þ;

e

c¼ 1  K 2þ 1  K 2   e2K=C A  1 ; K ¼ 1  eNTUAðCA=2Þ ð6Þ ðNrow¼ 3Þ;

e

c¼ 1  f 1  K 2  2 e3K=C A þ k K 1 K 4    1 K 2  K2 CA " # eK=C Ag1; K ¼ 1  eNTUAðCA=3Þ ð7Þ ðNrow¼ 4Þ;

ec

¼ 1  K 2 1  K 2þ K2 4 ! þ K 1 K 2   (  1  2K C A 1 K 2     e2K=C Aþ 1 K 2  3 e4K=C A )1 ; K ¼ 1  eNTUAðCA=4Þ ð8Þ

Fig. 3. Schematic diagram of the heat exchangers algorithm for multipass parallel cross flow, multipass counter cross flow and multipass parallel and counter cross-flow (Nrow= 2, 3, 4 and 5).

(5)

ðNrow¼ 5 or 1Þ;

e

c¼ 1  eNTUAð1CAÞ 1  C AeNTUAð1C  AÞ ð9Þ where C⁄= C

min/Cmaxis equal to Cc/Chor Ch/Ccdepending on the

va-lue of hot and cold fluid heat capacity rates

e

pc¼

e

e

C

2 for Nrow¼ 2; 3; 4 and 5 ð10Þ

The schematic diagram of circuitry arrangement for Nrow= 2, 3, 4

and 5 are shown inFig. 3.

The heat transfer performance is calculated by the method of Kays and London. Further details about the data reduction can be seen from Wongwises and Chokeman[8], The efficiency of a radial fin with rectangular profile is based on the derivation of Gardner

[12], i.e.,

g

f ¼ 2w /ð1 þ wÞ I1ð/RoÞK1ð/RiÞ  I1ð/RiÞK1ð/RoÞ I0ð/RiÞK1ð/RoÞ þ I1ð/RoÞK0ð/RiÞ ð11Þ where /¼ ðro riÞ3=2 2ho kfAp  1=2 ð12Þ Accordingly, the air-side heat transfer coefficient (ho) can be

cal-culated from Eq.(1). The air-side heat transfer characteristics of the heat exchanger are often in terms of dimensionless Colburn j factor: j ¼ Nu RedoPr 1=3¼ ho

q

aVmaxcPðPrÞ 2=3 ð13Þ

(6)

The frictional characteristics are termed with Fanning friction fac-tor, as depicted by Kays and London[13]:

f ¼ Amin Ao  

q

m

q

1   2

D

P

q

1 G2 c  1 þ

r

2

q

1

q

2  1   " # ð14Þ

where Gcis the mass flux of the air based on minimum free flow

area, Aois the total heat transfer area, Aminis the minimum free flow

area. The flow chart showing the reduction of the data is shown in

Fig. 4.

The experiments are conducted following the ANSI/ASHRAE 33 Standards[15] in which the energy un-balance between air and water of the crimped spiral fin-and-tube heat exchangers, denoting |Qa Qw|/Qave, is less than 0.05. The uncertainties are calculated

from the root mean sum square method, the maximum uncertain-ties are 3.5% for the Redo, 13.0% for the j-factor and 11.5% for

f-fac-tor. The uncertainties decreased as Reynolds number increased.

3. Results and discussion

In experiments, the analysis of air-side heat transfer and friction characteristics of all the heat exchangers examined are presented in terms of a dimensionless number including the Colburn factor (j) and friction factor (f) plotted against the Reynolds number (Redo)

and the Reynolds number based on the outside diameter of the tube. As expected, both the Colburn factor (j) and the friction factor (f) decrease an increasing Reynolds number.

Fig. 5shows the effect of the number of tube rows on the heat transfer and friction characteristic. The number of tube row of the heat exchangers are from 2 to 5. As can be seen inFig. 5, the num-ber of tube rows casts no significant effect on the Colburn factor (j) at high Reynolds numbers (3000–13,000). This phenomenon is similar to the plain fin data as reported by Rich[16] and Wang et al.[17]in which the effect of the number of tube rows dimin-ishes as the Reynolds number is increased over 2000. This is due to the downstream turbulence eddies shed from the tubes that Fig. 5. Effect of number of tube rows on the Colburn factor and friction factor of crimped spiral fin and tube heat exchangers.

(7)

cause good mixing in the downstream fin region. Moreover, the fact that the effect of the number of tube rows on the heat transfer characteristics vanishes for Reynolds numbers over 2000 can also be found in the works of[18–20]with fin-and-tube heat exchang-ers having wavy, louver and slit geometry, respectively. The data point inFig. 5 shows that the number of tube row (Nrow) does

not affect the friction factor (f) over the range of Reynolds numbers being examined.

For a comparison of the present test samples with previous studies, the Briggs and Young [21] correlation for circular fin-and-tube heat exchanger is chosen to compare with the present experimental results as illustrated inFig. 6. Note that the configu-Fig. 7. Effect of number of tube rows on the fin efficiency (a), heat transfer rate (b) and pressure drop (c) of crimped spiral fin and tube heat exchangers (Nrow= 2, 3, 4 and 5).

(8)

ration of circular fin is very similar to that of the tested crimped spiral fin. Therefore, the calculated Colburn factor (j) of circular fins reveals a similar trend and magnitude as the present crimped spir-al fins. Also, the Colburn factor (j) and friction factor (f) correlations of plain fin-and-tube heat exchangers, which is proposed by Wang and Chang[22]and Wang et al.[17], respectively, are selected to compare with the tested results. As shown inFig. 6, it is found that crimped spiral fins have a similar trend with the plain fins as well. However, due to the corrugated folding at the base of the present fin configuration, it appears that crimped spiral fins give a higher friction factor (f) than that plain fins at the same Reynolds number. Moreover, as shown inFig. 6, there is no significant effect of fin material on both the Colburn factor (j) and friction factor (f).

Fig. 7(a) illustrated the effect of the number of tube rows on the fin efficiency (

g

f) of both fin material. It can be seen that no

signif-icant effect of number of tube rows is found under the same exper-imental conditions. The reason may be explained by Eqs.(11) and (12), which show that an increase in the number of tube rows has no significant differences in terms of / and fin efficiency (

g

f) at the

same Reynolds number because the fin efficiency depends only on size, shape and material of fin. In the meantime, it can be clearly seen that the fin efficiency (

g

f) of the copper fin is higher than that

of aluminium fin due to a higher thermal conductivity of copper. Moreover, the heat transfer rate for both fins is shown in

Fig. 7(b). It seems that the heat transfer rate for copper fin only marginally higher than that of aluminium fin due to its very minor difference in fin efficiency. On the other hand, the number of tube rows had significant effect on average heat transfer rate at the same air frontal velocity.

A comparison of the results for the effect of the number of tube rows on the pressure drop of crimped spiral fin-and-tube heat exchangers is presented inFig. 7(c). As seen, the pressure drop in-creases with the frontal air velocity while the friction factor de-creases with increasing Reynolds number. It can be seen that the pressure drop for Nrow= 5 is two times higher than those for

Nrow= 2. The reason for this result can be explained by the increase

in the blocking flow area when Nrowis increased.

(9)

To determine the heat transfer coefficient of crimped spiral fin-and-tube heat exchangers, an empirical correlation between the Colburn factor (j) and the friction factor (f) is proposed in this work. The correlations may be valuable for industrial usage in order to design the heat exchangers operating at air flows of high Reynolds number.

An empirical correlation for j and f factors for crimped spiral fin-and-tube heat exchanger is developed in this work. The correlation also includes the experimental data used to study the effect of fin pitch as reported in Pongsoi et al.[3]. It must be noted that number of tube rows cast negligible influence on both j and f factors as fore-going discussions. As a result, the number of tube row is not in-cluded in the correlations. The test results are correlated as suggested by Wang et al. [23] in the form of j ¼ aReb

do and

f ¼ aReb

dowhere a and b are the empirical constants obtained from

least-square fitting of the experimental data. Furthermore, based on the data analysis, the f factor of crimped spiral fin-and-tube heat exchanger were also proportional to the fin pitch. Therefore, the present correlation for f factor is modified by including the dimensionless fin pitch (fp) normalized by the tube outside

diame-ter (do). The final correlation for the j and f factors takes the

follow-ing form: jcorr¼ 0:4132Re 0:4287 do ð15Þ fcorr¼ 0:3775Re0:1485do fp do  0:4321 ð16Þ Mean deviations ¼1 M XM 1 j

U

corr

U

expj

U

exp " #  100% ð17Þ

As shown inFig. 8, the proposed heat transfer and friction correla-tions Eqs.(15) and (16)can describe 95.04% and 91.07% of the j and f factors to be within ±10%, respectively. The mean deviations Eq.

(17) of the proposed heat transfer and friction correlations are 5.09% and 4.53%, respectively. However, Eq.(15) and (16)can be used only (Nrow= 2–5), (fp= 3.2–6.3 mm) when staggered arrangement.

4. Conclusion

This study has investigated the effect of number of tube rows on the air-side performance of crimped spiral fin and tube heat exchangers having multipass parallel and counter cross-flow under sensible heating conditions at high Reynolds number (3000– 13,000) based on the tube outside diameter. The following conclu-sions based on the tests are obtained:

– The number of tube rows cast a negligible influence on the air-side heat transfer performance at high Reynolds number (3000– 13,000). Moreover, it could be clearly seen that the airside per-formance is independent of fin material.

– The average heat transfer rate and pressure drop increase with increasing the number of tube rows.

– The correlation of Colburn factor (j) and friction factor (f) of crimped spiral fin-and-tube heat exchangers at high Reynolds number are proposed in this paper. The mean deviations of the proposed heat transfer and friction correlations are 5.09% and 4.53%, respectively.

Acknowledgments

The authors are indebted to the Thailand Research Fund and the National Research University Project for supporting this study. The third author also expresses gratitude for support funding from the National Science Council of Taiwan (99-2218-E-009-012-MY2). References

[1] A. Nuntaphan, T. Kiatsiriroat, C.C. Wang, Air side performance at low Reynolds number of cross-flow heat exchanger using crimped spiral fins, Int. Commun. Heat Mass Transfer 32 (1-2) (2005) 151–165.

[2] K. Srisawad, S. Wongwises, Heat transfer characteristics of a new helically coiled crimped spiral finned tube heat exchanger, Heat Mass Transfer 45 (4) (2009) 381–391.

[3] P. Pongsoi, S. Pikulkajorn, C.C. Wang, S. Wongwises, Effect of fin pitches on the air-side performance of crimped spiral fin-and-tube heat exchangers with a multipass parallel and counter cross-flow configuration, Int. J. Heat Mass Transfer 54 (9–10) (2011) 2234–2240.

[4] L.H. Tang, M. Zeng, Q.W. Wang, Experimental and numerical investigation on air-side performance of fin-and-tube heat exchangers with various fin patterns, Exp. Thermal Fluid Sci. 33 (2009) 818–827.

[5] G. Xie, Q. Wang, B. Sunden, Parametric study and multiple correlations on air-side heat transfer and friction characteristics of fin-and-tube heat exchangers with large number of large-diameter tube rows, Appl. Therm. Eng. 29 (1) (2009) 1–16.

[6] Y.C. Liu, S. Wongwises, W.J. Chang, C.C. Wang, Airside performance of fin-and-tube heat exchangers in dehumidifying conditions – data with larger diameter, Int. J. Heat Mass Transfer 53 (7-8) (2010) 1603–1608.

[7] C.C. Wang, J.S. Liaw, B.C. Yang, Airside performance of herringbone wavy fin-and-tube heat exchangers – data with larger diameter tube, Int. J. Heat Mass Transfer 54 (5–6) (2011) 1024–1029.

[8] S. Wongwises, Y. Chokeman, Effect of fin pitch and number of tube rows on the air side performance of herringbone wavy fin and tube heat exchangers, Energy Convers. Manage. 46 (13–14) (2005) 2216–2231.

[9] ESDU 86018, Effectiveness-NTU Relations for the Design and Performance Evaluation of two-stream heat exchangers, Engineering Science Data Unit 86018 with Amendment, London ESDU International plc, 1991, pp. 92–107. [10] H.A. Navarro, L. Cabezas-Gomez, A new approach for thermal performance

calculation of cross-flow heat exchanger, Int. J. Heat Mass Transfer 48 (18) (2005) 3880–3888.

[11] L. Cabezas-Gomez, H.A. Navarro, J.M. Saiz-Jabardo, Thermal performance of multipass parallel and counter-cross-flow heat exchangers, J. Heat Transfer 129 (3) (2007) 282–290.

[12] K.A. Gardner, Efficient of extended surface, ASME Trans. 67 (1945) 621. [13] W.M. Kays, A. London, Compact Heat Exchangers, third ed., McGraw-Hill, New

York, 1984.

[14] V. Gnielinski, New equation for heat and mass transfer in turbulent pipe and channel flow, Int. Chem. Eng. 16 (1976) 359–368.

[15] ANSI/ASHRAE Standard 33-2000, Method of Testing Forced Circulation Air Cooling and Air Heating Coils, 2000.

[16] D.G. Rich, The effect of the number of tube rows on heat transfer performance of smooth plate fin-and-tube heat, ASHRAE Trans. 81 (1) (1975) 307–317. [17] C.C. Wang, Y.J. Chang, Y.C. Hsieh, Y.T. Lin, Sensible heat and friction

characteristics of plate fin-and-tube heat exchangers having plane fins, Int. J. Refrig. 19 (4) (1996) 223–230.

[18] C.C. Wang, W.L. Fu, C.T. Chang, Heat transfer and friction characteristics of typical wavy fin-and-tube heat exchangers, Exp. Thermal Fluid Sci. 14 (2) (1997) 174–186.

[19] C.C. Wang, K.-Y. Chi, Y.-J. Chang, Y.-P. Chang, An experimental study of heat transfer and friction characteristics of typical louver fin-and-tube heat exchangers, Int. J. Heat Mass Transfer 41 (4-5) (1998) 817–822.

[20] Y.J. Du, C.C. Wang, An experimental study of the airside performance of the superslit fin-and-tube heat exchangers, Int. J. Heat Mass Transfer 43 (24) (2000) 4475–4482.

[21] D.E. Briggs, E.H. Young, Convective heat transfer and pressure drop of air flowing across triangular pitch banks of finned tubes, Chem. Eng. Prog. Symp. Ser. 59 (41) (1963) 1–10.

[22] C.C. Wang, C.T. Chang, Heat and mass transfer for plate fin-and-tube heat exchangers, with and without hydrophilic coating, Int. J. Heat Mass Transfer 41 (20) (1998) 3109–3120.

[23] C.C. Wang, K.Y. Chi, C.J. Chang, Heat transfer and friction characteristics of plain fin-and-tube heat exchangers: Part II. Correlation, Int. J. Heat Mass Transfer 43 (15) (2000) 2693–2700.

數據

Fig. 2. The photos of the tested crimped spiral fin and tube heat exchangers and schematic diagram of crimped spiral fin.
Fig. 3. Schematic diagram of the heat exchangers algorithm for multipass parallel cross flow, multipass counter cross flow and multipass parallel and counter cross-flow (N row = 2, 3, 4 and 5).
Fig. 4. Flowchart of the data reduction for air-side heat transfer performance (j-factor)
Fig. 5 shows the effect of the number of tube rows on the heat transfer and friction characteristic
+2

參考文獻

相關文件

Define instead the imaginary.. potential, magnetic field, lattice…) Dirac-BdG Hamiltonian:. with small, and matrix

Monopolies in synchronous distributed systems (Peleg 1998; Peleg

The Model-Driven Simulation (MDS) derives performance information based on the application model by analyzing the data flow, working set, cache utilization, work- load, degree

 name common laboratory apparatus (e.g., beaker, test tube, test-tube rack, glass rod, dropper, spatula, measuring cylinder, Bunsen burner, tripod, wire gauze and heat-proof

Microphone and 600 ohm line conduits shall be mechanically and electrically connected to receptacle boxes and electrically grounded to the audio system ground point.. Lines in

The min-max and the max-min k-split problem are defined similarly except that the objectives are to minimize the maximum subgraph, and to maximize the minimum subgraph respectively..

An integrated photovoltaic /thermal (PV/T) air collector to collect hot air and drive air flow, and mixing the air flow from earth-air heat exchanger (EAHE) and hot air flow to

Results of this study show: (1) involvement has a positive effect on destination image, and groups with high involvement have a higher sense of identification with the “extent