• 沒有找到結果。

4 CPU DIRECT CONNECTION

4.2 Connection Cables

(1) Connection with FX CPU

This section gives the connection diagrams and connectors of the RS-232C cables which are used to connect the GOT and FX CPU.

(a) Connection diagram

(b) Connector and connector cover

• GOT connector

• FX CPU connector

Use the connector compatible with the function extension board or link interface module.

(c) Precautions for cable preparation

The cable must be 15 m (49.21 feet) or shorter.

Description Model Manufacturer

Connector 17JE-13090-02(D1) DDK, Ltd.

Connector cover 17JE-09H-1C4 DDK, Ltd.

RXD TXD RTS CTS DSR SG DTR

RXD TXD RTS CTS DSR SG DTR FXCPU Side

Signal name Pin No. Signal name Pin No.

GOT Side Cable connection and direction of signal

2 3 7 8 6 5 4 2

3 7 8 6 5 4

4.2 Connection Cables 4 - 12

CPU DIRECT CONNECTION

5

COMPUTER LINK CONNECTION

6

MELSECNET CONNECTION (DATA LINK SYSTEM)

7

MELSECNET CONNECTION (NETWORK SYSTEM)

8

CC-LINK CONNEC- TION (INTELLIGENT DEVICE STATION)

(2) Connection with MELDAS C6/C64

The RS-232C cable connection diagram and the connector for the MELDAS C6/C64 and the GOT are as follows

For details, refer to the manual of the MELDAS C6/C64 used.

(a) Connection diagram

(b) Connector

MELDAS C6/C64 connector

GOT connector

(c) Precautions for cable preparation

The cable must be 15 m (49.21 feet) or shorter.

Item Description

Connector 10120-3000VE(Manufactured by Sumitomo 3M) Connector cover 10320-52F0-008(Manufactured by Sumitomo 3M)

Description Model Manufacturer

Connector 17JE-13090-02(D1) DDK, Ltd.

Connector cover 17JE-09H-1C4 DDK, Ltd.

6 16 18

1

Signal name Pin No. Pin No. Signal name

GOT Side Cable connection and direction of signal

MELDAS C6/C64 side

1

4 - 13 4.3 About Transparent Function (2-Port Interface Function) 4.3.1 About software used

4.3 About Transparent Function (2-Port Interface Function)

When the GOT is connected directly with the Q/QnA/A/FX/motion controller CPU, MELDAS, connecting a peripheral device such as a personal computer allows you to read, write and monitor the sequence programs of the CPU.

4.3.1 About software used

The software programs usable change with the CPU connected to the GOT.

Refer to the following table and use the software programs compatible with the connected CPU.

Connected PLC CPU Usable software

QCPU (Q mode) SW D5C-GPPW-E, SW D5F-GPPW-E

QnACPU SW D5C-GPPW-E, SW D5F-GPPW-E, SW IVD-GPPQ, SW IWC-MEDOC-E

QCPU (A mode), ACPU SW D5C-GPPW-E, SW D5F-GPPW-E, SW IVD-GPPA, SW IWC-MEDOC-E

FXCPU SW D5C-GPPW-E, SW D5F-GPPW-E, SW PC-FXGP/WIN,

SW IWC-MEDOC-E

Motion controller CPU (A series)

DOS version

SW2SRX-GSV13P, SW2SRX-GSV22P, SW2SRX-GSV43P, SW2SRX-GSV51P Windows version

SW3RN-GSV13P, SW3RN-GSV22P, SW3RN-GSV43P, SW3RN-GSV51P Motion controller CPU

(Q series) SW6RNC-GSVSET-E, SW6RNC-GSVPRO-E

MELDAS C6/C64 SW D5C-GPPW-E, SW D5F-GPPW-E, SW IVD-GPPQ, SW IWC-MEDOC-E Sequence programs can be read/written.

RS-232C/RS-422 cable RS-232C cable

4.3 About Transparent Function (2-Port Interface Function)

4.3.2 Instructions for using the transparent function 4 - 14

OVERVIEW

2

SPECIFICATION

3

BUS CONNECTION

4

CPU DIRECT CONNECTION

5

COMPUTER LINK CONNECTION

6

MELSECNET CONNECTION (DATA LINK SYSTEM)

7

MELSECNET CONNECTION (NETWORK SYSTEM)

8

CC-LINK CONNEC- TION (INTELLIGENT DEVICE STATION)

4.3.2 Instructions for using the transparent function

(1) Connect a peripheral device such as a personal computer to the RS-232C interface of the GOT.

(2) Only one of the bar code function, servo amplifier monitor function and transparent function can be used.

The following table indicates the priorities of the functions.

High Priority Low

The transparent function cannot be used when there is bar code setting in the monitor screen data or the extended function OS for servo amplifier monitor function has been installed in the GOT.

When there is bar code setting, delete the setting using GT Designer2.

When the extended function OS for servo amplifier monitor function has been installed, delete the extended function OS.

(3) When connecting the GOT with the QCPU (A mode), refer to the QCPU (A mode) User's Manual for the GPP function software package and the startup-time type setting (PLC type).

(4) A communication error will occur if GT Designer of SW4D5C-GOTR-PACKE Version F or earlier is used to communicate with the GOT where the basic function OS and PLC communication driver of SW5D5C-GOTR-PACKE Version A or later have been installed.

If a communication error occurs, perform the same operation again. (A communication error occurs at the first time only.)

Bar code function Servo amplifier monitor function Transparent function

There is bar code setting in the monitor screen data.

The extended function OS for servo amplifier monitor function has been installed in the GOT.

No setting items

4 - 15 4.3 About Transparent Function (2-Port Interface Function) 4.3.2 Instructions for using the transparent function

(5) The following cautions should be observed when using transparent function.

(a) Conditions transparent function will not work

The transparent function may not work if the following inoperable conditions are all met and further GX Developer is started with the RS-232C cable connected between the personal computer and GOT.

However, it will work if only one condition has not realized. (For example, it will work when the CPU to be monitored is QCPU.)

(b) Countermeasures

Either of the following countermeasures allows transparent function to work normally.

1) Use an RS-232C cable of Version A or later.

2) For the cable whose Version is neither A nor later, reconnect it after disconnecting.

(c) How to verify the cable version

The RS-232C cables of Version A or later have the version number inscribed at the upper right of the model name marked on the connector.

(6) The following cautions items should be observed if the monitor conditions are set by GX Developer.

(a) The GOT monitor will stop.

(b) Operation by a touch switch or input by the numerical/ASCII input function cannot be performed.

(c) "315 Device write error" is displayed in the display field of the alarm list display (system alarm) function.

(d) Do not perform any operation that requires GOT restarting (downloading project data, changing utility or others) while setting a monitor condition.

If any operation above is performed, a system alarm of "402 Communication timeout." may be displayed on restarting the GOT.

In the case that a registered monitor condition for a PLC CPU cannot be canceled, reconnect the GX Developer to the PLC CPU to cancel the monitor condition setting. (An error may occur on canceling a monitor condition setting.)

Item Conditions transparent function will

not work Remarks

CPU module to be

monitored ACPU Not applicable to QnACPU or QCPU.

RS 232C cable AC30R2-9SS or AC30R2-9P of Version A or later is used.

Not applicable to AC30R2-9SS or AC30R2-9P of Version A or later.

4.3 About Transparent Function (2-Port Interface Function)

4.3.2 Instructions for using the transparent function 4 - 16

OVERVIEW

CPU DIRECT CONNECTION

5

COMPUTER LINK CONNECTION

6

MELSECNET CONNECTION (DATA LINK SYSTEM)

7

MELSECNET CONNECTION (NETWORK SYSTEM)

8

CC-LINK CONNEC- TION (INTELLIGENT DEVICE STATION)

(e) If the time check period of GX Developer is set to 30 seconds or longer in the monitor condition setting, "402 Communication time-out" is displayed in the display field of the alarm list display (system alarm) function.

In this case, change the time check period of GX Developer to shorter than 30 seconds.

(7) When executing PLC Write to a PLC CPU using the transparent function, the writing may be failed due to a cable disconnection or other reasons.

In the case above, retry PLC Write from the personal computer that has failed the PLC Write or reset the PLC CPU.

(8) If the following GOT functions are used when connecting with a QCPU (Q mode), an error may occur in a GOT or GX Developer.

The following lists the errors that may occur and their handling procedures.

(9) When the PLC CPU is monitored by a peripheral device such as a personal computer, the display speed of the GOT decreases.

(10) For 45 seconds after exit from GX Developer, the GOT remains at the same monitor speed as during use of the transparent function.

(11) The access range of GX Developer does not change when the transparent function is used.

GOT function Error message of GOT Handling on GOT side Error message of GX Developer

Handling on GX Developer side

Execute ladder read with

the ladder monitor function. FILE NOT FOUND

Execute ladder read again when "PLC Read" or "PLC Write" is not being executed by GX Developer.

File access failure. Please try again.

Execute "PLC Read" or

"PLC Write" again when ladder read is not being executed with the ladder monitor function of a GOT.

Execute device value read/

write by specifying the file register name of the recipe function.

358 File of PLC access fail-ure

Turn ON the trigger device of the recipe function again when "PLC Read" or "PLC Write" is not being executed by GX Developer.

File access failure. Please try again.

Execute "PLC Read" or

"PLC Write" again when the recipe in-process signal in the system information of a GOT is OFF.

PLC file system error.

Unable to communicate with PLC.

Execute TC monitor read with the system monitor function.

The message does not appear.

"TC Setting" area is empty.

Execute TC monitor read again when "PLC Read" or

"PLC Write" is not being executed by GX Developer.

File access failure. Please try again.

Execute "PLC Read" or

"PLC Write" again when the TC monitor screen is not being read.

Execute to read the PC diagnosis monitor screen/

unit detailed information screen with the special unit monitor function.

Can’t Communication

Execute to read the PC diagnosis monitor screen/

unit detailed information screen again when "PLC Read" or "PLC Write" is not being executed by GX Developer.

File access failure. Please try again.

Execute "PLC Read" or

"PLC Write" again when the PC diagnosis monitor screen/unit detailed information screen is not being read with the special unit monitor function.

4 - 17 4.3 About Transparent Function (2-Port Interface Function) 4.3.2 Instructions for using the transparent function

(12) If the either of following operations, which will stop the monitoring of the GOT, is performed, the transparent function will stop.

(a) Monitor screen data is downloaded or uploaded using GT Designer2, or OS or ROM_BIOS is installed. *1

(b) Setup or screen & OS copy is executed on the GOT unit. *1

(c) When no communication request (online monitor, etc.) has been issued from GX Developer for 45 seconds.

*1 A time-out error will occur on GX Developer.

When the option function such as the utility or ladder monitor function is executed, the transparent function will not stop.

(13) When using multiple software run on a personal computer, the communication using the transparent function is enabled for one software only.

Do not perform multiple communications using the transparent function at the same time. (The offline operation is enabled for each software.)

In addition, do not perform communication from the GT Designer2 to the GOT (downloading project data, etc.) during communication using the transparent function.

(14) When connecting to the FXCPU, set the transmission speed of the GX Developer to 9600bps.

Otherwise, the transparent function will not operate.

4.3 About Transparent Function (2-Port Interface Function)

4.3.3 Compatible RS-232C cable 4 - 18

OVERVIEW

CPU DIRECT CONNECTION

5

COMPUTER LINK CONNECTION

6

MELSECNET CONNECTION (DATA LINK SYSTEM)

7

MELSECNET CONNECTION (NETWORK SYSTEM)

8

CC-LINK CONNEC- TION (INTELLIGENT DEVICE STATION)

4.3.3 Compatible RS-232C cable

Use any of the following types of RS-232C cables for connection of the personal computer and GOT.

*1 9-25 pin converter (introduced product: D232J31 of Diatrend make) is required.

*2 When connecting to a motion controller CPU, the usable RS-232C cable varies depending on the software.

The following shows RS-232C cables usable for respective software.

The RS-232C cable for connection of the personal computer and GOT may also be fabricated by the user.

The connection diagrams and connectors for the RS-232C cables are indicated below.

(1) Connection diagram

(a) Connection diagram of AC30R2-9SS, FX-232CAB-1

• AC30R2-9SS • FX-232CAB-1

• AC30R2-9P *1 • F2-232CAB-1 *1

• AC30N2A *1 • FX-232CAB-2 *1

Type Software used Usable cable

Motion controller CPU (A series)

DOS version

SW2SRX-GSV13P, SW2SRX-GSV22P, SW2SRX-GSV43P, SW2SRX-GSV51P

User-fabricated cable (Refer to Section 4.3.3 (1) (d).)

Windows version

SW3RN-GSV13P, SW3RN-GSV22P,

SW3RN-GSV43P, SW3RN-GSV51P AC30R2-9SS, AC30R2-9P, AC30N2A, FX-232CAB-1, F2-232CAB-1 Motion controller

CPU (Q series)

SW6RNC-GSVSET-E,

Signal name Pin No. Signal name Pin No.

GOT Side Cable connection and direction of signal

2

4 - 19 4.3 About Transparent Function (2-Port Interface Function) 4.3.3 Compatible RS-232C cable

(b) Connection diagram of AC30R2-9P, F2-232CAB-1

(c) Connection diagram of AC30N2A

(d) When using the software (DOS version) for motion controller CPU (A series)

*1 This RS-232C cable should not be used to transfer the monitor screen data of GT Designer2.

(2) Connector and connector cover

• GOT connector

Use the screw-in type connector (inch) for the GOT side.

• Personal computer connector

Use the connector compatible with the Personal computer.

(3) Precautions for cable preparation

The cable must be 15 m (49.21 feet) or shorter.

RXD

Signal name Pin No. Signal name Pin No.

GOT Side Cable connection and direction of signal

2

Signal name Pin No. Signal name Pin No.

GOT Side Cable connection and direction of signal

2

Signal name Pin No. Signal name Pin No.

GOT Side Cable connection and direction of signal

2

5.1 System Configurations

5.1.1 Connection with QCPU (Q mode) 5 - 1

OVERVIEW

2

SPECIFICATION

3

BUS CONNECTION

4

CPU DIRECT CONNECTION