• 沒有找到結果。

Wiring the S7-400

5.3 Rules for Configuring a Network

Rules

Observe the following rules for connecting the nodes of a network:

• Before you interconnect the individual nodes of the network, you must assign to each node the MPI address and the highest MPI address or PROFIBUS-DP address.

Tip: Mark the address of each node in a network on the housing. To do this, use the adhesive labels enclosed with the CPU. You can then always see which address is assigned to which node in your plant.

• Before you insert a new node in the network, you must switch off its supply voltage.

• Connect all the nodes in the network in a row. In other words, include the fixed programming devices and operator panels directly in the network.

Only use spur lines for connecting the programming devices / OPs to the network which are needed for startup or maintenance.

• If you operate more than 32 nodes in a PROFIBUS-DP network, you must connect the bus segments via RS 485 repeaters.

In a PROFIBUS-DP network, all bus segments together must have at least one DP master and one DP slave.

• You connect ungrounded bus segments and grounded bus segments via RS 485 repeaters (see Reference Manual CPU Data, Chapter 10).

• The maximum number of nodes per bus segment decreases with each RS 485 repeater. This means that if there is an RS 485 repeater in a bus segment, there may only be a maximum of 31 other nodes in a bus segment.

However, the number of RS 485 repeaters has no effect on the maximum number of nodes on the bus.

Up to ten segments can be connected in series.

• Switch on the terminating resistor at the first and last node of a segment.

To ensure the bus operates without interference, you should not switch off these nodes.

长沙工控帮教育科技有限公司整理

Networking

5-8 Automation System S7-400 Hardware and Installation

A5E00850741-01

Data Packets in the MPI Network

Observe the following feature in the MPI network:

Note

If you connect an additional CPU to the MPI network during operation, data may be lost.

Remedy:

1. Disconnect power from the nodes to be connected.

2. Connect the nodes to the MPI network.

3. Switch on the nodes.

Recommendation for MPI Addresses

Reserve MPI address “0” for a service programming device and “1” for a service OP, which will later be briefly connected to the MPI network as required. Thus you assign different MPI addresses to the programming devices / OPs incorporated in the MPI network.

Reserve MPI address “2” for a new CPU. You thus avoid the duplication of MPI addresses after a CPU with a default setting has been installed in the MPI network (for example, when replacing a CPU). Thus you assign an MPI address higher than

“2” to all CPUs in the MPI network.

Recommendation for PROFIBUS-DP Addresses

Reserve PROFIBUS-DP address “0” for a service programming device, which will later be briefly connected to the PROFIBUS-DP network as required. Thus you assign other PROFIBUS-DP addresses to all the programming devices

incorporated in the PROFIBUS-DP network.

Components

You connect the individual nodes via bus connectors and the PROFIBUS-DP bus cable. Remember to provide a bus connector with PG female port for nodes into which a programming device may be plugged if required.

Use RS 485 repeaters for the connection between segments and for extending the cable.

长沙工控帮教育科技有限公司整理

Networking

Automation System S7-400 Hardware and Installation 5-9

A5E00850741-01

Terminating Resistor on the Bus Connector

on off on

off

Terminating resistor switched on

Terminating resistor switched off

Figure 5-3 Terminating resistor on bus connector

Terminating Resistor on the RS 485 Repeater

DC24 V

L+ M PE M 5.2

A1 B1 A1 B1

A2 B2A2 B2 SIEMENS RS 485-REPEATER

ON

ON Terminating resistor for bus segment 1

Terminating resistor for bus segment 2

Figure 5-4 Terminating resistor on RS 485 repeater

长沙工控帮教育科技有限公司整理

Networking

5-10 Automation System S7-400 Hardware and Installation

A5E00850741-01

Example: Terminating Resistor in the MPI Network

The figure below shows where you have to connect the terminating resistor in a possible configuration for an MPI network.

RS 485 repeater {

{

{

{ Terminating resistor switch on

S7-400 S7-400

S7-400

Spur line

S7-300



OP OP

PG

Programming device

Figure 5-5 Terminating resistor on MPI network

长沙工控帮教育科技有限公司整理

Networking

Automation System S7-400 Hardware and Installation 5-11

A5E00850741-01

Example of an MPI Network

* Only connected via spur line for startup/maintenance (with default MPI address)

** Connected to the MPI later on (with default MPI address) 0 ... x MPI address of nodes

{ Terminating resistor switch on

S7-400** S7-400 S7-400 S7-400

S7-400 S7-400

0

11 10 9 8 7

1

2 3 4 5 6

OP OP

OP** PG

{ {

S7-300

Programming device

Figure 5-6 Example of an MPI network

长沙工控帮教育科技有限公司整理

Networking

5-12 Automation System S7-400 Hardware and Installation

A5E00850741-01

Example of a PROFIBUS-DP Network

0 ... x PROFIBUS DP addresses of nodes S7-400 with

CPU 414-2-DP

as DP master ET 200M

0 8 7 6

1 2 3 4 5

PG*

OP

ET 200M PG S5-95U

ET 200B ET 200B

{

{

{ Terminating resistor switched on

* Only connected via spur line for startup/maintenance (with default PROFIBUS-DP address = 0)

Figure 5-7 Example of a PROFIBUS DP network

长沙工控帮教育科技有限公司整理

Networking

Automation System S7-400 Hardware and Installation 5-13

A5E00850741-01

Example Using a CPU 414-2

The figure below shows an example of a configuration with CPU 414-2 DP which is integrated in an MPI network and simultaneously used as DP master in a

PROFIBUS-DP network.

In both networks, the node numbers can be assigned separately without conflicts resulting.

OP S7-400

S7-400 with CPU 414-2 as

DP master ET 200M

ET 200B

* Only connected via spur line for startup/maintenance { Terminating resistor switched on

MPI network PROFIBUS-DP network

Figure 5-8 Example with CPU 414-2

长沙工控帮教育科技有限公司整理

Networking

5-14 Automation System S7-400 Hardware and Installation

A5E00850741-01

Programming Device Access Beyond Network Limits (Routing)

You can access all modules beyond network limits using a programming device.

ET 200

PROFIBUS-DP network 2

Programming device / PC 2 Programming device / PC 3

Programming device / PC 1

MPI network 1

S7-400 with CPU 417 S7-400 with

CPU 416

S7-300 with CPU 318

S7-300 with CPU 318 MPI network 3

Figure 5-9 Programming device access beyond network limits Requirements :

• Use STEP 7 from version 5.0 onwards

• Assign STEP 7 to a programming device or PC on the network (SIMATIC Manager, Assign programming device/PC)

• The network limits are bridged by modules with routing capability.

长沙工控帮教育科技有限公司整理

Networking

Automation System S7-400 Hardware and Installation 5-15

A5E00850741-01

相關文件