• 沒有找到結果。

This chapter describes the performance specifications of the MELSECNET or MELSECNET/B data link system and the local module.

For the general specifications, refer to the QCPU User's Manual (Hardware Design, Maintenance and Inspection).

(1) Performance specifications of MELSECNET data link system and A1SJ71AP23Q

Table 2.1 Performance specifications of MELSECNET data link system and A1SJ71AP23Q

Item

Specifications MELSECNET data link system MELSECNET

mode MELSECNET II

mode MELSECNET II

composite mode Maximum

applicable link points per station

Input (X) Up to the maximum number of I/O points for the CPU module used in the master station is applicable.

(The total number of link points for slave station is equal to the number of link using points for the master station)

Output (Y)

Maximum link points in a system

B 1024 points

(128 byte) 4096 points (512 byte)

W 1024 points

(2048 byte) 4096 points (8192 byte)

Maximum link points per station

Master

station 1024 byte 1024 byte (First half of link parameters) 1024 byte (Latter half of link parameters) Local station

Remote I/O station

512 byte Number of I/O points: 512 points

-512 byte Number of I/O points: 512 points Communication speed 1.25Mbps

Communication method Half duplex bit serial method Synchronization method Frame synchronization method Transmission path Duplex loop

Overall cable distance Up to 10km (Station-to-station 1km) Number of connected

stations

Up to 65 (Master station: 1, The total number of local stations and remote I/O stations: 64)

Modulation method CMI method

Transmission format Conforming to HDLC (Frame format)

Error control system Retries due to CRC (generating polynomial X16+X12+X5+1) and time out

RAS function

• Loopback function due to error detection and cable break

• Diagnostic function including link line check of host station etc.

Connector 2-core optical connector plug (User prepared*1) Applicable cable Optical fiber cable (User prepared*1) Number of I/O occupied

points 32 points (Intelli: 32 points)

*1 Connecting an optical fiber cable with a connector requires professional skills and special tools. Also, a connector dedicated to an optical fiber cable is required.

For purchase, contact your local Mitsubishi Electric System Service or representative.

Internal current consumption

(5VDC) 0.33A

Weight 0.30kg

Table 2.1 Performance specifications of MELSECNET data link system and A1SJ71AP23Q(Continued)

Item

Specifications MELSECNET data link system MELSECNET

mode

MELSECNET II mode

MELSECNET II composite mode

(2) Performance specifications of MELSECNET data link system and A1SJ71AR23Q

Table 2.2 Performance specifications of MELSECNET data link system and A1SJ71AR23Q

Item

Specifications MELSECNET data link system MELSECNET

mode MELSECNET II

mode MELSECNET II

composite mode Maximum

applicable link points per station

Input (X) Up to the maximum number of I/O points for the CPU module used in the master station is applicable.

(The total number of link points for slave station is equal to the number of link using points for the master station)

Output (Y)

Maximum link points in a system

B 1024 points

(128 byte) 4096 points (512 byte)

W 1024 points

(2048 byte) 4096 points (8192 byte)

Maximum link points per station

Master

station 1024 byte 1024 byte (First half of link parameters) 1024 byte (Latter half of link parameters) Local station

Remote I/O station

512 byte Number of I/O points: 512 points

-512 byte Number of I/O points: 512 points Communication speed 1.25Mbps

Communication method Half duplex bit serial method Synchronization method Frame synchronization method Transmission path Duplex loop

Overall cable distance Up to 10km (Station-to-station 500m) Number of connected

stations

Up to 65 (Master station: 1, The total number of local stations and remote I/O stations: 64)

Modulation method CMI method

Transmission format Conforming to HDLC (Frame format)

Error control system Retries due to CRC (generating polynomial X16+X12+X5+1) and time out

RAS function

• Loopback function due to error detection and cable break

• Diagnostic function including link line check of host station etc.

Connector

Connector plug for 3C-2V (User prepared):

• BNC-P-3-NiCAu-CF (DDK Ltd.) Connector plug for 5C-2V (User prepared):

• BNC-P-5-NiCAu-CF (DDK Ltd.)

• BNC-P-5DV SA(41) (HIROSE ELECTRIC CO., LTD.) Applicable cable Cables equivalent to 3C-2V or 5C-2V (User prepared) Number of I/O occupied

points 32 points (Intelli: 32 points) Internal current consumption

(5VDC) 0.80A

Weight 0.33kg

(3) Performance specifications of MELSECNET/B data link system and A1SJ71AT23BQ

Table 2.3 Performance specifications of MELSECNET/B data link system and A1SJ71AT23BQ

Item

Specifications MELSECNET/B data link system MELSECNET

mode MELSECNET II

mode MELSECNET II

composite mode Maximum

applicable link points per station

Input (X) Up to the maximum number of I/O points for the CPU module used in the master station is applicable.

(The total number of link points for slave station is equal to the number of link using points for the master station)

Output (Y)

Maximum link points in a system

B 1024 points

(128 byte) 4096 points (512 byte)

W 1024 points

(2048 byte) 4096 points (8192 byte)

Maximum link points per station

Master

station 1024 byte 1024 byte (First half of link parameters) 1024 byte (Latter half of link parameters) Local station

Remte I/O station

512 byte Number of I/O points: 512 points

-512 byte Number of I/O points: 512 points Communication speed 125kbps/250kbps/500kbps/1Mbps

Communication method Half duplex bit serial method Synchronization method Frame synchronization method Transmission path Bus method

Overall cable distance

Changed due to communication speed

(125kbps: 1200m, 250kbps: 600m, 500kbps: 400m, 1Mbps:

200m) Number of connected

stations

Up to 32 (Master station: 1, The total number of local stations and remote I/O stations: 31)

Modulation method NRZI method

Transmission format Conforming to HDLC (Frame format)

Error control system Retries due to CRC (generating polynomial X16+X12+X5+1) and time out

RAS function Diagnostic function including link line check of host station etc.

Connector Terminal block

Applicable cable Shielded twisted pair cable (User prepared) Number of I/O occupied

points 32 points (Intelli: 32 points) Internal current consumption

(5VDC) 0.66A

Weight 0.22kg

Remarks

Overall cable distance

(1) MELSECNET data link system

The overall cable distance refers to a distance from OUT of the master station to IN of the master station via a slave station.

(2) MELSECNET/B data link system

The overall cable distance refers to a distance between stations at both ends.

The overall cable distance of the MELSECNET/B data link system is determined depending on communication speed.

The communiation speed is set by the communication speed setting switch of each link module.

Figure 2.1 Overall cable distance of MELSECNET

Table 2.4 Communication speed and overall cable distance Communication speed Overall cable distance

125kbps 1200m

250kbps 600m

500kbps 400m

1Mbps 200m

Figure 2.2 Overall cable distance of MELSECNET/B

L3 R4 R5 L6

M L1

R2 MELSECNET

Overall cable distance of MELSECNET

Overall cable distance of MELSECNET/B

L3

M L1 L2