Outline of the system configuration
C200H SYSMAC Support Software
CX-Programmer
CX-Programmer
The table below lists the models of C200H-series and each corresponding models of CS1-series. Select the CS1-series model which is compatible with the C200H-series model. Or, select the CS1-series model with similar specification to the C200H-series Unit.
Refer to the CS1G/H-CPU
□□H/CS1G/H-CPU□□-EV1 CS SERIES CPU UNITS OPERATIAN MANUAL (Cat. No.W339) for details of the Units.
< CPU Units and Power Supply Units >
Unit name C200H-series CS1-series Description
CPU Units C200H-CPU01
C200H-CPU02 C200H-CPU03 C200H-CPU21 C200H-CPU22 C200H-CPU23
CS1G-CPU42H UM 10K steps
CPU Unit-mounting Host Link Units
C120-LK201(RS232C) C120-LK202(RS422)*1
Built-in Host Link port (*) To replace C120-LK202, use a NT-AL001 to convert RS232C into RS422.
Power Supply Units (For C200H-CPU01/02/21/22) C200HW-PA204 (AC Power Supply Unit)
To use RUN output, prepare Output Unit separately.
C200HW-PA204S (AC Power Supply Unit)
With 24 VDC service power supply
To use RUN output, prepare Output Unit separately.
C200HW-PA204C (AC Power Supply Unit)
With maintenance forecast monitor.
C200HW-PA204R (AC Power Supply Unit)
With RUN output.
C200HW-PA209R (AC Power Supply Unit)
With RUN output.
(For C200H-CPCPU03/23) C200HW-PD024(DC Power Supply Unit)
To use RUN output, prepare Output Unit separately.
C200HW-PD025(DC Power Supply Unit)
To use RUN output, prepare Output Unit separately.
CPU Backplanes C200H-BC031(-□□) C200H-BC051(-□□)
Respectively for 3, 5, 8, and 10 slots.
The installation hole position is the same.
Memory Cassette
Unit name C200H-series CS1-series Description
Memory Unit Memory Unit (RAM type) C200H-MR431
(Battery type, with clock function)
C200H-MR833
(Battery type, with clock function)
None The CS Series CPU Units have a nonvolatile memory for user program in it. The memory unit is unnecessary.
They also have the clock function.
EEP ROM Unit C200H-ME431 C200H-ME432
(with clock function) C200H-ME831 C200H-ME832
(with clock function)
None The CS Series CPU Units have a nonvolatile memory for user program in it. The memory unit is unnecessary.
They also have the clock function. The program file and the parameters are stored in the memory card. It is possible to execute operation by reading them at power ON.
(Automatic Transfers at Power ON)
C200H-MP831 None The CS Series CPU Units have a nonvolatile
memory for user program in it. The memory unit is unnecessary.
They also have the clock function. The program file and the parameters are stored in the memory card. It is possible to execute operation by reading them at power ON.
(Automatic Transfers at Power ON)
<I/O Expansion System>
Unit name C200H-series CS1-series Description
Power Supply Units C200H-PS221 C200HW-PA204
(AC Power Supply Unit) C200HW-PA204C (AC Power Supply Unit)
With maintenance forecast monitor.
C200HW-PA204S (AC Power Supply Unit)
With 24 VDC power supply.
C200HW-PA204R (AC Power Supply Unit)
The RUN output does not operate.
C200HW-PA209R (AC Power Supply Unit)
The RUN output does not operate.
C200H-PS211 C200HW-PD024
(DC Power Supply Unit) C200HW-PD025 (DC Power Supply Unit) Backplanes
Respectively for 3, 5, 8, and 10 slots The installation hole position is the same.
Connecting Cables for Expansion Backplanes
C200H-CN□□1 CS1W-CN□□3 This cable connects a CS1 CPU Backplane
and a CS1 Expansion Backplanes.
CS1W-CN□□1 This cable connects a CS1 CPU Backplane and an Expansion I/O Backplanes (C200HW-BI□□1-V2).
6
<I/O Units, CPU Bus Units>
Unit name C200H-series CS1-series Description
Basic I/O Units C200H-I□□□
C200H-O□□□
C200H-series Basic I/O Units can be used with CS1-series CPU Units.
Refer to Appendix E. Table of Input/Output Units for CS1 Basic Input/Output Units corresponding to C200H Basic Input/Output Units.
We recommend replacing the C200H-series Basic Units with CS1-series Basic I/O Units for maintenance purpose.
Special I/O Unit
C200H-□□□□ C200H-□□□□
Or,
CS1W-□□□□
C200H-series Special I/O Units can be used with CS1-series CPU Units. However, there are some remarks to be followed.
To improve the system performance and to facilitate maintenance, we recommend you to use the CS-series Units instead.
Communication Units [SYSMAC LINK]
Coaxial cable type:
C200H-SLK21-V1 C200HS-SLK22 C200HW-SLK23/24 Optical Fiber Cable type:
C200H-SLK11
Wire type: CS1W-CLK23 Optical Fiber Cable type:
CS1W-CLK13/53
C200HW-SLK□□ can not be used with CS1-series CPU Unit.
Refer to the SYSMAC CS1W-SLK11/21 SYSMAC LINK Units OPERATIAN MANUAL (Cat. No. W367) for details about SYSMAC LINK.
We recommend you to use the Controller Link instead.
Refer to the Controller Link Units (Wire type) Operation Manual (Cat. No. W309) and Controller Link Units (H-PCF Optical Fiber Cable ring connection) Operation Manual (Cat. No. W370) for details.
[SYSNET] Optical Fiber Cable type:
CS1W-CLK13/53
SYSNET can not be used with CS1-series CPU Unit.
We recommend you to renewal the system with Controller Link instead.
Refer to the Controller Link Units (Wire type) Operation Manual (Cat. No. W309) and Controller Link Units (H-PCF Optical Fiber Cable ring connection) Operation Manual (Cat. No. W370) for details.
[Host Link] [Serial Communication] C200H Host Link Unit can not be used with CS1-series CPU Unit.
Refer to the SYSMAC CS/CJ Series Serial
Communications Boards/Units OPERATIAN MANUAL (Cat. No. W336) for
details.
C200H-LK101-PV1 None
CS1W-SCU21-V1 (+ optical link module)
The CS-series does not have the Optical-type Serial Communications Board/Unit. Use the wire-type instead, or use an external optical link module.
C200H-LK201-V1 CS1W-SCU21-V1 CS1W-SCB21-V1 CS1W-SCB41-V1
Host Link port built-in the CPU Unit
Use one of the left CS1-series Unit/Board.
C200H-LK202-V1 CS1W-SCU31-V1 CS1W-SCB41-V1
Use one of the left CS1-series Unit/Board.
[PC Link] Optical Fiber Cable type:
CS1W-CLK13/53
PC Link Unit can be used with CS1-series CPU Unit. However, link area allocation, etc.
must be modified.
We recommend you to use the Controller Link instead.
Refer to the Controller Link Units (Wire type) Operation Manual (Cat. No. W309) and Controller Link Units (H-PCF Optical Fiber Cable ring connection) Operation Manual (Cat. No. W370) for details.
Unit name C200H-series CS1-series Description Communication Units [SYSBUS]
Wire type:C200H-RM201 Optical Fiber Cable type:
C200H-RM001-PV1
[SYSBUS]
Wire type: C200H-RM201 Optical Fiber Cable type:
C200H-RM001-PV1
SYSBUS Unit can be used with CS1-series CPU Unit. However, relay area allocation, etc. must be modified.
To improve the system performance and to facilitate maintenance, we recommend you to use left networks instead.
Refer to the CS/CJ series CompoNet Master Units Operation Manual (Cat. No.
W456) and CompoNet Slave Units and Repeater Unit OPERATION MANUAL (Cat.
No. W457) for details of CompoNet.
Refer to the SYSMAC CS/CJ series CS-series: CS1W-DRM21(-V1)CJ Series:
CJ1W-DRM21 DeviceNet Units OPERATIAN MANUAL (Cat. No. W380) for details about DeviceNet.
Refer to the C200HW-SRM21-V1 CS1W-SRM21, CJ1W-SRM21 CQM1-SRM21-V1 SRT1 Series SRT2 Series CompoBus/S OPERATIAN MANUAL (Cat. No. W226) for details about CompoBus/S.
<Support software and peripheral devices>
Name C200H-series CS1-series Description
Support software SYSMAC Support Software CX-Programmer
CX-One
CXONE-AL□□C-V□/ AL□□D-V□
(CX-Programmer Ver.3.0 or higher)
SYSMAC Support Software can not be used with CS1-series CPU Unit.
Peripheral Interface Unit, connecting cable
C200H-IP007 CS1W-CN226/626 To load the program onto CX-Programmer
from C200H, C200H-IP007 and cable (CQM1-CIF02) are required.
Programming Console C120-PRO15 C120-PRO25
C200H-PRO27(+CS1W-CN□□4 )
CQM1-PRO01(+CS1W-CN114)
CS1W-CN□□4 is a Programming Console Connecting Cable.
A cassette interface can not be used.
PROM Writer C500-PRW06 None EPROM can not be used with CS1-series.
Save the data using a PC (CX-Programmer).
Floppy disk interface C500-FD103 None Save the data using a PC
(CX-Programmer).
Printer interface unit C500-PRT01
C2000-MP103-V□ None Print the data using a PC
(CX-Programmer).