Outline of the system configuration
C200Hα
C200HW Expansion Backplanes Or,
CS1 Expansion Backplanes
SYSMAC Support Software CX-Programmer
CX-Programmer
The table below lists the models of SYSMACα series units and each corresponding models of CS1-series. Select the CS1-series model which is compatible with the C200H Series model. Or, select the CS1-series model with similar specification to the C200H Series Unit.
Refer to the manuals below for details.
⋅ CS1-series: CS1G/H-CPU**H/CS1G/H-CPU**-EV1 CS SERIES CPU UNITS OPERATIAN MANUAL (Cat.
No. W339)
⋅ C200Hα series: Programmable Controllers C200HX-CPU□□-E/-ZE, C200HG-CPU□□-E/-ZE, C200HE-CPU□□-E/-ZE INSTALLATION GUIDE (Cat. No. W302)
< CPU Units and Power Supply Units >
Unit name SYSMACα Series CS1-series Description
CPU Units C200HE-CPU11(-Z)
C200HE-CPU32(-Z) C200HE-CPU42(-Z)
CS1G-CPU42H UM 10K steps
C200HG-CPU33(-Z) C200HG-CPU43(-Z) C200HG-CPU53(-Z) C200HG-CPU63(-Z)
CS1G-CPU43H UM 20K steps
C200HX-CPU34(-Z)
CS1G-CPU45H UM 60K steps
Memory Casette C200HW-ME□□K C200HS-MP16K
HMC-EF□□□
Power Supply Units C200HW-PA□□□
C200HW-PD□□□ C200HW-PA□□□
C200HW-PD□□□ The Power Supply Units of SYSMACα series can be used with CS1-series, if its capacity is larger than the total current consumption of the new PLC.
Backplanes
The installation hole position is the same.
Note: CS1W-BC□□2 can not be used with C200H Units.
Communication Boards C200HW-COM01 Unnecessary* *It is not necessary to mount the communication unit for networks such as SYSMAC LINK and SYSNET.
C200HW-COM02(-V1) CS1W-SCB21-V1
C200HW-COM03(-V1) CS1W-SCB41-V1
C200HW-COM04(-V1) CS1W-SCB21-V1
C200HW-COM05(-V1) CS1W-SCB21-V1
C200HW-COM06(-V1) CS1W-SCB41-V1
CPU Backplane
Unnecessary* * The backplane of the CS1-series has an installation structure to be insulated from the control board etc., CPU Backplane Insulation Plates are unnecessary.
<I/O Expansion System>
Unit name SYSMACα Series CS1-series Description
Power Supply Units C200HW-PA□□□
C200HW-PD□□□ C200HW-PA□□□
C200HW-PD□□□ The Power Supply Units of SYSMACα series can be used with CS1-series, if its capacity is larger than the total current consumption of the new PLC.
Backplanes
C200HW Expansion Backplane can be used with CS1-series.
When the unit of the CS1-series is used, use the CS1 Expansion Backplane (CS1W-BI□□□), instead of C200HW Backplane.
Attention: The installation hole position of CS1 Expansion Backplane changes with the number of slot (3, 5, 8 and 10 slots).
CS1W-BI□□2 can not be used with C200H Units.
Connecting Cables for Expansion Backplanes
C200H-CN□□1 CS1W-CN□□3 This cable connetct a CS1 CPU
Backplane and a CS1 Expansion Backplanes.
CS1W-CN□□1 This cable connetcts a CS1 Backplane (CPU/Expansion) and an Expansion I/O Backplanes (C200HW-BI□□1).
C200H-CN□□1 This cable connetcts two CS1 Expansion Backplanes (C200HW-BI□□1).
Backplane Insulation
[When using C200HW Expansion Backplanes]
C200HW-ATT32 C200HW-ATT52 C200HW-ATT82 C200HW-ATTA2
[When using CS1 Expansion Backplanes]
Unnecessary*
*The backplane of the CS1-series has an installation structure to be insulated from the control board etc., Backplane Insulation Plates are unnecessary.
Expansion Backplane installation hole dimension
118±0.2
<I/O Units, CPU Bus Units>
Unit name SYSMACα Series CS1-series Description
Basic I/O Units C200H-I□□□
C200H-O□□□
C200H-series Basic I/O Units can be used with CS1-series.
Refer to Appendix E. Table of Input/Output Units for CS1 Basic Input/Output Units corresponding to C200H Basic Input/Output Units.
We recommend replacing the C200H-series Basic Units with CS1-series Basic I/O Units for maintenance purpose.
Special I/O Units C200H-□□□□ C200H-□□□□
Or,
CS1W-□□□□
C200H-series Special I/O Units can be used with CS1-series Units. However, there are some remarks to be followed.
To improve the system performance and to facilitate maintenance, we recommend you to use the CS1-series Unit instead.
Communications Units [SYSMAC LINK]
Coaxial cable type:
C200HW-SLK23/24
Optical Fiber Cable type:
C200HW-SLK13/14
[SYSMAC LINK]
Coaxial cable type:
CS1W-SLK21
Optical Fiber Cable type:
CS1W-SLK11 Or,
[Controller Link】
Wire type:CS1W-CLK23 Optical Fiber Cable type:
CS1W-CLK13/53
C200HW-SLK□□ can not be used with CS1-series.
Refer to the SYSMAC CS1W-SLK11/21 SYSMAC LINK Units OPERATIAN MANUAL (Cat. No. W367) for details about SYSMAC LINK.
We recommend you to use the Controller Link instead.
Refer to the Controller Link Units (Wire type) Operation Manual (Cat, No. W309) and Controller Link Units (H-PCF Optical Fiber Cable ring connection) Operation Manual (Cat, No. W370)
Wire type: CS1W-CLK23 Optical Fiber Cable type:
CS1W-CLK13/53
SYSNET can not be used with CS1-series.
We recommend you to renewal the system with Controller Link.
Refer to the Controller Link Units (Wire type) Operation Manual (Cat, No. W309) and Controller Link Units (H-PCF Optical Fiber Cable ring connection) Operation Manual (Cat, No. W370)
[Controller Link]
Wire type: C200HW-CLK21
[Controller Link]
Wire type: CS1W-CLK23
C200HW-CLK21 can not be used with CS1-series. To use the CS1-series, change the related area, including status area.
Refer to the Controller Link Units (Wire type) Operation Manual (Cat, No. W309).
[Host Link] [Serial Communication] C200H Host Link Unit can not be used with CS1-series.
Refer to the SYSMAC CS/CJ Series Serial
Communications Boards/Units OPERATIAN MANUAL (Cat. No. W336) for
details.
C200H-LK101-PV1 None
CS1W-SCU21-V1 (+ optical link module)
The CS1-series does not have the Optical-type Serial Communications Board/Unit. Use the wire-type instead, or use an external optical link module.
C200H-LK201-V1 CS1W-SCU21-V1 CS1W-SCB21-V1 CS1W-SCB41-V1
Host Link port built-in the CPU Unit
Use one of the left CS1-series Unit/Board.
C200H-LK202-V1 CS1W-SCU31-V1 CS1W-SCB41-V1
This Unit can not be used with CS1-series.
Use one of the left CS1-series Unit/Board.
[PC Link]
C200H-LK401
[PC Link]
C200H-LK401 [Controller Link]
Wire type: CS1W-CLK23 Optical Fiber Cable type:
CS1W-CLK13/53
PC Link Unit can be used with CS1-series.
The link area allocation, etc. must be modified.
We recommend you to use the Controller Link instead.
Refer to the Controller Link Units (Wire type) Operation Manual (Cat, No. W309) and Controller Link Units (H-PCF Optical Fiber Cable ring connection) Operation Manual (Cat, No. W370)
Unit name SYSMACα Series CS1-series Description Communications Units [CompoBus/S]
C200HW-SRM21(-V1)
[CompoBus/S]
C200HW-SRM21(-V1) Or,
CS1W-SRM21
C200HW-SRM21(-V1) can be used with CS1-series; however, I/O allocation must be changed.
There are also some points to follow, when CS1W-SRM21 is replaced.
Refer to the C200HW-SRM21-V1, CS1W-SRM21, CJ1W-SRM21, CQM1-SRM21-V1, SRT1 Series, SRT2 Series CompoBus/S OPERATIAN MANUAL (Cat. No. W226) for details about CompoBus/S. CS1-series; however, program including I/O allocation must be changed.
Refer to the SYSMAC CS/CJ SeriesCS Series: CS1W-DRM21(-V1) CJ-Series:
CJ1W-DRM21 DeviceNet Units OPERATIAN MANUAL (Cat. No. W380) for details.
[SYSBUS]
Wire type: C200H-RM201 Optical Fiber Cable type:
C200H-RM001-PV1
[SYSBUS]
Wire type: C200H-RM201 Optical Fiber Cable type:
C200H-RM001-PV1
SYSBUS Unit can be used with CS1-series.
However, relay area allocation, etc. must be modified.
To improve the system performance and to facilitate maintenance, we recommend you to use left networks instead.
Refer to the CS/CJ-series CompoNet Master Units Operation Manual (Cat. No.
W456) and CompoNet Slave Units and Repeater Unit OPERATION MANUAL (Cat.
No. W457) for details of CompoNet.
Refer to the SYSMAC CS/CJ SeriesCS Series: CS1W-DRM21(-V1) CJ-Series:
CJ1W-DRM21DeviceNet Units OPERATIAN MANUAL (Cat. No. W380) for details about DeviceNet.
Refer to the C200HW-SRM21-V1, CS1W-SRM21, CJ1W-SRM21, CQM1-SRM21-V1, SRT1 Series, SRT2 Series CompoBus/S OPERATIAN MANUAL (Cat. No. W226) for details about CompoBus/S.
Insert the memory card into the CS1-series CPU Unit to save and retrieve PLC memory area contents between the CPU Unit and the memory card.
Moreover, the communication can be made with the Ethernet Unit and the EtherNet/IP Unit.
<Support software and peripheral devices>
Name SYSMACα Series CS1-series Description
Support software SYSMAC Support Software CX-Programmer
CX-One
CXONE-AL□□C-V□/ AL□□D-V□
(CX-Programmer Ver.3.0 or higher)
SYSMAC Support Software can not be used with CS1-series.
Peripheral Interface Unit, connecting cable
CQM1-CIF02 CS1W-CN226/626
Programming Console C200H-PRO27 (+C200H-CN□□2) CQM1-PRO01
C200H-PRO27(+CS1W-CN□□4 )
CQM1-PRO01(+CS1W-CN114)
CS1W-CN□□4 is a Programming Console Connecting Cable.