BM Monitor screen display and key functions

9 OPERATION OF THE VARIOUS SYSTEM MONITOR SCREENS

9.3 Batch monitor

9.5.2 BM Monitor screen display and key functions

9.5.2 BM Monitor screen display and key functions

In this section, the BM Monitor screen display and the functions of keys displayed at the top of the screen are explained.

(1) Display

*1 Displayed for QCPU monitor only.

(2) Key functions

The chart below shows the function of the keys that are used with the operation of the BM Monitor screen.

Displays current value of a maximum of 16 devices.

1) Displays the keys that are used with the operation of the BM Monitor screen shown in (2) (Touch input).

2) Displays the monitor station network No., station No., CPU No.*1 and the first 2 digits of the I/O signal No. of the object module.

3) Displays the current values of the buffer memory (The screen above shows when the monitor module is 16 bits.).

Key Function

This moves to basic screen (function change menu screen) for changing to another moni-tor function or ending the system monimoni-tor (See Sec. 9.1.1.).

This moves to display change menu screen for changing the number display on the BM monitor screen (decimal/hexadecimal) (See Sec. 9.1.2.).

This moves to device setting menu screen to change the monitor device or execute a test.

Change of monitor device (See Sec. 9.1.3.) Test (See Sec. 9.6.)

NETWK No.[ 0] STATION[FF]

I/O NO[ 1]

BM 1110 -32767 BM 1118 0 BM 1111 64 BM 1119 0 BM 1112 149 BM 1120 150 BM 1113 -1111 BM 1121 131 BM 1114 126 BM 1122 -32768 BM 1115 160 BM 1123 555 BM 1116 255 BM 1124 2368 BM 1117 1200 BM 1125 11000

BM MONITOR TEST MENU FORM SET 1) 2)

3)

MENU FORM

SET

9.6 Test 9 - 16

OPERATION OF THE VARIOUS SYSTEM MONITOR SCREENS

10

ERROR MESSAGES FOR SYSTEM MONI- TOR

11

OPERATING SP MODULE MONITOR

12

OPERATING SP MODULE MONITOR SCREEN

13

OPERATING I/O MODULE MONITOR SCREENS

14

ERROR MESSAGES FOR SP MODULE MONITOR

15

OPERATING NET- WORK MONITOR

16

SWITCHING THE NETWORK MONI- TOR SCREENS

9.6 Test

When monitoring with the system monitor function, you can specify an optional station or device to be moni-tored and test it.

The operation of testing a bit device, word device, or special module buffer memory of the PLC CPU is explained in this section.

CAUTION

Read the manual carefully and fully understand the operation before the test operation (ON/OFF of bit devices, modifying current value of a word device,

modifying timer/counter setting, modifying the current value, or modifying the current value of a buffer memory) of system monitor.

In addition, never modify data in a test operation to a device which performs a crucial operation to the system. It may cause an accident by a false output or malfunction.

9 - 17 9.6 Test

9.6.1 Basic operation

9.6.1 Basic operation

The operation procedure for testing when monitoring with the system monitor function is shown below.

See Sec. 9. .2.

... When a screen other than the monitor screen is displayed, display any monitor screen according to the explanatory section for each monitor function.

When Device Monitor screen is displayed.

... When you touch , the display moves (returns) to the previous monitor screen.

... When you touch , the display moves (returns) to the previous monitor screen.

D 15 -2147483648 DW D 10 -32767 X 001  25 

NETWK No.[ 0] STATION[FF]

DEVICE MONITOR TEST MENU FORM SET When monitoring with the system monitor function, display any monitor screen.

[Operation procedure]

SET (Touch)

TEST (Touch)

NETWK No.[ 0] STATION[FF]

DEVICE MONITOR

DELETE

MENU FORM SET

ALL CLR DEVICE

TEST TEST

CANCEL

Display device setting menu screen.

NETWK No.[ 0] STATION[FF]

DEVICE MONITOR

VALUE16

MENU FORM SET

SET/RST

SET VAL VALUE32 BM VAL16

BM VAL32

CANCEL

Display test menu screen.

1)

CANCEL

CANCEL

9.6 Test

9.6.1 Basic operation 9 - 18

OPERATION OF THE VARIOUS SYSTEM MONITOR SCREENS

10

ERROR MESSAGES FOR SYSTEM MONI- TOR

11

OPERATING SP MODULE MONITOR

12

OPERATING SP MODULE MONITOR SCREEN

13

OPERATING I/O MODULE MONITOR SCREENS

14

ERROR MESSAGES FOR SP MODULE MONITOR

15

OPERATING NET- WORK MONITOR

16

SWITCHING THE NETWORK MONI- TOR SCREENS

(1) Touch either, depending on test contents.

SET/RST (set/reset) bit device.

or

Change current value of word device.

Change T, or C set value.

or

Change current value of buffer memory.

* With VALUE16 or BM VAL16, 16 bits is the object module.

With VALUE32 or BM VAL32, 32 bits is the object module.

(2) Specify the network No., station No. and CPU No.

of the object PLC CPU (See Sec. 9.1.3, *1.).

(For data link system) Network No.: 0 (For multi-CPU system) * CPU No. 0 to 4 (CPU number)

* Displayed for QCPU monitor only.

(3) Specify object device.

(4) Specify test value.

With SET/RST (set/reset) of bit device, specify 0 (RST) or 1 (SET).

When changing current value of word device When changing T or C set value

or

When changing current value of buffer memory Match current display form (decimal/hexadeci-mal) and specify change value. (*4)

Select test item.

When VALUE16 / VALUE32 is selected.

Arrow : Select input area.

( : Left/right)

Character: Enter network No., station No., CPU No.*3, device name, device No.,

When SET VALUE is selected.

9 - 19 9.6 Test

9.6.1 Basic operation

*1 The data being entered can be cleared by using the following keys.

: Clear all data being entered in the object area.

: Clear one character from the cursor position.

*2 The format for the data being entered is displayed on the right side of the screen.

: Enter in decimal.

: Enter in hexadecimal.

*3 The monitor target must be preset using GT Designer2.

For ACPU monitor, specify the network number/station number set on GT Designer2.

Refer to the GOT-A900 series User's Manual (Connection System Manual) for details of the monitor target setting for Ethernet connection.

*4 Even when the setting value/current value is changed after the timer (T) has timed out and the counter (C) has fin-ished counting, the time-up status/count-up status do not change. The current status is maintained.

(When the setting value is changed to a large value/when the current value is changed to a small value)

*5 When an index-qualified T/C set value is changed, only its constant part is changed. Its index-qualified part is not changed.

Example) Changing the set value of T5 from "300" to "200"

AC DEL

DEC HEX

K300 Z2 T5

K200 Z2 T5 NETWK No.[ ] STATION[ ] DEVICE[ T] [ 5] VL [K200 ]

Constant part

Index-qualified part

9.6 Test