4 OPERATING THE UTILITY FUNCTION

4.4 Screen & OS Copy

(1) Display screen

(2) Features

• Project data stored in the internal memory can be saved to the memory card.

• Project data stored in the memory card can be saved to the internal memory.

• OS data can be backed up by copying them from the internal memory to the memory card.

(3) Procedure

(a) Basic operation

• Touch or to select options.

• Touching will display a message asking you to answer the question "Do you want to execute?"

• If you answers Yes to the question, touch again. Touch or to select another option. To quit the backup copy, touch to return to the Utility Menu screen.

(b) To return to the Utility Menu screen:

• Touch to return to the Utility Menu screen.

(4) On-screen error messages Sample screen

Message Cause Corrective Action

Cancel write protect

function The memory card is write-protected. Release write protection of the memory card.

Install memory card A memory card is not installed on the GOT. Install a memory card on the GOT.

Format memory card The installed memory card is not yet

formatted. Format the memory card.

Write Error (M-CARD capacity shortage)

Data transfer error

Memory card loaded has memory space less than written data.

Change the memory card for the one having enough memory space.

M-CARD error Data transfer error

Write error occurred in the memory card during copying, or the memory card used has no free space.

Change the memory card, or increase the free space of the memory card.

Memory card error The hardware of the installed memory card is defec-tive.

Replace the memory card with a new one.

4.4 Screen & OS Copy 4 - 6

OVERVIEW

2

BEFORE BEGIN- NING OPERATION

3

SPECIFICATIONS

4

OPERATING THE UTILITY FUNCTION

5

OPERATING LAD- DER MONITOR

6

OPERATING THE VARIOUS LADDER MONITOR SCREENS

7

ERROR MESSAGES FOR LADDER MONI- TOR

8

OPERATING SYS- TEM MONITOR

(5) Directory tree in a memory card

The directory tree in a memory card is shown as follows.

(a) The copied screen data is stored under the UserData folder.

Since the OS and screen data are managed by the Dlist.ini file and the Flist.ini files in the corresponding folders, always install or download the GT Designer2 OS (specify the memory card as the download destination) to create the memory card.

If Explorer or like in the personal computer is used to copy the OS, the GOT cannot recognize the data in the memory card.

(b) Do not edit the screen data in the memory card directly using GT Designer2.

When edit the screen data, use the following method.

• Connect the GOT to a PC with the RS-232C cable and edit the uploaded screen data.

• Copy the data in the memory card to a PC and edit the data.

(c) When copy a file (alarm history data, recipe data) in the memory card to a PC or delete it, install the memory card to the PC and copy/delete the file by the Explorer.

(d) The SRAM type memory card can be formatted on the GOT.

Check the memory card with the self-diagnostics of the utility function.

When the memory card is checked, the memory card is formatted after the check.

The compact flash PC card cannot be formatted on the GOT.

Use the personal computer to format it.

For the way to format the memory card, refer to the GT Designer2 Version2 Operating Manual.

(e) The dat format file is used in the GOT system.

There fore, the user must not create the file with the extension of "dat".

You cannot use this function to install the OS (from memory card to internal memory).

For details of OS installation, refer to the GT Designer2 Version2 Operating Manual.

ALARMHST RECIPE REPORT SNAPSHOT SNAPHDCP.BMP USERDATA OS SYSTEMD SPCDATA

\

(File structure)

For alarm history file storage For recipe file storage For report file storage For screen image file storage Work file for printer printout

For monitor screen data storage (for screen copy) For OS storage (for OS copy)

For OS system screen storage (for OS copy)

For special function module monitor data storage (for screen copy) For motion monitor data storage (for screen copy)

For servo amplifier monitor data storage (for screen copy)

4 - 7 4.5 Setup

4.5 Setup

After changing any of the items in Setup, touching automatically resets the GOT and shows the monitor screen.

(1) Display screen

The display screen differs with the GOT used.

GOT Used Screen Example

A97*GOT/

A960GOT

This screen example assumes that the communication driver "Computer" has been installed.

A985GOT (-V)

This screen example assumes that the communication driver "Bus (Q)" has been installed.

A video window (channel, etc.) and RGB screen (H-Position, etc.) may be set only when the A985GOT-V is used.

4.5 Setup 4 - 8

OVERVIEW

2

BEFORE BEGIN- NING OPERATION

3

SPECIFICATIONS

4

OPERATING THE UTILITY FUNCTION

5

OPERATING LAD- DER MONITOR

6

OPERATING THE VARIOUS LADDER MONITOR SCREENS

7

ERROR MESSAGES FOR LADDER MONI- TOR

8

OPERATING SYS- TEM MONITOR

(2) Functions

(a) Data that can be set on any GOT

• Buzzer volume

You can select the length of the beep sound.(Factory-set to SHORT)

• Outside speaker sound

You can select whether or not voice output is provided from the external speaker (only the voice specified for the touch input sound on the GT Designer2).

(Factory-set to OFF)

• Screen save time

Set the time until the monitor screen display is switched off by the screen saver function.

You can set the time between "00 minutes" and "60 minutes".

When this setting is "0", the monitor screen is always displayed.(Factory-set to 0)

• Screen save light

When this setting is OFF, the backlight goes off as soon as the display is erased by the screen saver function.

When this setting is ON, the display will disappear but the backlight will not go off.

• Language

You can select the language (Japanese or English) of the messages to be displayed on the screen. (Factory-set to Japanese)

As message display languages, four languages (Japanese/English/Chinese (simplified characters)/Chinese (traditional characters)) are available for some system dialogs, while two languages (Japanese/English) are available normally. (Refer to Section 3.10, Section 32.)

GOT Used Screen Example

A95*GOT

This screen example assumes that the communication driver other than "Bus(A, QnA)" has been installed.

The grip switch setting and grip switch cancel-time key OFF setting are available only for use of the A950 handy GOT.

4 - 9 4.5 Setup

(b) Data that can be set when the corresponding communication driver is installed 1) When communication driver for bus connection (Q) is installed

QBUS extension number

Set the GOT extension number for bus connection to the QCPU.

(Factory set to extension 7) QBUS slot number

Set the slot number where the GOT is assigned for bus connection to the QCPU. (Factory set to slot 0)

2) When communication driver for microcomputer connection is installed Microcomputer connection baud rate

You can select the transmission speed when the GOT is connected to a microcomputer.(Factory-set to 19200)

Microcomputer connection communication form

You can select the protocol when the GOT is connected to a microcomputer.(Factory-set to FORM-1)

3) When communication driver for computer link connection (AJ71QC24) is installed QC24 Baud rate

Set the transmission speed for connection with the QC24N.

(Factory-set to 19200bps)

4) When communication driver for OMRON/Hitachi PLC connection is installed Baud rate

Choose the transmission speed for connection with the Omron or Hitachi PLC. (Factory-set to 19200bps)

5) When communication driver for Yasukawa PLC connection is installed Baud rate

Choose the transmission speed (4800, 9600, 19200, 38400).

(Factory-set to 19200bps) Startup time

Set when (seconds) to start communication with the PLC CPU after power-on of the GOT.

(Factory-set to 16 seconds for the GL series or 1 second for other than the GL series) Send message delay

Set the waiting time from when the GOT has received data from the PLC CPU until the GOT send the next data to the PLC CPU. (Factory-set to 0msec)

6) When communication driver for SIEMENS PLC connection is installed Baud rate

Choose the transmission speed (4800, 9600, 19200, 38400).

(Factory-set to 19200bps) Adapter address

Specify the MPI address on PROFIBUS assigned to the HMI adaptor connected to the GOT. (Factory-set to 2)

Host (FF) address

Specify the MPI address on PROFIBUS assigned to the HMI adaptor connected to the GOT. The specified PLC CPU is the "host" when monitor device setting is made on GT Designer2.

For details of monitor device setting, refer to the GT Designer2 Version2 Reference Manual. (Factory-set to 2)

4.5 Setup 4 - 10

OVERVIEW

2

BEFORE BEGIN- NING OPERATION

3

SPECIFICATIONS

4

OPERATING THE UTILITY FUNCTION

5

OPERATING LAD- DER MONITOR

6

OPERATING THE VARIOUS LADDER MONITOR SCREENS

7

ERROR MESSAGES FOR LADDER MONI- TOR

8

OPERATING SYS- TEM MONITOR

7) When communication driver for Allen-Bradley PLC connection is installed Baud rate

Choose the transmission speed (4800, 9600, 19200, 38400).

(Factory-set to 19200bps) Adapter address

Set the address on the DH-485 network assigned to the HMI adaptor connected to the GOT. This setting is required only when multiple CPUs are connected to the GOT.

Set the same address as the DH-485 Node Address specified for the adaptor.

The DH-485 Node Address specified should not overlap the Node Address of the PLC on the DH-485 network. (Factory-set to 1)

Host (FF) address

Specify the address on the DH-485 network assigned to the PLC CPU to which the HMI adaptor is connected.

The specified PLC CPU is the "host" when monitor device setting is made on GT Designer2.

For details of monitor device setting, refer to the GT Designer2 Version2 Reference Manual. (Factory-set to 1)

8) When communication driver for Matsushita Electric Works PLC connection is installed Baud rate

Choose the transmission speed (4800, 9600, 19200, 38400).

(Factory-set to 19200bps) Startup time

Set when (seconds) to start communication with the PLC CPU after power-on of the GOT.

(Factory-set to 0msec) Send message delay

Set the waiting time from when the GOT has received data from the PLC CPU until the GOT send the next data to the PLC CPU. (Factory-set to 3msec)

C.C.U monitor registration

Choose whether CCU monitor registration is made or not.

When multiple GOTs/peripheral devices are connected to one CPU via the C.C.U., up to one unit(When the CPU is the FP10SH, up to five units can be set) can be registered for C.C.U. monitor. When two or more GOTs are used or they are used with peripheral devices together, set "No" for C.C.U. monitor registration.

9) When communication driver for Ethernet connection is installed 10) When extended function OS for gateway functions is installed

4 - 11 4.5 Setup

11) When A9GT-J71E71-T module is connected GOT NET No.

Set the network number of the GOT. (Factory-set to 1) GOT PC No.

Set the station number of the GOT.

Do not set the same number as the PC No. of the Ethernet module to be monitored.

(Factory-set to 1) GOT IP address

Set the IP address of the GOT.

GOT port No.

Set the port number of the GOT. (Factory-set to 5001) Router address

When the network is connected to the other network by a router, set the router address of the network where the GOT is connected.

(Factory-set to 000.000.000.000) Sub-net mask

When the GOT is connected to the Ethernet network which is controlled the sub-network, set the sub-network mask set commonly to the networks. When the sub-network is not used, operation is performed at the default value. (Factory-set to 255.255.255.000) Send message wait

Set the transmission wait time to reduce loads on the network and target PLC. (Factory-set to 0)

Send message time

Set the time-out period. (Factory-set to 3) Startup time

Set when (seconds) to start communication after power-on of the GOT. (Factory-set to 3msec)

12) When communication driver for CC-Link connection (CC-Link (ID)) is installed.

Send message time

Set the time-out period. (Factory-set to 3)

4.5 Setup 4 - 12

OVERVIEW

2

BEFORE BEGIN- NING OPERATION

3

SPECIFICATIONS

4

OPERATING THE UTILITY FUNCTION

5

OPERATING LAD- DER MONITOR

6

OPERATING THE VARIOUS LADDER MONITOR SCREENS

7

ERROR MESSAGES FOR LADDER MONI- TOR

8

OPERATING SYS- TEM MONITOR

(c) Data that can be set when the specific GOT is used

1) Setting of display mode (may be made for the A95*GOT-LBD(-M3) only) Reverse display

The display mode (normal display (No)/highlighted display (Yes)) is selected.

(Only A95*GOT-LBD (-M3) can be selected. Normal display is set at the time of shipment.)

2) Setting of human sensor (may be made for the A985GOT(-V) only) Screen save Human sensor

You can select whether the screen saver is deactivated or not when the Human sensor has detected a man's motion. (Available for the A985GOT only, factory-set to Invalid) Human sensor detection sensitivity

You can select the detection sensitivity of the Human sensor in any of 11 steps, levels 0 to 10, so that the sensor will not detect a motion such as a man passing before the GOT.

(Available for the A985GOT only, factory-set to 10)

Human sensor OFF delay

The Human sensor can be turned off when it does not detect a man's motion after it has turned on. You can set that period between "00 min. 10 sec." and "60 min. 00

sec.".(Available for the A985GOT only, factory-set to 00 min. 10 sec.) 3) Setting of grip switch (may be made for the A950 handy GOT only)

Grip switch

You can set whether the grip switch will be used or not.

When the setting is USE, hold down the grip switch and perform operation.

Setup and self-diagnostic operations can be performed independently of the grip switch.

(May be set only for the A950 handy GOT, factory-set to USE) If it is released

You can set whether the touch key pressed on the GOT display will be turned off or not at the time of grip switch cancel.

At the setting of "NO ACTION", the pressed touch key is turned off when it is released.(May be set only for the A950 handy GOT, factory-set to KEY OFF) 4) Setting of video window (may be selected only when the A9GT-80V4 is fitted to the

A985GOT-V) Channel

You can choose the video channel for which video window settings are made.

The settings can be made per video channel.

Signal

You can choose the video picture input system (NTSC/PAL).

Video width

You can choose the video window resolution (720

_

480 dots/640

_

480 dots) Color balance/contrast/brightness/color power

You can adjust the contrast, brightness and others of the video picture displayed on the GOT. (May be selected only when the A9GT-80V4 is fitted to the A985GOT-V, factory-set to 50%)

Detection sensitivity setting 10 9 8 7 6 5 4 3 2 1 0

Monitor time [sec] 0 0.1 0.2 0.4 0.8 1 1.5 2 2.5 3 4

4 - 13 4.5 Setup

5) Setting of RGB screen (may be selected only when the A9GT-80R1 is fitted to the A985GOT-V)

Clock phase

You can adjust the flicking of the RGB screen displayed on the GOT.

H-Position/V-Position

You can adjust the position of the RGB screen displayed on the GOT.

RGB close key

You can select which position of the screen to touch to switch from the RGB screen to the GOT monitor screen.

You can also turn on/off the bit device (RGB display controlling bit) to switch the screen.

For the RGB display controlling bit, refer to the GT Designer2 Version2 Reference Manual.

(Factory set to FULL)

• If the touch panel is not touched within the specified time, the screen saver function switches off the display to prevent "burn-in" of the display device.

Especially for the display screen type of EL, it is recommended to use this function.

• Dedicated to the A985GOT, the Human sensor function automatically deactivates the screen saver, without any touch on the touch panel, by means of a signal detected by the Human sensor.

• Using the system information function of the GOT, the signal detected by the Human sensor may also be controlled by the PLC CPU. For full information on the system information function, refer to the GT Designer2 Version2 Reference Manual.

Signal detection timings are shown below.

Detection No detection

Human sensor (operator motion)

Screen saver status

Activation Deactivation

Operator approached Operator moved away System signal 2

(Human sensor detection signal)

1) Motion that the Human sensor cannot detect (outside the range or too low moving speed)

2) Detection error of Human sensor (approx. 0.5 sec) + delay due to Human sensor detection sensitivity 3) Human sensor OFF delay time + communication processing time

4) Time when screen saver is being deactivated

5) Human sensor OFF delay setting is required since the Human sensor outputs Detection and No detection alternately.

6) Human sensor OFF delay + screen save time

3) 4)

6) 2)

1)

5)

4.5 Setup 4 - 14

OVERVIEW

2

BEFORE BEGIN- NING OPERATION

3

SPECIFICATIONS

4

OPERATING THE UTILITY FUNCTION

5

OPERATING LAD- DER MONITOR

6

OPERATING THE VARIOUS LADDER MONITOR SCREENS

7

ERROR MESSAGES FOR LADDER MONI- TOR

8

OPERATING SYS- TEM MONITOR

(3) Operation

(a) Basic operation

• Touch or to select the necessary item.

• When the A985GOT, A950 handy GOT is used, select the last item on Page 1/2 and touch to show Page 2/2.

• For the setting item whose value will be changed, highlight the digit to be set by touching , and set the value by touching or .

(If you are going to select another setting item after that, return the highlight to the setting item by touching , and make selection by touching or .)

• After setting, touch .

After touching , the GOT is automatically reset and the monitor screen appears.

(b) Return to each screen

• If any change has been made to the Setup settings, touching resets and restarts the GOT.

• If any change has been made to the Setup settings, touching resets and restarts the GOT.

The display returns to the utility menu or monitor screen.

4 - 15 4.6 Self-Test