Analog Modules
STEP 7 blocks for analog functions
4.8 Connecting Sensors to Analog Inputs
Introduction
You can connect different sensors to the analog input modules depending on the measuring method; voltage and current sensors, and resistors.
This section contains general information that is generally applicable to all the connection options for sensors described in the sections that follow.
Cables for analog signals
To reduce electrical interference, you should use twisted-pair shielded cables for the analog signals. The shield of the analog signal cables should be grounded at both cable ends.
If there are potential differences between the cable ends, an equipotential bonding current can flow over the shield, which leads to an interference of the analog signals. In such a case, you should ground the shield at one end of the cable only.
Isolated analog input modules
With the isolated analog input modules there is no electrical connection between the reference point of the measuring circuit MANA and the M terminal of the CPU.
You must use isolated analog input modules if a potential difference EISO can occur between the reference point of the measuring circuit MANA and the M terminal of the CPU. By means of a equipotential bonding conductor between the MANA terminal and the M terminal of the CPU, make sure that EISO does not exceed the permitted value.
Non-isolated analog input modules
With the non-isolated analog input modules, you must establish a connection between the reference point of the measuring circuit MANA and the M terminal of the CPU. Establish IM 153. For this purpose, connect the MANA terminal with the M terminal of the CPU and IM 153. A potential difference between MANA and the M terminal of the CPU and the IM 153 can result in corruption of the analog signal.
长沙工控帮教育科技有限公司整理
Limited potential difference ECM
Only a limited potential difference ECM (common mode voltage) may occur between the measuring lines M– of the input channels and the reference point of the measuring circuit MANA. In order to prevent the permissible value from being exceeded, you must take different actions, described below, depending on the potential connection of the sensors.
Abbreviations and mnemonics used in the figures below
The abbreviations and mnemonics used in the figures below have the following meanings:
M +: Measuring lead (positive) M –: Measuring lead (negative)
MANA: Reference potential of the analog measuring circuit M: Ground terminal
L +: Terminal for 24 VDC supply voltage
ECM: Potential difference between inputs and reference potential of the MANA measuring circuit
EISO: Potential difference between MANA and M terminal of CPU
Connecting isolated sensors
The isolated sensors are not connected with the local ground potential (local ground). They can be operated free of potential.
With isolated sensors, potential differences might arise between the different sensors. These potential differences can arise as a result of interference or the local distribution of the sensors.
In order to prevent the permissible value for ECM from being exceeded when operating in areas with heavy EMC interference, we recommend you to connect M– with MANA.
长沙工控帮教育科技有限公司整理
You can operate the CPU in Grounded mode (refer to the figure below) or Ungrounded mode.
Isolated sensors
M+
M L+
M–
MANA M+
M– Backplane
bus ADC
Minternal L+M
Ground bus CPU EISO
Logic
Recommended connection
Figure 4-7 Connecting Isolated Sensors to an Isolated AI
Isolated sensors
M+
M L+
M–
MANA M+
M– Backplane
bus
Minternal L+
M Ground bus
CPU
ADC Logic
Recommended connection
Figure 4-8 Connecting Isolated Sensors to a Non-Isolated AI
长沙工控帮教育科技有限公司整理
Note
Do not connect M– to MANA when connecting two-wire transmitters for current measurement and resistance-type sensors. This also applies to inputs which are not used.
Non-isolated sensors
The non-isolated sensors are connected with the local ground potential (local ground). When using non-isolated sensors, you must connect MANA to the local ground.
Connecting non-isolated sensors
Caused by local conditions or interferences potential differences ECM (static or dynamic) can occur between the locally distributed individual measuring points. If the potential difference ECM exceeds the permissible value, you must provide equipotential bonding conductors between the measuring points.
When connecting non-isolated sensors to optically isolated modules, you can operate the CPU in Grounded mode (refer to the figure below) or Ungrounded mode.
Non-isolated sensors
M+
M L+
M–
MANA M+
M– Backplane
bus ECM
ADC
Minternal ML+
Ground bus CPU EISO
Logic
Equipotential bonding conductor
Figure 4-9 Connecting Non-Isolated Sensors to an Isolated AI
长沙工控帮教育科技有限公司整理
When connecting non-isolated sensors to non-isolated modules, you can operate the CPU only in Grounded mode.
Non-isolated sensors
M+
M L+
M–
MANA M+
M– Backplane
bus
Minternal L+
M Ground bus
CPU
ADC Logic
ECM
Equipotential bonding conductor
Figure 4-10 Connecting Non-Isolated Sensors to a Non-Isolated AI
Note
Non-isolated 2-wire transmitters and non-isolated resistance-type sensors may not be used with non-isolated AI!
长沙工控帮教育科技有限公司整理