3 Function overview (In the case of GOT-A900 series)
3.5.1 Setting methods
3.5.1 Setting methods
1 Select [Common] [System Environment] from the menu.
2 Double click on [System Information] in "System Environment" dialog box.
3 As the setting dialog box appears, make the settings according to the following explanation.
Remark
When making the settings in project work spaceDouble click on [System Environment] to display "System Environment" dialog box, and then double click on [System Information] there.
3.5.2 Setting items
Set devices and functions to be used in the system information.
In the case of GOT-A900 series
Double click
OVERVIEW
2
SPECIFICATIONS
3
COMMON SETTING
4
PREPARATORY OPERATION FOR OBJECT SETTING
5
COMMON SETTINGS FOR OBJECTS
6
LAMP, SWITCH
7
NUMERICAL/ CHARACTER DISPLAY
8
M
In the case of GOT-F900 series
(Continued to next page)
Item Description A F
Read Device
Set this item to control GOT operations with the device of PLC CPU.
If a device No. is assigned to the system signal 1, the devices of the following Nos. will be consecutively assigned to the items following to the system signal 1 automatically. (The unchecked items will not be set.)
System Signal 1*1 Set the device that stores the data that triggers GOT action. ( Section 5.1 Device Setting) External I/O Function
Output Information*3
Check this item to externally output by turning the bit of the specified device ON when the external I/O function is used.
Current Recipe No.
Check this item to use recipe function to specify the recipe No. for writing to PLC CPU from the PLC CPU.
The recipe No. assigned is less than one of the actual recipe No. to be read/written.
For example: to read/write from/to recipe No. 5, Set the current recipe No. to 4.
Write Device
Set this item to write GOT operations to PLC CPU.
If the device No. is assigned to the system signal 2 or the base screen currently displayed is set, the devices of the following Nos. will be consecutively assigned to the items following to the system signal 2.
(The device of unchecked items will not be set in GOT-A900 series.)
System Signal 2*2 Set the write device of GOT operation status.( Section 5.1 Device Setting)
GOT Error Code
Check this item to store the GOT error.
( Section 3.5.3 Confirm the error occurred in GOT (for GOT-A900 Series only))
3 - 31 3.5 System Information Setting 3.5.2 Setting items
(Continued to next page)
Item Description A F
Write Device
On-screen Base Screen Number
In case of GOT-A900 series
• Check this item to store the screen No. currently displayed.
The screen No. stored is as follows.
Display screen Data format of screen switching device
BIN BCD
The screen other than user- created
screen (utility, RGB etc) -1
Hold user-created base screen No. right before being displayed.
During screen switching 0
Currently displayed base screen 1to 32767 1to 9999
In case of GOT-F900 series
The following 15 points will be occupied after device setting.
D+0 : On-screen base screen No.
D+1 : On-screen overlay screen No. 1 D+2 : On-screen overlay screen No. 2
D+3 : Object ID after input is complete (after input value is updated, the user ID number of numerical input function is stored.)
D+4 : System signal 2*2 D+5 to D+14 : Others
D+5 and D+6 output the information on keys pressed on the keypad in the F920GOT-K and F930GOT-K. (The system signal 1 of the read device should be set.)
For the details, refer to the GOT-F900 SERIES OPERATION MANUAL [GT Designer2 Version].
On-screen Window Screen Number
Check this item to store the currently displayed window screen (overlap window 1).
The screen No. stored is as follows.
Display screen Data format of the screen switching device
BIN BCD
No screen is displayed or , during
screen switching 0
The screen No. of the currently
displayed overlap window 1 1to 32767 1to 9999
The status of screens other than overlap window 1 is confirmed by using switching screen device.
( Section 3.2 Switching Screen Device Setting)
Numeric Value Input Number
Check this item to store the user ID No. for numerical input function after the input value is updated.
( Section 7.1 Numerical Display/Numerical Input)
This can be applied to ASCII input function by turning ON the GOT internal device GS450.b2.
Current Cursor Position
Check this item to store the object ID No. of the object in which the cursor is currently located.
( Section 3.5.3 Confirm cursor's display position (for GOT-A900 Series only))
Previous Cursor Position
Check this item to store the object ID No. of the object in which the cursor was previously located.
( Section 3.5.3 Confirm cursor's display position (for GOT-A900 Series only))
Key Code Input
Check this item to store the set key code when input keys (numerical input, ASCII input, touch switch, and operating panel) are used for input.
( Section 3.5.3 Confirm the input key code by input key (for GOT-A900 series only))
Previous Numeric Value Input (32 bit)
Check this item to store the value (32 bit) before being changed by numerical input function.
( Section 7.1 Numerical Display/Numerical Input)
Current Numeric Value Input (32 bit)
Check this item to store the value (32 bit) changed by numerical input function.
( Section 7.1 Numerical Display/Numerical Input)
OVERVIEW
2
SPECIFICATIONS
3
COMMON SETTING
4
PREPARATORY OPERATION FOR OBJECT SETTING
5
COMMON SETTINGS FOR OBJECTS
6
LAMP, SWITCH
7
NUMERICAL/ CHARACTER DISPLAY
8
M
For details of *1 to *3, refer to the following.
Write Device
Currently Printed Report Screen
Check this item to store the report screen No. being printed.
( Section 12.1 Report Function)
External I/O Function Input Information*3
Check this item to store the information externally input to the specified word device when external I/O function is used.
Cursor Position's Numeric Value Input
Stores the user ID No. of the numerical input function currently displayed with input cursor.
( Section 3.5.3 Confirm cursor's display position (for GOT-A900 Series only)) This can be applied to ASCII input function by turning ON the GOT internal device GS450.b2.
Select All/Unselect Selects/Deselects all the items selected in [Write Device].
Delete Deletes the set read and write devices.
3 - 33 3.5 System Information Setting 3.5.2 Setting items
* 1. System Signal 1
Controls the GOT operation by turning the bit of word device set as system signal 1 ON/OFF
In the case of GOT-A900 series
Signal Name Description
Automatic Screen Saver Disable Signal (b0)
ON : Disables screen saver function (that turns monitor screen display OFF) . OFF : Enables screen saver function.
( Section 3.5.3 Control of Screen Display (for GOT-A900 series only))
Forced Screen Saver Enable Signal (b1)
ON : Forcibly turns the GOT into screen saver mode.
OFF : Common status (Displays screen again)
( Section 3.5.3 Control of Screen Display (for GOT-A900 series only))
Key Code Read Complete Signal (b3)
ON : Clears the following signal.
• Turns [Key input signal (System signal 2)] OFF OFF : Does not clear the above signal.
( Section 3.5.3 Confirm the input key code by input key (for GOT-A900 series only))
Numeric Value Input Read Complete Signal (b4)
ON : Turns [Numeric value input signal (System signal 2)] OFF.
OFF : Does not turn the above signal OFF ( Section 7.1 Numerical Display/Numerical Input)
This can be applied to ASCII input function by turning ON the GOT internal device GS450.b2.
Barcode Input Disable Signal (b5) ON : Disables bar code function.
OFF : Enables bar code function.
Barcode Input Read Complete Signal (b6)
ON : Turns [Barcode input signal (System signal 2)] OFF.
OFF : Does not turn the above signal OFF.
( Section 12.4 Bar Code Function)
Key-In Disable Signal (b9) ON : Disables all key-input . OFF : Enables key-input .
Hard Copy Setting Enable Signal (b10)
ON : Makes hard copy output setting changeable according to bit ON/OFF status of [Hard copy black-white print signal (b11)] and [Hard copy black-white inversion signal (b12)] for system signal 1.
OFF : Carries out hard copy output according to the settings made by GT Designer2) ( Section 12.2 Hard Copy)
Hard Copy Black-White Print Signal (b11)
ON : Changes the hard copy printing mode to [Black-White] .
OFF : Changes the hard copy printing mode to [Color (256 Colors/ 16 Colors)]
( Section 12.2 Hard Copy)
Hard Copy Black-White Inversion Signal (b12)
ON : Inverses the black-white portion of monitor screen and output.
OFF : Outputs the black-white portion of monitor screen without making any changes.
( Section 12.2 Hard Copy)
GOT Error Reset Signal (b13)
ON : Processes the following signals.
• Stores "0" to [GOT error code storage area (Write Device)]
• Turns [GOT error detection signal (System signal 2)] OFF.
OFF : Does not process the above signals.
( Section 3.5.3 Confirm the error occurred in GOT (for GOT-A900 Series only))
Buzzer Output Signal (b14)
ON : Keeps buzzer.
OFF : Does not output buzzer.
Even if [Buzzer Volume] of GOT utility (Setup) is set as [None] , buzzer volume will be output when the bit is ON.
Buzzer One-shot Output Signal (b15)
ON : Outputs buzzer once.
OFF : Does not output buzzer.
The length of buzzer volume is same with the settings (Long, Short) made in [Buzzer Volume] of GOT utility. (When set as [None], buzzer volume is same as the setting of [Long].)
OVERVIEW
PREPARATORY OPERATION FOR OBJECT SETTING
5
COMMON SETTINGS FOR OBJECTS
6
Writes the GOT operation status to PLC CPU according to the bit ON/OFF status of the word device set in system signal 2.
(Continued to next page)
Signal Name Description
Screen saving signal(b0) ON : GOT is in screen saver mode.
OFF : GOT is not in screen saver mode.
GOT Ready Signal (b1)
ON : GOT status normal at power-on OFF : GOT status abnormal at power-on
If the signal will not be ON by resetting the GOT again, its possible cause is hardware error of GOT.
Consult your local Mitsubishi service center or representative.
PC Card Battery Error Detection Signal (b2)
ON : Battery error detected OFF : Battery normal
Key Input Signal (b3)
ON : Key input done OFF : No key input
( Section 3.5.3 Confirm the input key code by input key (for GOT-A900 series only))
Numeric Value Input Signal (b4)
ON : The value input by value input function has been updated.
OFF : The value input by value input function has not been updated.
( Section 7.1 Numerical Display/Numerical Input)
This can be applied to ASCII input function by turning ON the GOT internal device GS450.b2.
Human Sensor Detection Signal (valid in A985GOT only) (b5)
ON : Human movement is detected by human sensor
OFF : Human movement has not been detected by human sensor
(In the case that the human movement can not be detected during the period specified within the GOT utility)
( Section 3.5.3 Control of Screen Display (for GOT-A900 series only))
Due to the characteristic of human sensor, the signal output remains ON for 60 seconds after starting the GOT.
Barcode Input Signal (b6)
ON : The data read by bar code reader has been stored into the specified device.
OFF : No data has been read by bar code reader.
( Section 12.4 Bar Code Function)
Hard Copy Output Signal (b7)
ON : Hard copy function being executed.
OFF : Hard copy function execution completed, or interrupted.
( Section 12.2 Hard Copy)
Report Output Signal (b8)
ON : Printing by report function
OFF : Printing by report function completed, or interrupted.
( Section 12.1 Report Function) A950 Handy GOT's Grip Switch
Pressing Signal (b9)
ON : A950 Handy GOT's Grip Switch being pressed.
OFF : A950 Handy GOT's Grip Switch is released.
Recipe Processing Signal (b10)
ON : Recipe being processed (Write/Read operation) OFF : Recipe process completed, or interrupted.
( Section 11.2 Recipe Function)
Key window Output Signal (b11) ON : Key window being displayed OFF : Key window not displayed
Hardcopy Sub-signal (b12)
ON : The number of files (file No.) for screen data stored in PC card by hard copy function exceeds 9900 OFF : The number of files (file No.) of screen data stored in PC card by hard copy function is less than 9900 ( Section 12.2 Hard Copy)
GOT Error Detection Signal (b13)
ON : GOT error has occurred.
OFF : Normal
( Section 3.5.3 Confirm the error occurred in GOT (for GOT-A900 Series only))
3 - 35 3.5 System Information Setting 3.5.2 Setting items
Signal Name Description
Numeric Value Error Detection Signal (b14)
ON : The value exceeding the input range has been stored into the write target device of numeric value input function
(Check this item on screen switching)
OFF : The value within the input range has been stored into the write target device of numeric value input function.
( Section 7.1 Numerical Display/Numerical Input)
Printer Error Detection Signal (b15)
ON : Printer error (power OFF, cable disconnected, No paper provided/ paper jammed, etc) has occurred.
(The signal turns OFF when printer problem is resolved.) OFF : Normal
OVERVIEW
PREPARATORY OPERATION FOR OBJECT SETTING
5
COMMON SETTINGS FOR OBJECTS
6
External I/O function enables data to be input from the outside of GOT (Operation panel); to be output to the outside of GOT (Lamp or relay), according to the device set in system information.
Remark
(1) When A950 handy GOT is usedWhen A950 handy GOT is used, b0 to b3 within the storage area of external output function (read device) controls the LED status of operation switch.
b0: LED of operation switch (SW1) for A950 handy GOT b1: LED of operation switch (SW2) for A950 handy GOT b2: LED of operation switch (SW3) for A950 handy GOT b3: LED of operation switch (SW4) for A950 handy GOT (2) When external I/O function is used without system information
Data can be input to/output from the outside of GOT by using GOT internal device (GB).
Section 2.6.1 GOT internal devices
Bit No. Output signal storage area of external I/O function (Read Device)
Input signal storage area of external I/O function (Write Device)
b0 Output Y0 Input X0
b1 Output Y1 Input X1
b2 Output Y2 Input X2
b3 Output Y3 Input X3
b4 Output Y4 Input X4
b5 Output Y5 Input X5
b6 Output Y6 Input X6
b7 Output Y7 Input X7
b8 Output Y8 Fuse blown
b9 Output Y9
3 - 37 3.5 System Information Setting 3.5.2 Setting items
*1 System Signal 1
Controls the GOT operation by turning the bit of word device set as system signal 1 ON/OFF.
*2 System Signal 2
Writes the GOT operation status to PLC CPU according to the bit ON/OFF status of the word device set in system signal 2.
(Continued to next page)
In the case of GOT-F900 series
Signal Name Description
Alarm History Clear Signal (b0) ON : Clears the history data of alarm history function.
OFF : Does not clear alarm history data.
Back Light OFF Signal (b1) ON : Turns the backlight OFF after the backlight OFF setting time has passed.
OFF : Keeps the backlight always ON.
Sampling Data Clear Signal (b2) ON : Clears the sampling data of sampling function.
OFF : Does not clear sampling data.
Unused Signal (b3 to b4) Not used
Barcode Input Disable Signal (b5) ON : Disables bar code function and clears the data.
OFF : Enables bar code function.
Barcode Input Read Complete OFF Signal (b6)
ON : Turns [Barcode input signal (System signal 2)] OFF.
OFF : Does not turn the above signal OFF.
Turn OFF b5 of write device +4 (System signal 2) to which input data of bar code reader has been written.
Unused Signal (b7) Not used
Password Input Request Signal (b8)
ON : Automatically displays the window for password input when switching to a higher lever security.
OFF : Does not automatically display the window for password input.
Unused Signal (b9) Not used
Keypad information valid signal 1 (b10)
[Only in the F920GOT-K and F930GOT-K]
ON : Writes the information on pressing of the keypad to the write devices Do +6 and Do +7.
OFF : Does not write such information.
Keypad information valid signal 2 (b11)
ON : Writes information to the write devices D +5 and D +6 when the key pad status is changed or when a scan processing is executed inside the GOT. (Only in the F920GOT-K)
ON : Writes the information to the write devices D +5 and D +6 when the key pad status is changed and in a constant cycle (1 sec). (Only in the F930GOT-K)
OFF : Writes information to the write devices Do +5 and Do +6 when the key pad status is changed.
Unused signal (b12 to b15) Not used
Signal Name Description
Alarm Device ON Confirmation Signal (b0)
ON : Turns ON when any of the devices assigned by alarm function turns ON.
OFF : Turns OFF when all of the devices assigned by alarm function turn OFF.
Sampling Function Execution ON Signal (b1)
ON : Turns ON while the device value of sampling function is being sampled.
OFF : Turns OFF when the device value of sampling function is not sampled.
Numeric Value Input Signal (b2)
ON : The value input by numeric value input function has been updated.
OFF : The value input by in numeric value input function has not been updated.
( Section 7.1 Numerical Display/Numerical Input) Battery Voltage Drop Detection
Signal (b3)
ON : GOT battery voltage low (It is recommend to replace it within a month after turning ON.) OFF : Normal
Handy GOT's Grip Switch Pressing Signal (b4)
ON : F94* Handy GOT's (except RH type) grip switch is being pressed.
OFF : F94* Handy GOT's grip switch is released.
Barcode Input Signal (b5)
ON : The data read by bar code reader has been stored into the specified device.
OFF : No data has been read by bar code reader.
( Section 12.4 Bar Code Function) Unused signal (b6 to b7) Not used.
OVERVIEW
PREPARATORY OPERATION FOR OBJECT SETTING
5
COMMON SETTINGS FOR OBJECTS
6
1 Confirm the error occurred in GOT (for GOT-A900 Series only)
The code of the error occurred in GOT can be confirmed.
The error codes within the range of error code 300 to 499 are displayed.
For the details of error code, refer to the following manuals.
GOT-A900 Series User's Manual
*1. When multiple errors occur simultaneously, the latest error code will be stored.
*2. Error code will not be cleared automatically even after the cause of error is removed.
Clear the error code by using the GOT error reset signal.
*3. Turn the GOT error reset signal OFF after error reset is completed.
If the GOT error reset signal is kept ON, error code will be reset when error occurs next time.
Error Reset Method
An error can be reset by using GOT as explained below.
When the cause of error is removed, error can be reset by touching the touch switch.
Example: Create the touch switch that keeps GOT error reset signal ON only while being touched.
Signal Name Description
Confirmation Signal during data change (b8)
ON : Turns ON when the data is changed by numeric value input and ASCII input function.
OFF : Turns OFF when the data is not changed by numeric value input and ASCII input function.
( Section 7.1 Numerical Display/Numerical Input)
Keypad information signal 1 (b9)
[Only in the F920GOT-K and F930GOT-K]
ON : Indicates that the cursor is displayed in the Alarm List Display or Alarm History Display.
OFF : Indicates that the cursor is not displayed in the Alarm List Display or Alarm History Display.
Keypad information signal 2 (b10)
[Only in the F920GOT-K and F930GOT-K]
ON : Indicates that the backlight is ON.
OFF : Indicates that the backlight is OFF.
Unused Signal (b9 to b15) Not used.
GOT status
"0"
Error occurs
Normal (cause of error removed) *2
OFF
ON
"0" is stored
OFF *3 ON
Error code storage *1 GOT error detection signal
(System Signal 2 'b13')
GOT error reset signal (System Signal 1 "b13") GOT error code (Write device)
GOT error reset signal (System signal1 "b13")
ON
OFF