Setting Item PLC Type GOT Type Base Screen Switching Device

Settings MELSEC-QnA,Q A97*GOT/GT SoftGOT D300

(2) Base screen No. 1 settings

MAIN MANU OF BLOCK A

LINE CONDITIONS

PRODUCTION CONDITIONS

OTHER BLOCK CONDITIONS

1) 2)

3)

No. Object Function to Be Set Setting Operation

1) Touch key function Base screen switching fixed value: 2 Setting made to switch to base screen No. 2.

2) Touch key function Base screen switching fixed value: 3 Setting made to switch to base screen No. 3.

3) Touch key function Base screen switching fixed value: 4 Setting made to switch to base screen No. 4.

(3) Base screen No. 2 settings

The devices of the master station assigned to the AJ65BTB1-16DT (remote I/O station) are monitored. (Monitor using cyclic transmission)

LINE CONDITIONS OF BLOCK A

PRODUCTION CONDITIONS

OTHER BLOCKS

1) 2) 3)

4) 5) 6)

TROUBLE OCCURRENCE

OPERATING CONDITON

LINE 1 LINE 2 LINE 3

MAIN

7) 8) 9)

No. Object Function to Be Set Setting Operation

1) Lamp display function Monitor device: X0 (RX0) to M0 2) Lamp display function Monitor device: X1 (RX1) to M1 3) Lamp display function Monitor device: X2 (RX2) to M2

Settings made for the remote I/O station to display on the GOT the line operating statuses (ON/OFF) stored in M0 to M3.

4) Lamp display function Monitor device: Y0 (RY0) from M112 5) Lamp display function Monitor device: Y1 (RY1) from M113 6) Lamp display function Monitor device: Y2 (RY2) from M114

Settings made to display on the GOT the fault occurrence information output to the remote I/O station.

7) Touch key function Screen switching device: Fixed at 1 Setting made to switch to base screen No. 1.

8) Touch key function Screen switching device: Fixed at 3 Setting made to switch to base screen No. 3.

9) Touch key function Screen switching device: Fixed at 4 Setting made to switch to base screen No. 4.

(4) Base screen No. 3 settings

The devices of the master station assigned to the GOT (intelligent device station) are monitored. (Monitor using cyclic transmission)

PRODUCTION CONDITION OF BLOCK A

1) 2) 3)

No. Object Function to Be Set Setting Operation

1) Numerical input function Write device Wr4 to D204 2) Numerical input function Write device Wr5 to D205 3) Numerical input function Write device Wr6 to D206

Settings made to store the values entered with the numerical input function into D204-D206.

4) Numerical display function Write device Ww4 from 104 5) Numerical display function Write device Ww5 from 105 6) Numerical display function Write device Ww6 from 106

Settings made to display the values stored in D104-D106.

7) Lamp display function Monitor device: Y20 (RY20) from M144 Settings made to display on the GOT the fault occurrence information stored in M144.

8) Touch key function Bit ALT: X20 (RX20) to M32 Setting made to store the ON/OFF information entered with the touch key function into M32.

9) Touch key function Screen switching device: Fixed at 1 Setting made to switch to base screen No. 1.

10) Touch key function Screen switching device: Fixed at 2 Setting made to switch to base screen No. 2.

11) Touch key function Screen switching device: Fixed at 4 Setting made to switch to base screen No. 4.

(5) Base screen No. 4 settings

The PLC CPU devices of the master station are directly specified and monitored.

(Monitor using Transient transmission)

PRODUCTION CONDITIONS OF OTHER BLOCKS

LINE

No. Object Function to Be Set Setting Operation

1) Lamp display function Monitor device: M200 2) Lamp display function Monitor device: M201

Settings made to display on the GOT the values stored in M200-M201.

3) Numerical input function Write device D300 4) Numerical input function Write device D301

Settings made to store the values entered with the numerical input function into D300-D301.

5) Touch key function Bit ALT: M202 6) Touch key function Bit ALT: M204

Settings made to store the ON/OFF information entered with the touch key function into M200-M201.

7) Touch key function Screen switching device: Fixed at 1 Setting made to switch to base screen No. 1.

8) Touch key function Screen switching device: Fixed at 2 Setting made to switch to base screen No. 2.

9) Touch key function Screen switching device: Fixed at 3 Setting made to switch to base screen No. 3.

The following is an example of setting the A8GT-J61BT13 switches.

Switch Name Setting Description

mode setting switch 0 Online (data link enabled and with automatic return)

10 0

Station number

setting switches 1 1 Station No. 1

Transmission baudrate

setting switch 0 156kBPS

SW1 OFF Input data state of data link error station: Clear Condition setting

switches SW2 OFF Number of occupied stations: 1 station

8.3.5 Parameter setting example (setting using GX Developer)

In the network parameter CC-Link list setting, set the first I/O No., total number of stations connected, remote I/O refresh devices, remote register refresh devices, and station information setting.

Setting the items of the following CC-Link list setting and CC-Link station information makes a GOT communication sequence program unnecessary.

Item Setting Screen Example

CC-Link list setting

CC-Link station information

9.1 System configuration

(1) System configuration and connection conditions

The following system configuration and connection conditions assume CC-Link connection (remote device station) with the PLC CPU.

The numbers ( to ) given in the system configuration denote the numbers ( to ) in "(2) System equipment".

Refer to these numbers when you want to confirm the types and applications.

Connection Conditions Number of

connected

Installation distance

System Configuration

32 GOTs (Max.)

Within 1200m (Longest)

Max. 1200m CC-Link dedicated cable

CC-Link system master/local unit *2*3

*1 The number of connected GOTs varies with the configuration of the CC-Link system, and the installation distance (maximum transmission distance) varies with the transmission speed of the CC-Link system.

For details, refer to the CC-Link System Master/Local Unit User's Manual (Details).

*2 On the CC-Link system, the GOT is handled as a slave station as described below.

Item Description

CC-Link station type Remote device station

Number of occupied stations 2 stations/4 stations (selectable)

*3 A termination resistor is needed to install the GOT at the end of the CC-Link system.

(2) System equipment

The following table indicates the system equipment needed for connection with the PLC CPU.

Image No. Application Type

GOT unit CC-Link communication unit

CC-Link connected (remote device station) GOT

A985GOT(-V), A97*GOT, A960GOT,

A956WGOT, A956GOT A8GT-J61BT15

CC-Link system master/local unit

QJ61BT11, QJ61BT11N *1,

AJ61QBT11, A1SJ61QBT11, AJ61BT11, A1SJ61BT11

CC-Link dedicated cable Refer to the user's manual of the CC-Link master/local unit used.

*1 Set the station No. that corresponds to the GOT as Ver.1 intelligent device station in the CC-Link parameter settings of GX Developer.

9

9.2.1 Monitoring Overview

When the A8GT-J61BT15 is used, the GOT has the following two monitoring methods.

Monitor Method Normal Monitor Dedicated Command Monitor

Description

The remote inputs/outputs and remote registers of the GOT assigned to the remote device station in the CC-Link parameter setting are specified and monitored.

The remote register area is used as the GOT internal device transfer command area to specify and monitor the GOT internal devices.

Advantage Data update processing speed is high.

Data update processing speed is high.

Since a dedicated command is executed to develop data in the GOT internal word devices (GD0 to GD1023), multiple pieces of

information, such as the operating status, production and operation directives, can be monitored within one screen.

(The number of devices that can be displayed on one screen is larger than that of normal monitor.)

Disadvantage

As the remote register assignment area of the GOT is small, the number of devices that can be displayed on one screen is small.

A sequence program is needed to execute the dedicated command.