Data link system (MELSECNET/B, (II)) access range for monitoring

(6) When using Ethernet connection

2.3.1 Data link system (MELSECNET/B, (II)) access range for monitoring

(1) Bus connection/CPU direct connection/Computer link connection (a) If connected to master station

• Local stations can be monitored. If the PLC CPU of the local station is QnACPU, devices other than B and W that are allocated by the link parameter cannot be monitored.

L3 M L1

L2

GOT

(b) If connected to local station

• The master station can be monitored.

If the PLC CPU of the local station is QnACPU, devices other than B and W that are allocated by the link parameter cannot be monitored.

• Other local stations cannot be monitored.

(c) If connected to the master station on the third layer

• The master station on the second layer and local stations on the third layer can be monitored. If the PLC CPU of the local station is QnACPU, devices other than B and W that are allocated by the link parameter cannot be monitored.

• Local stations on the second layer cannot be monitored.

GOT

(2) MELSECNET/B connection and MELSECNET(II) connection

• The GOT is regarded as a local station and can monitor only the master station. If the PLC CPU of the local station is QnACPU, devices other than B and W that are allocated by the link parameter cannot be monitored.

• Local devices cannot be monitored.

When setting the monitor device, designate the NW number and the station number as follows.

When monitoring devices B and W that are allocated by the link parameter : NW number : 0, Station number : Local When monitoring devices other than B and W of the master station :

NW number : 0, Station number : Others (Station number : 0)

GOT

For monitoring devices B and W that are allocated by the link parameter, make sure to use the local device number if designating devices allocated to other station.

If not, display speed will be reduced.

significantly reduced. Therefore monitor link relay (B) and link register (W) that are allocated by the link parameter.

(4) Setting method of monitor device

Describes the NW numbers for setting monitor devices and method of setting station numbers with an example shown below.

GOT L3 M L1

L2m

3 1

2

(a) When monitoring devices B and W that are allocated by the connected station (local station) and link parameter :

NW number : 0, Station number : Local (b) When monitoring devices of other stations :

NW number : 0, Station number : Refer to the following table.

Station number setting

Station connected to GOT

Station to be

accessed M L1 L2

m L3 1 2 3

M Local Other 1 Other 2 Other 3

L1 Other 0 Local

L2

m Other 0 Local Other 1 Other 2

L3 Other 0 Local

1 Other 0 Local

2 Other 0 Local

3(GOT) Other 0

POINT

For monitoring devices B and W that are allocated by the link parameter, make sure to use the local device number if designating devices allocated to other station.

If not, display speed will be reduced.

(1) Bus connection

(a) If connected to multi-PLC system

1) The control station on the network and all normal stations can be monitored.

2) The control station on the other network and all normal stations can be monitored.

(To monitor the other network, be sure to designate the routing parameter.) 3) When the monitor target is the multi-PLC system, CPU No. 1 to No. 4 can be

monitored.

4) Devices of other stations (other than devices B and W that are allocated by the network parameter) may not allow monitoring depending on their PLC CPU.

Refer to Examples 1 to 4.in (7).

The motion controller CPU (Q Series) at other stations cannot be monitored.

(b) If connected to QCPU(Q Mode)/QnACPU/AnUCPU

1) The control station on the network and all normal stations can be monitored.

2) The control station on the other network and all normal stations can be monitored.

(To monitor the other network, be sure to designate the routing parameter.) 3) If connected to an intermediate station and the data link system is included,

the master station and local stations can be monitored.

4) If connected to an intermediate station, it is not necessary to designate the data link parameter "Effective unit number for accessing other stations" for the PLC CPU of the connected station. (If designated, the parameter will be ignored.)

5) Devices of other stations (other than devices B and W that are allocated by the network parameter) may not allow monitoring depending on their PLC CPU.

Refer to Examples 1 to 4.in (7).

(c) If connected to AnACPU/AnNCPU

1) Control stations on the network can be monitored.

If the PLC CPU of the local station is QCPU (Q Mode)/QnACPU, devices other than B and W that are allocated by the network parameter cannot be monitored.

2) Normal stations on the network cannot be monitored.

3) Stations on the other network cannot be monitored.

(2) CPU direct connection/computer link connection (a) If connected to multi-PLC system

1) Access range is as described in (1) (a).

(b) If connected to QCPU (Q Mode)/QnACPU 1) Access range is as described in (1) (b).

(c) If connected to QCPU (A Mode)/AnUCPU

1) Control station on the network and all normal stations can be monitored.

When devices of other stations (other than devices B and W that are allocated by the network parameter) are monitored, monitoring is not available if the PLC CPU to be monitored is QCPU (Q Mode)/QnACPU.

2) If connected to an intermediate station, use data link parameter "Effective unit number to access other stations" to designate the unit number that is connected to the network to be monitored.

(d) If connected to AnACPU/AnNCPU

1) Control stations on the network can be monitored.

If the PLC CPU of the control station is QCPU (Q Mode)/QnACPU, devices other than B and W that are allocated by the network parameter cannot be monitored.

2) Normal stations on the network cannot be monitored.

3) The other network cannot be monitored.

monitored.

• Other stations on the network system cannot be monitored.

(4) MELSECNET/10 connection

(a) The GOT is regarded as a normal station. The control station on the network and all normal stations can be monitored.

If the PLC CPU to be monitored is QCPU (Q Mode)/QnACPU, monitoring is available within the device access range for AnA. (The access range for monitoring of timer (T) and counter (C) is limited to 0 to 225. File registers (R, ER, ZR) cannot be monitored.)

When the PLC CPU of the monitor target is the multi-PLC system, the control PLC of the network unit can be monitored.

(b) The other network cannot be monitored.

(c) If devices of other stations (other than devices B and W that are allocated by the network parameter) are monitored, monitoring may not be available depending on the PLC CPU of the network system to be monitored. Refer to (Example 6).

(5) Monitoring devices of other stations on network

If devices of other stations on the network system are monitored, display speed will be significantly reduced. Therefore monitor link relay (B) and link register (W) that are allocated by the network parameter.

(6) Monitoring devices of the other network

(a) Be sure to designate the routing parameter to the PLC CPU of the connected station.

(b) If the other network is monitored, display speed of object etc. will be significantly reduced.

(7) Monitor access range of other stations and setting method of monitor devices (Example 1) When using bus connection

Control station

(1-2) Network No.1 Network No.2

Control station

• Monitor access range of other station devices (other than B and W)/other network

Network No.1 Network No.2

Station connected to GOT

Station to be accessed

{ : Accessible ×: Not accessible

1) Monitoring devices B and W that are allocated by the network parameter at the connected station (local station)

NW number: 0, Station number: Local

2) When monitoring other stations (other than B and W)/other network

Network No.1 Network No.2

Station connected to GOT

Station to be accessed

How to read the

table 2, Other (2)

NW number Station number (Example 2) When using bus connection

GOT Data link system

(2-3)

Control station Control station

Network No.2

• Monitor access range of other station devices (other than B and W)/other network

Network No.1 Network No.2 Data link system

Station connected to GOT

Station to be accessed

{ : Accessible : Accessible within the range for AnA (T/C: 0 to 255, R/ER/ZR cannot be monitored)

× : Not accessible For monitoring devices B

and W that are allocated by the network parameter, make sure to use the local device number if designating devices allocated to other station.

If not, display speed will be reduced.

parameter at the connected station (local station) NW number: 0, Station number: Local station

2) When monitoring other stations (other than B and W)/other network

Network No.1 Network No.2 Data link system

Station connected to GOT

Station to be accessed

*1 When monitoring the data link system, designate the NW number as 0.

How to read the

table 2, Other (2)

NW number Station number by the network parameter,

make sure to use the local device number if designating devices allocated to other station.

If not, display speed will be reduced.

Control station

Network No. 2

*1 Data link parameter "Effective unit number for accessing other stations" is designated to the unit number that is connected to the network No. 1.

• Monitor access range of other station devices (other than B and W)/other network

Network No.1 Network No.2

Station connected to GOT

Station to be accessed

{ : Accessible ×: Not accessible

• Designating NW number and station number for setting monitor device 1) Monitoring devices B and W that are allocated by the network parameter at

the connected station (local station) NW number: 0, Station number: Local

2) When monitoring other stations (other than B and W)/other network

Network No.1 Network No.2

Station connected to GOT

Station to be accessed

How to read the

table 2, Other (2)

NW number Station number POINT

For monitoring devices B and W that are allocated by the network parameter, make sure to use the local device number if designating devices allocated to other station.

If not, display speed will be reduced.

GOT

Network No. 1

AnA

Data link system (2-3) Network No. 2

• Monitor access range of other station devices (other than B and W)/other network

Network No.1 Network No.2 Data link system

Station connected to GOT

Station to

beaccessed Q(Q Mode) (1-1)

{ : Accessible : Accessible within the range for AnA (T/C: 0 to 255, R/ER/ZR cannot be monitored)

× : Not accessible

1) When monitoring devices B and W that are allocated by the network parameter at the connected station (local station)

NW number: 0, Station number: Local station

2) When monitoring other stations (other than B and W)/other network

Network No.1 Network No.2 Data link system

Station

*1 When monitoring the data link system, designate the NW number as 0.

How to read the

table 2, Other (2)

NW number Station number For monitoring devices B

and W that are allocated by the network parameter, make sure to use the local device number if designating devices allocated to other station.

If not, display speed will be reduced.

(1-1)

AnU (1-4)

When using MELSECNET/10 connection, the other network cannot be monitored.

GOT Q(Q Mode)

(1-2)

(1-3)

• Monitor access range for other station devices (other than B and W)

Station connected to GOT

Station to be accessed QnA

(1-4) { : Accessible

GOT (1-3) {

: Accessible within the range of AnA

(T/C: 0 to 255, R/ER/ZR cannot be monitored.)

× : Not accessible y Designating NW number and station number for setting monitor device

1) Monitoring devices B and W that are allocated by network parameter NW number: 0, Station number: Local

2) Monitoring other stations (other than B and W)

Station connected to GOT

Station to be accessed QnA

NW number Station number

(Example 6) When using CC-Link connection (intelligent device station) /CC-Link connection (via G4)

Network Unit (1-2) CC-Link Master Unit (0 station)

Network

Image of CC-Link Conection

Station connected to GOT

Station to be

accessed QnA

For monitoring devices B and W that are allocated by the network parameter, make sure to use the local device number if designating devices allocated to other station.

If not, display speed will be reduced.

(1) When using Bus connection/CPU direct connection/computer link connection Only connected stations can be monitored.

(2) When using CC-link connection (remote device station) (a) Access range

Devices RX, RY, RWw, RWr for which the GOT is allocated to the master station by setting the CC-Link parameter and the internal device of the GOT can be monitored.

Other devices RX, RY, RWw, RWr allocated to the master station cannot be monitored.

(b) Designating NW number and station number Be sure to designate as follows.

NW number:0, Station number: Local (c) Designating device name and device number

Use the following device names.

For devices RX, RY, RWw and RWr, designate the addresses allocated by station number setting.

Device to be monitored Device name to be set by

GT Designer Device setting range

Remote input RX X X0 to X7FF

Remote output RY Y Y0 to Y7FF

Remote register (writing area) RWw Ww Ww0 to WwFF

Remote register (reading area) RWr Wr Wr0 to WrFF

GOT internal bit device GB GB GB0 to GB1023

GOT internal word device GD GD GD0 to GD1023

Master station/local station can be monitored.

By setting CC-Link parameter, all devices RX, RY, RWw and RWr that are allocated to the master station can be monitored.

When the monitor target is the multi-PLC system, CPU No. 1 to No. 4 can be monitored.

(b) Setting NW number and station number

1) When monitoring devices RX, RY, RWw and RWr that are allocated to the master station by setting CC-Link parameter

NW number: 0, PLC station number: Local

2) When monitoring PLC CPU devices of other station

NW number: 0, PLC station number: Other (Station number: n)

(n: Station number of other station you want to monitor (0: Master station, 1-64: Local station))

(c) Setting device name and device number

1) Monitoring devices RX, RY, RWw and RWr that are allocated by setting CC-Link parameter

Use the following device names.

For devices RX, RY, RWw and RWr, designate the addresses allocated by station number setting.

Device to be monitored Device name to be set by

GT Designer Device setting range

Remote input RX X X0 to X7FF

Remote output RY Y Y0 to Y7FF

Remote register (writing area) RWw Ww Ww0 to WwFF

Remote register (reading area) RWr Wr Wr0 to WrFF

2) Monitoring PLC CPU devices of other stations

For device name and device number, refer to the GT Works Version 5/GT Designer Version 5 Reference Manual.

(4) When using CC-Link connection (via G4) (a) Access range

Master station/local station can be monitored.

(b) Setting NW number and station number 1) When monitoring master station

NW number: 0, PLC station number: Host/other (station number: 0) 2) Monitoring local station

NW number: 0, PLC station number: Other (station number: 1 to 64) (c) Setting device name and device number

For the device names and device numbers, refer to the GT Works Version 5/GT Designer Version 5 Reference Manual.

POINT

For monitoring devices RX, RY, RWw and RWr that are allocated

by setting CC-Link parameter, make sure to use the local device number if designating devices allocated to other station.

If not, display speed will be reduced.

2.3.4 Access range for monitoring when using Ethernet connection