Description of Manual (Built-in Positioning Function)

2. GX Developer

1) GX Developer English version (SWD5C-GPPW-E) is applicable to FX3G/FX3U/FX3UC PLCs from the following versions.

2) GX Developer Japanese version (SWD5C-GPPW-J) is applicable to FX3G/FX3U/FX3UC PLCs from the following versions.

Point:

• It is possible to create programs in FX3GC PLC using programming tools of inapplicable versions by selecting "FX3G" as the alternative model.

• It is possible to create programs in FX3S PLC using programming tools of inapplicable versions by selecting "FX3G" as the alternative model. However, memory capacity setting of the PLC parameter must be set to 4000 steps or less.

Model name PLC version Applicable GX Works2

version Remarks

FX3S PLC Ver. 1.00 or later Ver. 1.492N or later

-FX3G PLC Ver. 1.00 or later Ver. 1.08J or later

-FX3GC PLC Ver. 1.40 or later Ver. 1.77F or later

-FX3U PLC Ver. 2.20 or later Ver. 1.08J or later

-FX3UC PLC Ver. 1.00 or later Ver. 1.08J or later

-Model name PLC version Applicable GX Works2

version Remarks

FX3S PLC Ver. 1.00 or later Ver. 1.492N or later

-FX3G PLC Ver. 1.00 or later Ver. 1.07H or later

-FX3GC PLC Ver. 1.40 or later Ver. 1.77F or later

-FX3U PLC Ver. 2.20 or later Ver. 1.07H or later

-FX3UC PLC Ver. 1.00 or later Ver. 1.07H or later

-Model name PLC version Applicable

GX Developer version Remarks

FX3G PLC Ver. 1.00 or later Ver. 8.72A or later

-FX3U PLC Ver. 2.20 or later Ver. 8.24A or later

-FX3UC PLC Ver. 1.00 or later Ver. 8.18U or later

-Ver. 2.20 or later Ver. 8.24A or later The built-in positioning setting was added

Model name PLC version Applicable

GX Developer version Remarks

FX3G PLC Ver. 1.00 or later Ver. 8.72A or later

-FX3U PLC Ver. 2.20 or later Ver. 8.23Z or later

-FX3UC PLC

Ver. 1.00 or later Ver. 8.13P or later

-Ver. 1.30 or later Ver. 8.18U or later

-Ver. 2.20 or later Ver. 8.23Z or later The built-in positioning setting was added

FX /FX /FX /FX /FX PLC User's Manual - Positioning Control Edition

Built-in Positioning Functions 1.5 Assignment of Input/Output Numbers

1.5 Assignment of Input/Output Numbers

1.5.1 Assignment of Input Numbers

Assign the input numbers of the FX3S/FX3G/FX3GC/FX3U/FX3UC PLC as follows:

Application Input number Remarks

Stop command All input points

Connect a line to any input.

If the line-connected input is turned on, turn off the positioning instruction signal must be turned off.

Zero return command

All input points

Connect a line to any input.

If the line-connected input is turned on, the DSZR or ZRN instruction must be turned on.

Near-point signal (DOG)

All input points

Connect a line to the input of the near-point signal (DOG) specified by DSZR or ZRN instruction.

For details on the near-point signal of the DSZR instruction, refer to Section 6.2.

For details on the near-point signal of the ZRN instruction, refer to Section 6.3.

Point:

• To use the ZRN instruction:

If X000 to X007*1 of the main unit are set for the near-point signal (DOG), the PLC interruption function will be used for processing of the near-point signal (DOG).

Zero-phase signal

X000 to X007*1

Connect a line to the input specified for the zero-phase signal (this input is specified by DSZR instruction).

ABS read All input points

Connect a line if it is necessary to use the absolute position detection system.

Connect a line to the input specified by the ABS instruction.

Use 3 consecutive input points for this function.

JOG command All input points

Connect a line to any input.

If the line-connected input is turned on, the DRVI instruction for the jogging motion must be turned on.

FX /FX /FX /FX /FX PLC User's Manual - Positioning Control Edition Built-in Positioning Functions

A

Comm

on Items

Functions Positioning

B

Built-in

Apx.

Connection Example 1.5 Assignment of Input/Output Numbers

Interrupt input X000 to X007

The interrupt input depends on the pulse output destination specified by the DVIT instruction*2 as shown in the following table. If the version number of the PLC is 1.30 or higher, the interrupt input can be specified.

FX3UC PLC Ver. 1.30 or later

If the interrupt input specification function is used, register D8336 (interrupt input specification register) can specify the interrupt input number (X000 - X007) for each pulse output destination.

 For details on the interrupt input specification method, refer to Subsection 4.3.7.

FX3U/FX3UC PLC*4 Ver. 2.20 or later

If the interrupt input specification function is used, register D8336 (interrupt input specification register) can specify the interrupt input number (X000 - X007) for each pulse output destination, or the user interrupt input command can be specified.

 For details on the user interrupt input command, refer to Subsection 4.3.7.

The user interrupt input command depends on the pulse output destination as shown in the following table.

Forward rotation limit (LSF)

All input points

Connect a line to any input.

If the line-connected input is turned on, the forward limit relay must be turned on.

The forward limit relay depends on the pulse output destination as shown in the following table.

Reverse rota-tion limit (LSR)

All input points

Connect a line to any input.

If the line-connected input is turned on, the reverse limit relay must be turned on.

The reverse limit relay depends on the pulse output destination as shown in the following table:

Application Input number Remarks

Pulse output destination Interrupt input

Y000 X000

Y001 X001

Y002 X002

Y003*3 X003

Pulse output destination User interrupt input command

Y000 M8460

Y001 M8461

Y002 M8462

Y003*3 M8463

Pulse output destination Forward limit relay

Y000 M8343

Y001 M8353

Y002*5 M8363

Y003*3 M8373

Pulse output destination Reverse limit relay

Y000 M8344

Y001 M8354

Y002*5 M8364

Y003*3 M8374

FX /FX /FX /FX /FX PLC User's Manual - Positioning Control Edition

Built-in Positioning Functions 1.5 Assignment of Input/Output Numbers

*1. X000 to X005 for FX3S PLC.

*2. Interrupt outputs are supported only in the FX3U and FX3UC PLC.

*3. Y003 can be specified as the pulse output destination only if 2 high-speed output special adapters are connected to the FX3U PLC.

*4. Ver. 2.20 is assigned to the initial product of the FX3U PLC.

*5. Y002 is not available in FX3G PLC (14-point and 24-point type) and FX3S/FX3GC PLC.

1.5.2 Assignment of Output Numbers