Description of Manual (Built-in Positioning Function)
2. Source internal output circuit
FX /FX /FX /FX /FX PLC User's Manual - Positioning Control Edition
Built-in Positioning Functions 2.5 Output Specifications
FX /FX /FX /FX /FX PLC User's Manual - Positioning Control Edition
Built-in Positioning Functions 2.5 Output Specifications
A
Common Items
Functions Positioning
B
Built-inApx.
Connection Example2.5.2 FX
3GSeries main unit (Transistor Output)
This section describes the transistor output specifications of the FX3G Series main unit. Note that the simultaneous turning-on rate is restricted for the output extension units and the main unit. For details on this restriction, refer to the following manual.
Refer to the FX3G Hardware Edition.
For MELSERVO Series amplifiers, use a sink input/sink output type PLC.
Pulse output terminals Y000, Y001, and Y002*1 are high-speed response output terminals.
To use the positioning instruction, adjust the load current of the NPN open collector to 10 to 100 mA (5 to 24 V DC).
*1. Y002 works as a high-speed response pulse output terminal only in 40-point and 60-point type main units.
Item Transistor output specifications
External voltage All outputs 5 to 30 V DC
Maximum load
Resistance load All outputs
The total load current of resistance loads per common terminal should be the following value or less.
- 1 point output common:0.5 A - 4 points output common:0.8 A
Inductive load All outputs
The total of inductive loads per common terminal should be the following value or less.
- 1 point output common:12 W/24 V DC - 4 points output common:19.2 W/24 V DC Open-circuit leakage current All outputs 0.1 mA or less at 30 V DC
ON voltage All outputs 1.5 V or less
Response time
14-point, 24-point type
OFFON Y000, Y001 5 s or less at 10 mA or more (5 to 24 V DC) Y002 or more 0.2 ms or less at 200 mA or more (at 24 V DC) ONOFF Y000, Y001 5 s or less at 10 mA or more (5 to 24 V DC)
Y002 or more 0.2 ms or less at 200 mA or more (at 24 V DC)
40-point, 60-point type
OFFON Y000 to Y002 5 s or less at 10 mA or more (5 to 24 V DC) Y003 or more 0.2 ms or less at 200 mA or more (at 24 V DC) ONOFF Y000 to Y002 5 s or less at 10 mA or more (5 to 24 V DC)
Y003 or more 0.2 ms or less at 200 mA or more (at 24 V DC)
Circuit insulation All outputs Photocoupler insulation
Indication of output motion All outputs LED is lit when the photocoupler is driven.
Item Description
Operation voltage range 5 to 24 V DC Operation current range 10 to 100 mA Output frequency 100 kHz or less
FX /FX /FX /FX /FX PLC User's Manual - Positioning Control Edition
Built-in Positioning Functions 2.5 Output Specifications
1. Sink internal output circuit
2. Source internal output circuit
*1. To ground the unit, refer to the servo amplifier (drive unit) manual. If the grounding method is not specified, carry out class-D grounding.
*2. For MELSERVO Series amplifiers, use a sink output type FX3G Series main unit.
Grounding*1 Servo amplifier (Drive unit) 5 to 24V DC
Pulse train signal
Direction signal Y000
COM0 Y004
COM3 FX3G Series
main unit
Grounding*1
Servo amplifier*2
(Drive unit) 5 to 24V DC
Pulse train signal
Direction signal
+V3 Y004
+V0 Y000 FX3G Series
main unit
FX /FX /FX /FX /FX PLC User's Manual - Positioning Control Edition
Built-in Positioning Functions 2.5 Output Specifications
A
Common Items
Functions Positioning
B
Built-inApx.
Connection Example2.5.3 FX
3GCSeries main unit (Transistor Output)
This section describes the transistor output specifications of the FX3GC Series main unit. Note that the simultaneous turning-on rate is restricted for the output extension units and the main unit. For details on this restriction, refer to the following manual:
Refer to the FX3GC Hardware Edition.
For MELSERVO Series amplifiers, use a sink input/sink output type PLC.
*1. When the two COM1 terminals are connected outside the PLC, resistance load is 1.6 A or less.
Pulse output terminals Y000 and Y001 are high-speed response output terminals.
To use the positioning instruction, adjust the load current of the NPN open collector to 10 to 100 mA (5 to 24 V DC).
1. Sink internal output circuit
*2. To ground the unit, refer to the servo amplifier (drive unit) manual. If the grounding method is not specified, carry out class-D grounding.
Item Transistor output specifications
External voltage All outputs 5 to 30 V DC
Maximum load
Resistance load
Y000, Y001 0.3 A/point The total load current of the common items (8 points) should be 0.8 A*1 or less.
Y002 to Y017 0.1 A/1point
Inductive load
Y000, Y001 7.2 W/1point
(24 V DC) The total load of the common items (16 points) should be 38.4 W or less at 24 V DC.
Y002 to Y017 2.4 W/1point (24 V DC)
Open-circuit leakage current All outputs 0.1 mA or less at 30 V DC
ON voltage All outputs 1.5 V or less
Response time
OFFON Y000, Y001 5 s or less at 10 mA or more (5 to 24 V DC) Y002 to Y017 0.2 ms or less at 100 mA (at 24 V DC) ONOFF Y000, Y001 5 s or less at 10 mA or more (5 to 24 V DC)
Y002 to Y017 0.2 ms or less at 100 mA (at 24 V DC)
Circuit insulation All outputs Photocoupler insulation
Indication of output motion All outputs LED is lit when the photocoupler is driven.
Item Description
Operation voltage range 5 to 24 V DC Operation current range 10 to 100 mA Output frequency 100 kHz or less
Y0
Y4 Main unit
Grounding*3
Servo amplifier (Drive unit) Pulse train signal
Direction signal
5 to 24 V DC
COM1 FX3GC-32MT/D
FX /FX /FX /FX /FX PLC User's Manual - Positioning Control Edition
Built-in Positioning Functions 2.5 Output Specifications
2. Source internal output circuit
*1. To ground the unit, refer to the servo amplifier (drive unit) manual. If the grounding method is not specified, carry out class-D grounding.
*2. For MELSERVO Series amplifiers, use a sink output type FX3GC Series main unit . Y0
Y4 Main unit
Grounding*1
Servo amplifier*2 (Drive unit) Pulse train signal
Direction signal
5 to 24 V DC
+V0 FX3GC-32MT/DSS
FX /FX /FX /FX /FX PLC User's Manual - Positioning Control Edition
Built-in Positioning Functions 2.5 Output Specifications
A
Common Items
Functions Positioning
B
Built-inApx.
Connection Example2.5.4 FX
3USeries main unit (Transistor Output)
This section describes the transistor output specifications of the FX3U Series main unit. Please note that the simultaneous turning-on rate is restricted for the output extension units and the main unit. For details on the restriction, refer to the following manual.
Refer to the FX3U Hardware Edition.
For MELSERVO Series amplifiers, use a sink input/sink output type PLC.
Pulse output terminals Y000, Y001, and Y002 are high-speed response output terminals.
To use the positioning instruction, adjust the load current of the NPN open collector to 10 to 100 mA (5 to 24 V DC).
Item Transistor output specifications
External voltage All outputs 5 to 30 V DC
Maximum load
Resistance load All outputs
The total load current of resistance loads per common termi-nal should be the following value or less.
- 1 point output common:0.5 A - 4 points output common:0.8 A - 8 points output common:1.6 A
Inductive load All outputs
The total of inductive load per common terminal should be the following value or less.
- 1 point output common:12 W/24 V DC - 4 points output common:19.2 W/24 V DC - 8 points output common:38.4 W/24 V DC Open-circuit leakage current All outputs 0.1 mA or less at 30 V DC
ON voltage All outputs 1.5 V or less
Response time
OFFON Y000 to Y002 5 s or less at 10 mA or more (5 to 24 V DC) Y003 or more 0.2 ms or less at 200 mA (at 24 V DC) ONOFF Y000 to Y002 5 s or less at 10 mA or more (5 to 24 V DC)
Y003 or more 0.2 ms or less at 200 mA (at 24 V DC) Circuit insulation All outputs Photocoupler insulation
Indication of output motion All outputs LED is lit when the photocoupler is driven.
Item Description
Operation voltage range 5 to 24 V DC Operation current range 10 to 100 mA Output frequency 100 kHz or less
FX /FX /FX /FX /FX PLC User's Manual - Positioning Control Edition
Built-in Positioning Functions 2.5 Output Specifications
1. Sink internal output circuit
*1. To ground the unit, refer to the servo amplifier (drive unit) manual. If the grounding method is not specified, carry out class-D grounding.
2. Source internal output circuit
*2. To ground the unit, refer to the servo amplifier (drive unit) manual. If the grounding method is not specified, carry out class-D grounding.
*3. For MELSERVO Series amplifiers, use a sink output type FX3U Series main unit.
FX3U Series main unit
Grounding*1 Servo amplifier (Drive unit) 5 to 24V DC
Pulse train signal
Direction signal Y000
COM1
Y004 COM2
FX3U Series main unit
Grounding*2 Servo amplifier*3 (Drive unit) 5 to 24V DC
Pulse train signal
Direction signal
+V1 Y004
+V0 Y000
FX /FX /FX /FX /FX PLC User's Manual - Positioning Control Edition
Built-in Positioning Functions 2.5 Output Specifications
A
Common Items
Functions Positioning
B
Built-inApx.
Connection Example2.5.5 FX
3UCSeries main unit (Transistor Output)
This section describes the transistor output specifications of the FX3UC Series main unit. Note that the simultaneous turning-on rate is restricted for the output extension units and the main unit. For details on this restriction, refer to the following manual:
Refer to the FX3UC Hardware Edition.
For MELSERVO Series amplifiers, use a sink input/sink output type PLC.
*1. When the two COM1 terminals are connected outside the PLC, resistance load is 1.6 A or less.
*2. The FX3UC-32MT-LT(-2) uses the display module for monitoring.
Pulse output terminals Y000, Y001, and Y002 are high-speed response output terminals.
To use the positioning instruction, adjust the load current of the NPN open collector to 10 to 100 mA (5 to 24 V DC).
1. Sink internal output circuit
*3. To ground the unit, refer to the servo amplifier (drive unit) manual. If the grounding method is not specified, carry out class-D grounding.
Item Transistor output specifications
External voltage All outputs 5 to 30 V DC
Maximum load
Resistance load
Y000 to Y003 0.3 A/point The total load current of the common items (8 points) should be 0.8 A*1 or less.
Y004 or more 0.1 A/1point
Inductive load
Y000 to Y003 7.2 W/1point
(24 V DC) The total load of the common items (16 points) should be 38.4 W or less at 24 V DC.
Y004 or more 2.4 W/1point (24 V DC)
Open-circuit leakage current All outputs 0.1 mA or less at 30 V DC
ON voltage All outputs 1.5 V or less
Response time
FX3UC-32MT-LT FX3UC-32MT-LT-2
OFFON ONOFF
Y000 to Y003 5 s or less at 10 mA or more (5 to 24 V DC) Y004 to Y017 0.2 ms or less at 100 mA (at 24 V DC) FX3UC-MT/D
FX3UC-MT/DSS
OFFON ONOFF
Y000 to Y002 5 s or less at 10 mA or more (5 to 24 V DC) Y003 or more 0.2 ms or less at 100 mA (at 24 V DC)
Circuit insulation All outputs Photocoupler insulation
Indication of output motion All outputs LED is lit when the photocoupler is driven.*2
Item Description
Operation voltage range 5 to 24 V DC Operation current range 10 to 100 mA Output frequency 100 kHz or less
Y0
Y4 FX3UC- MT/D
FX3UC-32MT-LT(-2) Main unit
Grounding*3
Servo amplifier (Drive unit) Pulse train signal
Direction signal
5 to 24 V DC
COM1
FX /FX /FX /FX /FX PLC User's Manual - Positioning Control Edition
Built-in Positioning Functions 2.5 Output Specifications
2. Source internal output circuit
*1. To ground the unit, refer to the servo amplifier (drive unit) manual. If the grounding method is not specified, carry out class-D grounding.
*2. For MELSERVO Series amplifiers, use a sink output type FX3UC Series main unit . Y0
Y4 FX3UC- MT/DSS
Main unit
Grounding*1
Servo amplifier*2 (Drive unit) Pulse train signal
Direction signal
5 to 24V DC
+V0
FX /FX /FX /FX /FX PLC User's Manual - Positioning Control Edition
Built-in Positioning Functions 2.5 Output Specifications
A
Common Items
Functions Positioning
B
Built-inApx.
Connection Example2.5.6 High-Speed Output Special Adapter [FX
3U-2HSY-ADP]
This section describes the output specifications of the high-speed output special adapter (FX3U-2HSY-ADP).