• 沒有找到結果。

List of Alternative I/O Module Models

5 5 REPLACING I/O MODULE

5.1 List of Alternative I/O Module Models

MELSECNET/MINI-S3, A2C models

to be discontinued Alternative model for CC-Link

Product name Model name Model name Remarks (restrictions)

Input module

AX11C AJ65SBTB2N-16A

1) Change in external wiring: Required

2) Change in number of modules (2 modules necessary) 3) Change in program

Change in number of occupied I/O points: Required 4) Change in specifications

Change in rated input voltage: Not required Change in rated input current: Required Change in ON voltage/ON current: Not required Change in OFF voltage/OFF current: Required Change in input resistance: Required

5) Change in functions: Required (2-wire type for inputs)

AX21C None

No alternative model

• Please consider using the FA goods

FA-TH16X200A31L. (The FA goods are manufactured by Mitsubishi Electric Engineering Co., Ltd.) The 24VDC input module for CC-Link (AJ65SBTCF1-32D) is required to use the FA goods.

AX31C AJ65SBTB1-32D

1) Change in external wiring: Required 2) Change in number of modules: Not required 3) Change in program

Change in number of occupied I/O points: Not required 4) Change in specifications

Change in rated input voltage: Required (12/24VAC, 12VDC not allowed)

Change in rated input current: Not required Change in ON voltage/ON current: Required Change in OFF voltage/OFF current: Required Change in input resistance: Required Change in input response time: Required

(35/30ms 1.5ms)

5) Change in functions: Required (12/24VAC, 12VDC not allowed)

5 REPLACING I/O MODULE

Input module

AJ35PTF-32A*1 AJ65SBTB2N-16A

1) Change in external wiring: Required

2) Change in number of modules (2 modules necessary) 3) Change in program

Change in number of occupied I/O points: Required 4) Change in specifications

Change in rated input voltage: Not required Change in rated input current: Required Change in ON voltage/ON current: Required Change in OFF voltage/OFF current: Required Change in input resistance: Required

5) Change in functions: Required (2-wire type for inputs)

AX41C AJ65SBTB1-32D

1) Change in external wiring: Required 2) Change in number of modules: Not required 3) Change in program

Change in number of occupied I/O points: Not required 4) Change in specifications

Change in rated input voltage: Required (12VDC not allowed)

Change in rated input current: Not required Change in ON voltage/ON current: Required Change in OFF voltage/OFF current: Required Change in input resistance: Not required Change in input response time: Required

(10ms 1.5ms)

5) Change in functions: Required (12VDC not allowed) MELSECNET/MINI-S3, A2C models

to be discontinued Alternative model for CC-Link

Product name Model name Model name Remarks (restrictions)

5 REPLACING I/O MODULE

MELSECNET/MINI-S3, A2C models to be

discontinued Alternative models for CC-Link

Product name Model name Model name Remarks (restrictions)

Input module

AX41C AJ65DBTB1-32D

1) Change in external wiring: Required (Communication cable and power cable only)

2) Change in number of modules: Not required 3) Change in program

Change in number of occupied I/O points: Not required

4) Change in specifications

Change in rated input voltage: Required (12VDC not allowed)

Change in rated input current: Required Change in ON voltage/ON current: Required Change in OFF voltage/OFF current: Required Change in input resistance: Required Change in input response time: Not required 5) Change in functions: Required (12VDC not allowed)

AX81C

AJ65SBTB1-32D

1) Change in external wiring: Required 2) Change in number of modules: Not required 3) Change in program

Change in number of occupied I/O points: Not required

4) Change in specifications

Change in rated input voltage: Required (12VDC not allowed)

Change in rated input current: Not required Change in ON voltage/ON current: Required Change in OFF voltage/OFF current: Required Change in input resistance: Not required Change in input response time: Required

(10ms 1.5ms)

5) Change in functions: Required (12VDC not allowed)

AJ65DBTB1-32D

1) Change in external wiring: Required (Communication cable and power cable only)

2) Change in number of modules: Not required 3) Change in program

Change in number of occupied I/O points: Not required

4) Change in specifications

Change in rated input voltage: Required (12VDC not allowed)

Change in rated input current: Required Change in ON voltage/ON current: Required Change in OFF voltage/OFF current: Required Change in input resistance: Required Change in input response time: Not required 5) Change in functions: Required (12VDC not allowed)

5 REPLACING I/O MODULE

Input module

AJ35PTF-32D*1 AJ65SBTB1-32D

1) Change in external wiring: Required 2) Change in number of modules: Not required 3) Change in program

Change in number of occupied I/O points: Not required

4) Change in specifications

Change in rated input voltage: Required (12VDC not allowed)

Change in rated input current: Required Change in ON voltage/ON current: Required Change in OFF voltage/OFF current: Required Change in input resistance: Not required Change in input response time: Required

(10ms 1.5ms)

5) Change in functions: Required (12VDC not allowed, no optics)

AJ35TB1-16A AJ65SBTB2N-16A

1) Change in external wiring: Required 2) Change in number of modules: Not required 3) Change in program

Change in number of occupied I/O points: Required 4) Change in specifications

Change in rated input voltage: Not required Change in rated input current: Required Change in ON voltage/ON current: Not required Change in OFF voltage/OFF current: Required Change in input resistance: Required

5) Change in functions: Required (2-wire type for inputs)

AJ35TB2-8D AJ65SBTB3-8D

1) Change in external wiring: Required 2) Change in number of modules: Not required 3) Change in program

Change in number of occupied I/O points: Required 4) Change in specifications

Change in rated input voltage: Not required Change in rated input current: Not required Change in ON voltage/ON current: Not required Change in OFF voltage/OFF current: Not required Change in input resistance: Not required

Change in input response time: Required (10ms 1.5ms)

5) Change in functions: Required (2-wire type 3-wire type)

AJ35TB3-8D AJ65SBTB3-8D

1) Change in external wiring: Required 2) Change in number of modules: Not required 3) Change in program

Change in number of occupied I/O points: Required 4) Change in specifications

Change in rated input voltage: Not required Change in rated input current: Not required Change in ON voltage/ON current: Not required Change in OFF voltage/OFF current: Not required Change in input resistance: Not required MELSECNET/MINI-S3, A2C models to be

discontinued Alternative models for CC-Link

Product name Model name Model name Remarks (restrictions)

5 REPLACING I/O MODULE

Input module AJ35TB1-16D AJ65SBTB1-16D

1) Change in external wiring: Required 2) Change in number of modules: Not required 3) Change in program

Change in number of occupied I/O points: Required 4) Change in specifications

Change in rated input voltage: Not required Change in rated input current: Not required Change in ON voltage/ON current: Not required Change in OFF voltage/OFF current: Not required Change in input resistance: Not required Change in input response time: Required

(10ms 1.5ms)

5) Change in functions: Not required MELSECNET/MINI-S3, A2C models to be

discontinued Alternative models for CC-Link

Product name Model name Model name Remarks (restrictions)

5 REPLACING I/O MODULE

MELSECNET/MINI-S3, A2C models

to be discontinued Alternative models for CC-Link

Product name Model name Model name Remarks (restrictions)

Input module

AJ35TB1-16D AJ65BTB1-16D

1) Change in external wiring: Required 2) Change in number of modules: Not required 3) Change in program

Change in number of occupied I/O points: Required 4) Change in specifications

Change in rated input voltage: Not required Change in rated input current: Not required Change in ON voltage/ON current: Not required Change in OFF voltage/OFF current: Not required Change in input resistance: Not required Change in input response time: Not required 5) Change in functions: Not required

AJ35TB2-16D

AJ65SBTB3-16D

1) Change in external wiring: Required 2) Change in number of modules: Not required 3) Change in program

Change in number of occupied I/O points: Required 4) Change in specifications

Change in rated input voltage: Not required Change in rated input current: Not required Change in ON voltage/ON current: Not required Change in OFF voltage/OFF current: Not required Change in input resistance: Not required Change in input response time: Required

(10ms 1.5ms)

5) Change in functions: Required (2-wire type 3-wire type)

AJ65BTB2-16D

1) Change in external wiring: Required 2) Change in number of modules: Not required 3) Change in program

Change in number of occupied I/O points: Required 4) Change in specifications

Change in rated input voltage: Not required Change in rated input current: Not required Change in ON voltage/ON current: Not required Change in OFF voltage/OFF current: Not required Change in input resistance: Not required Change in input response time: Not required 5) Change in functions: Not required

AJ35TC1-32D AJ65SBTCF1-32D

1) Change in external wiring: Required 2) Change in number of modules: Not required 3) Change in program

Change in number of occupied I/O points: Not required

4) Change in specifications

Change in rated input voltage: Not required Change in rated input current: Not required Change in ON voltage/ON current: Required Change in OFF voltage/OFF current: Not required Change in input resistance: Not required Change in input response time: Required

(10ms 1.5ms)

5 REPLACING I/O MODULE

Output module

AY13C

AJ65SBTB2N-16R

1) Change in external wiring: Required

2) Change in number of modules (2 modules necessary) 3) Change in program

Change in number of occupied I/O points: Required 4) Change in specifications

Change in rated output voltage: Not required Change in rated output current: Not required 5) Change in functions: Required

(2-wire type for outputs)

AJ65DBTB1-32R

1) Change in external wiring: Required (Communication cable and power cable only)

2) Change in number of modules: Not required 3) Change in program

Change in number of occupied I/O points: Not required

4) Change in specifications

Change in rated output voltage: Not required Change in rated output current: Not required 5) Change in functions: Not required

AY15CEU

AJ65SBTB2N-16R

1) Change in external wiring: Required

2) Change in number of modules (2 modules necessary) 3) Change in program

Change in number of occupied I/O points: Required 4) Change in specifications

Change in rated output voltage: Not required Change in rated output current: Not required

(Note that a connect life is half.) 5) Change in functions: Required

(2-wire type for outputs)

AJ65DBTB1-32R

1) Change in external wiring: Required 2) Change in number of modules: Not required 3) Change in program

Change in number of occupied I/O points: : Not required

4) Change in specifications

Change in rated output voltage: Not required Change in rated output current: Not required 5) Change in functions: Not required

AY23C AJ65SBTB2N-16S

1) Change in external wiring: Required

2) Change in number of modules (2 modules necessary) 3) Change in program

Change in number of occupied I/O points: Required 4) Change in specifications

Change in rated output voltage: Not required Change in rated output current: Required 5) Change in functions: Required

(2-wire type for outputs)

1) Change in external wiring: Required 2) Change in number of modules: Not required 3) Change in program

Change in number of occupied I/O points: Not MELSECNET/MINI-S3, A2C models

to be discontinued Alternative models for CC-Link

Product name Model name Model name Remarks (restrictions)

5 REPLACING I/O MODULE

Output module

AY51C AJ65DBTB1-32T1

1) Change in external wiring: Required (Communication cable and power cable only)

2) Change in number of modules: Not required 3) Change in program

Change in number of occupied I/O points: Not required

4) Change in specifications

Change in rated output voltage: Not required Change in rated output current: Required 5) Change in functions: Not required

AY61CE

AJ65SBTB1-16TE

1) Change in external wiring: Required

2) Change in number of modules (2 modules necessary) 3) Change in program

Change in number of occupied I/O points: Required 4) Change in specifications

Change in rated output voltage: Required (5VDC not allowed)

Change in rated output current: Required (2A 0.1A) 5) Change in functions: Required (5VDC not allowed)

AJ65SBTB1-32TE1

1) Change in external wiring: Required 2) Change in number of modules: Not required 3) Change in program

Change in number of occupied I/O points: Not required

4) Change in specifications

Change in rated output voltage: Required (5VDC not allowed)

Change in rated output current: Required (2A 0.5A) 5) Change in functions: Required (5VDC not allowed)

AY81C

AJ65SBTB1-16TE

1) Change in external wiring: Required

2) Change in number of modules (2 modules necessary) 3) Change in program

Change in number of occupied I/O points: Required 4) Change in specifications

Change in rated output voltage: Required Change in rated output current: Required

(0.5A 0.1A)

5) Change in functions: Not required

AJ65SBTB1-32TE1

1) Change in external wiring: Required 2) Change in number of modules: Not required 3) Change in program

Change in number of occupied I/O points: Not required

4) Change in specifications

Change in rated output voltage: Not required Change in rated output current: Not required 5) Change in functions: Not required

1) Change in external wiring: Required

2) Change in number of modules (2 modules necessary) 3) Change in program

Change in number of occupied I/O points: Required MELSECNET/MINI-S3, A2C models

to be discontinued Alternative models for CC-Link

Product name Model name Model name Remarks (restrictions)

5 REPLACING I/O MODULE

MELSECNET/MINI-S3, A2C models

to be discontinued Alternative models for CC-Link

Product name Model name Model name Remarks (restrictions)

Output module

AJ35PTF-24T*1 AJ65SBTB1-32T1

1) Change in external wiring: Required 2) Change in number of modules: Not required 3) Change in program

Change in number of occupied I/O points: Required 4) Change in specifications

Change in rated output voltage: Not required Change in rated output current: Not required 5) Change in functions: Required (no optics)

AJ35TB1A-8R AJ65SBTB2N-8R

1) Change in external wiring: Required 2) Change in number of modules: Not required 3) Change in program

Change in number of occupied I/O points: Required 4) Change in specifications

Change in rated output voltage: Not required Change in rated output current: Not required 5) Change in functions: Required

(Change to 16 points per common (2-wire type))

AJ35TB2-8R AJ65SBTB2N-8R

1) Change in external wiring: Required 2) Change in number of modules: Not required 3) Change in program

Change in number of occupied I/O points: Required 4) Change in specifications

Change in rated output voltage: Not required Change in rated output current: Not required 5) Change in functions: Not required

AJ35TB1-16R AJ65SBTB2N-16R

1) Change in external wiring: Required 2) Change in number of modules: Not required 3) Change in program

Change in number of occupied I/O points: Required 4) Change in specifications

Change in rated output voltage: Not required Change in rated output current: Not required 5) Change in functions: Required

(2-wire type for outputs)

AJ35TB1A-8T AJ65SBTB1-8T1

1) Change in external wiring: Required 2) Change in number of modules: Not required 3) Change in program

Change in number of occupied I/O points: Required 4) Change in specifications

Change in rated output voltage: Required Change in rated output current: Required 5) Change in functions: Required

(Change to 16 points per common (2-wire type) )

AJ35TB2-8T AJ65SBTB2-8T1

1) Change in external wiring: Required 2) Change in number of modules: Not required 3) Change in program

Change in number of occupied I/O points: Required 4) Change in specifications

Change in rated input voltage: Required (5VDC not allowed)

Change in rated output current: Not required

5 REPLACING I/O MODULE

*1: Replacement using renewal tool for A0J2 is possible (refer to Appendix 2).

MELSECNET/MINI-S3, A2C models

to be discontinued Alternative model for CC-Link

Product name Model name Model name Remarks (restrictions)

Output module

AJ35TB1-16T

AJ65SBTB1-16T1

1) Change in external wiring: Required 2) Change in number of modules: Not required 3) Change in program

Change in number of occupied I/O points: Required 4) Change in specifications

Change in rated output voltage: Required Change in rated output current: Required 5) Change in functions: Not required

AJ65BTB1-16T

1) Change in external wiring: Required 2) Change in number of modules: Not required 3) Change in program

Change in number of occupied I/O points: Required 4) Change in specifications

Change in rated output voltage: Not required Change in rated output current: Not required 5) Change in functions: Not required

AJ35TB2-16T AJ65SBTB2-16T1

1) Change in external wiring: Required 2) Change in number of modules: Not required 3) Change in program

Change in number of occupied I/O points: Required 4) Change in specifications

Change in rated output voltage: Required Change in rated output current: Required 5) Change in functions: Not required

AJ35TC1-32T AJ65SBTCF1-32T

1) Change in external wiring: Required 2) Change in number of modules: Not required 3) Change in program

Change in number of occupied I/O points: Not required

4) Change in specifications

Change in rated output voltage: Required Change in rated output current: Not required 5) Change in functions: Not required

6) Others: External wiring connectors not attached

AJ35PTF-24R*1 AJ65SBTB2N-16R

1) Change in external wiring: Required

2) Change in number of modules: Required (2 modules necessary)

3) Change in program

Change in number of occupied I/O points: Required 4) Change in specifications

Change in rated output voltage: Not required Change in rated output current: Not required 5) Change in functions: Required (2-wire type for

outputs, no optics)

5 REPLACING I/O MODULE

MELSECNET/MINI-S3, A2C models

to be discontinued Alternative model for CC-Link

Product name Model name Model name Remarks (restrictions)

I/O module

AX10Y10C

AJ65SBTB2N-16A + AJ65SBTB2N-16R

1) Change in external wiring: Required

2) Change in number of modules (2 modules necessary) 3) Change in program

Change in number of occupied I/O points: Required 4) Change in specifications

Change in rated input voltage: Not required Change in rated input current: Required Change in ON voltage/ON current: Not required Change in OFF voltage/OFF current: Required Change in input resistance: Required Change in rated output voltage: Not required Change in rated output current: Not required 5) Change in functions: Required (2-wire type for I/Os)

AX10Y22C

AJ65SBTB2N-16A + AJ65SBTB2N-16S

1) Change in external wiring: Required

2) Change in number of modules (2 modules necessary) 3) Change in program

Change in number of occupied I/O points: Required 4) Change in specifications

Change in rated input voltage: Not required Change in rated input current: Required Change in ON voltage/ON current: Not required Change in OFF voltage/OFF current: Required Change in input resistance: Required Change in rated output voltage: Not required Change in rated output current: Required

5) Change in functions: Required (2-wire type for I/Os)

5 REPLACING I/O MODULE

MELSECNET/MINI-S3, A2C models

to be discontinued Alternative models for CC-Link

Product name Model name Model name Remarks (restrictions)

I/O module

AX40Y10C

AJ65SBTB1-16D + AJ65SBTB2N-16R

1) Change in external wiring: Required

2) Change in number of modules (2 modules necessary) 3) Change in program

Change in number of occupied I/O points: Required 4) Change in specifications

Change in rated input voltage: Required (12VDC not allowed)

Change in rated input current: Required Change in ON voltage/ON current: Required Change in OFF voltage/OFF current: Required Change in input resistance: Not required Change in input response time: Required

(10ms 1.5ms)

Change in rated output voltage: Not required Change in rated output current: Not required 5) Change in functions: Required

(2-wire type for outputs, 12VDC not allowed)

AJ65SBTB32-16DR

1) Change in external wiring: Required

2) Change in number of modules: Required (2 modules necessary)

3) Change in program

Change in number of occupied I/O points: Required 4) Change in specifications

Change in rated input voltage: Required (12VDC not allowed)

Change in rated input current: Required Change in ON voltage/ON current: Required Change in OFF voltage/OFF current: Required Change in input resistance: Not required Change in rated output voltage: Not required Change in rated output current: Not required 5) Change in functions: Required (12VDC not allowed)

AX40Y10C AJ65DBTB1-32DR

1) Change in external wiring: Required (Communication cable and power cable only)

2) Change in number of modules: Not required 3) Change in program

Change in number of occupied I/O points: Not required

4) Change in specifications

Change in rated input voltage: Required (12VDC not allowed)

Change in rated input current: Required Change in ON voltage/ON current: Required Change in OFF voltage/OFF current: Required Change in input resistance: Required Change in rated output voltage: Not required Change in rated output current: Not required 5) Change in functions: Required (12VDC not allowed)

5 REPLACING I/O MODULE

I/O module AX40Y50C

AJ65SBTB1-32DT2

1) Change in external wiring: Required 2) Change in number of modules: Not required 3) Change in program

Change in number of occupied I/O points: Not required

4) Change in specifications

Change in rated input voltage: Required (12VDC not allowed)

Change in rated input current: Required Change in ON voltage/ON current: Required Change in OFF voltage/OFF current: Required Change in input resistance: Not required Change in input response time: Required (10ms 1.5ms)

Change in rated output voltage: Required (12VDC not allowed)

Change in rated output current: Required

5) Change in functions: Required (12VDC not allowed)

AJ65DBTB1-32DT1

1) Change in external wiring: Required (Communication cable and power cable only)

2) Change in number of modules: Not required 3) Change in program

Change in number of occupied I/O points: Not

Change in number of occupied I/O points: Not