• 沒有找到結果。

Performance Specification for Power Supply Modules

4.3 Power Supply Connection

4.3.1 Performance Specification for Power Supply Modules

Table 4.1 Power Supply Module Specifications

Specifications Item

A61P A61PN A62P A63P A65P A66P A67P Base unit

loading position Power supply module loading slot

I/O module loading

slot

Power supply module loading slot

+10% +10% Input voltage

(170 to 264 VAC)

Input voltage distortion factor.

Within 5%

(Refer to Section 4.4) ⎯ Within 5%

(Refer to Section 4.4) ⎯ Max. input apparent

power 160 VA 155 VA 65 W 110 VA 95 VA 65 W

Inrush current 20 A, within 8 ms*4 100 A,

within 1 ms 20 A, within 8 ms*4 20 A, within 8 ms

5 VDC 8 A 5 A 8 A 2 A ⎯ 8 A

Rated output

current 24 VDC ⎯ 0.8 A ⎯ 1.5 A 1.2 A ⎯

5 VDC 8.8 A or higher 5.5 A or higher

8.5 A or higher

2.2 A or

higher ⎯ 8.5 A or

higher

*1

Overcurrent

protection 24 VDC ⎯ 1.2 A or

higher ⎯ 2.3 A or higher

1.7 A or

Overvoltage

protection 24 VDC

Efficiency 65 % or higher

Withstanding voltage 1500 VAC for 1 minute between all AC external terminals together and ground 500 VAC for 1 minute between all DC external terminals together and ground

Noise durability

Noise voltage 1500 Vp-p Noise width 1 s, Noise

frequency 25 to 60 Hz (noise simulator condition)

Noise voltage 500 Vp-p Noise width 1 s, Noise frequency 25 to 60 Hz (noise simulator

condition)

Noise voltage 1500 Vp-p Noise width 1 s, Noise frequency 25 to 60 Hz

(noise simulator condition)

Noise voltage 500 Vp-p Noise width 1 s, Noise frequency

25 to 60 Hz (noise simulator

condition) Insulation resistance 10 M or higher, measured with a 500 VDC insulation resistance tester

Table 4.1 Power Supply Module Specifications

Specifications Item

A61P A61PN A62P A63P A65P A66P A67P

Power indicator Power LED display

Terminal screw size M4 × 0.7 × 6 M3 × 0.5 × 6 M4 × 0.7 × 6

Applicable wire size 0.75 to 2 mm2

Applicable

solderless terminal R1.25-4, R2-4, RAV1.25-4, RAV2-4

R1.25-3, R2-3, RAV1.25-3,

RAV2-3

R1.25-4, R2-4, RAV1.25-4,

RAV2-4 Applicable

tightening torque: 78 to 118 N x cm 39 to 59 N x cm 78 to 118 N x cm External

dimensions

250 (H) × 55 (W)× 121 (D) (9.8× 2.1× 4.7) mm (inch)

250 (H) × 37.5 (W)

× 121 (D) (9.8× 1.5× 4.7)

mm (inch)

250 (H) × 55 (W)

× 121 (D) (9.8× 2.1× 4.7)

mm (inch) Weight 0.98 kg 0.75 kg 0.94 kg 0.8 kg 0.94 kg 0.75 kg 0.8 kg Allowable

momentary power interruption time *3

Less than 20ms

Less than 1ms

Less than 20ms

⎯⎯ Less than 20ms (at 100 VDC)

REMARK

The A66P module has the number of occupied slots shown below.1 slot

(2) Power supply module for CE marking

Table 4.2 Power Supply Module Specifications

Specifications Item

A61PEU A62PEU Base unit loading

position Power supply module loading slot

+10%

100 to 120 / 200 to 240 VAC -15%

Input voltage

(85 to 264 VAC)

Input frequency 50/60 Hz ±5 %

Input voltage distortion

factor. Within 5% (See Section 4.4)

Max. input apparent

power 130 VA 155 VA

Inrush current 20 A, within 8 ms

5 VDC 8 A 5 A

Rated output

current 24 VDC ⎯ 0.8 A

5 VDC 8.8 A or higher 5.5 A or higher

Overcurrent

protection *1 24 VDC ⎯ 1.2 A or higher

5 VDC 5.5 to 6.5 V ⎯

Overvoltage

protection *2 24 VDC ⎯

Efficiency 65 % or higher

Withstanding voltage 2830 VAC

Noise durability Noise voltage IEC801-4; 2kV, 1500 Vp-p

Noise width 1 s, Noise frequency 25 to 60 Hz (noise simulator condition) Insulation resistance 10 M or higher, measured with a 500 VDC insulation resistance tester

Power indicator Power LED display

Terminal screw size M4 × 0.7 × 6

Applicable wire size 0.75 to 2 mm2

Applicable

solderless terminal RAV1.25-4, RAV2-4

Applicable tightening

torque 78 to 118 N x cm

External dimensions 250 (H) × 55 (W)× 121 (D) (9.8× 2.1× 4.7) mm (inch)

Weight 0.8 kg 0.9 kg

Allowable momentary

power interruption time *3 Less than 20ms

POINTS

*1: Overcurrent protection

The overcurrent protection device shuts off the 5VDC and/or 24VDC circuit(s) and stops the system if the current exceeding the specified value flows in the circuit(s).

As this results in voltage drop, the power supply module LED turns OFF or is dimly lit.

After that, eliminate the causes of overcurrent, e.g., insufficient current capacity and short circuit, and then start the system.

When the current has reached the normal value, the initial start up of the system will be performed.

*2: Overvoltage protection

The overvoltage protection shuts off the 5VDC circuit and stops the system if the overvoltage of 5.5 to 6.5V is applied to the circuit.

This results in the power supply module LED turning OFF.

When restarting the system, power OFF and ON the input power supply, and the initial start up of the system will be performed.

If the system is not booted and the LED remains off, this means that the power supply module has to be replaced.

*3: Allowable momentary power failure period

The PLC CPU allowable momentary power failure period varies with the power supply module used.

In case of the A1S63P power supply module, the allowable momentary power failure period is defined as the time from when the primary side of the stabilized power supply for supplying 24VDC to the A1S63P is turned OFF until when the voltage (secondary side) has dropped from 24VDC to the specified value (15.6VDC) or less.

*4: Inrush current

If the power supply module is re-powered ON right after powered OFF (within 5seconds), the inrush current exceeding the specified value (2ms or less) may be generated. Therefore, make sure to re-power ON the module 5seconds after power off.

When selecting a fuse or breaker for external circuit, consider the

above point as well as meltdown and detection characteristics.

4.3.2 Part names and settings of Power Supply Module

The names and descriptions of each of the parts of the power supply modules are given below.

(1) Names and description of parts of the A61P, A61PN and A61PEU module

PN

Module fixing hook

Hook for fixing the module to the base unit.

"POWER" LED

LED for indicating 5 VDC power.

Power fuse, fuse holder

4 A cartridge fuse for AC input power is secured by the fuse holder.

Spare fuse for power supply

Spare fuse for power supply, mounted on rear side of the terminal cover.

Terminal block

For details, see below. (Located under the terminal cover) Terminal cover

Cover for protection of terminal block. Remove during wiring.

Re-install after wiring.

Module mounting screw mounting hole

Allows the module to be secured with a screw in addition to the module fixing hook. (For M4 screw)

Terminal details

Power input terminals

Power input terminals to which AC power of 100 VAC or 200 VAC.

Applied voltage select terminals

Terminals for selecting applied voltage. Use 100 VAC or 200 VAC as described below. When 100 VAC is input, connect together the "SHORT AC100V" terminals with the jumper provided. When 200 VAC is input, connect together the

"SHORT AC200V" terminals with the jumper provided.

LG terminal

Grounding of power filter. Has half the input potential.

FG terminal

Connection terminal connected to the shielding pattern on printed circuit board.

Terminal screw M4 × 0.7 × 6

(2) Names and description of parts of the A62P, A62PEU and A65P modules

Module fixing hook

Hook for fixing the module to the base unit.

"POWER" LED

LED for indicating 5 VDC power.

Power fuse, fuse holder

4 A cartridge fuse for AC input power is secured by the fuse holder.

Spare fuse for power supply

Spare fuse for power supply, mounted on rear side of the terminal cover.

Terminal block

For details, see below. (Located under the terminal cover) Terminal cover

Cover for protection of terminal block. Remove during wiring.

Re-install after wiring.

Module mounting screw mounting hole

Allows the module to be secured with a screw in addition to the module fixing hook. (For M4 screw)

Terminal details

Power input terminals

Power input terminals to which AC power of 100 VAC or 200 VAC.

Applied voltage select terminals

Terminals for selecting applied voltage. Use 100 VAC or 200 VAC as described below. When 100 VAC is input, connect together the "SHORT AC100V" terminals with the jumper provided. When 200 VAC is input, connect together the

"SHORT AC200V" terminals with the jumper provided.

LG terminal

Grounding of power filter. Has half the input potential.

FG terminal

Connection terminal connected to the shielding pattern on printed circuit board.

24 VDC, 24 GDC terminals

For supply to output module which requires 24 V inside the module. (Supplied to the module via external wiring) Terminal screw

M4 × 0.7 × 6

(3) Names and description of parts of the A63P and A67P modules

Module fixing hook

Hook for fixing the module to the base unit.

"POWER" LED

LED for indicating 5 VDC power.

Power fuse, fuse holder

Cartridge fuse for DC input power is fixed by the fuse holder.

The rating for the fuses are as follows.

A63P: 6.3 A (SM6.3 A or FGTA 250V 6A) A67P: 4 A (GTH4 or FGTA 250V 4A) Spare fuse for power supply

Spare fuse for power supply, mounted on rear side of the terminal cover.

Terminal block

For details, see below. (Located under the terminal cover) Terminal cover

Cover for protection of terminal block. Remove during wiring.

Re-install after wiring.

Module mounting screw mounting hole

Allows the module to be secured with a screw in addition to the module fixing hook. (For M4 screw)

Terminal details

Power input terminals

Power input terminals for A63P: 24 VDC, A67P: 100 VDC.

The power fuse will be blown if the 24 VDC connection is made with the wrong polarity.

LG terminal

Grounding of power filter.

FG terminal

Connection terminal connected to the shielding pattern on printed circuit board.

Terminal screw M4 × 0.7 × 6

(4) Names and description of parts of the A66P module

Module fixing hook

Hook for fixing the module to the base unit.

"POWER" LED

LED for indicating 5 VDC power.

Power fuse, fuse holder

4 A cartridge fuse for AC input power is secured by the fuse holder.

Terminal block mouniting screw

Screw for installing and fixing the terminal block to the module.

Terminal block

For details, see below. (Located under the terminal cover) Module mouniting screw mounting hole

Allows the module to be secured with a screw in addition to the module fixing hook. (For M4 screw)

Terminal details

Power input terminals

Power input terminals to which AC power of 100 VAC or 200 VAC.

Applied voltage select terminals

Terminals for selecting applied voltage. Use 100 VAC or 200 VAC as described below. When 100 VAC is input, connect together the "SHORT AC100V" terminals with the jumper provided. When 200 VAC is input, connect together the

"SHORT AC200V" terminals with the jumper provided.

LG terminal

Grounding of power filter. Has half the input potential.

FG terminal

Connection terminal connected to the shielding pattern on printed circuit board.

24 VDC, 24 GDC terminals

For supply to output module which requires 24 V inside the module. (Supplied to the module via external wiring) Power ON terminal

Contact terminal which conducts if the 24 VDC output is normal when power input turns on.

Terminal screw M3 × 0.5 × 6

(5) Setting

For A61P, A61PN, A61PEU, A62P, A62PEU, A65P or A66P, the input voltage range, 100V or 200V, must be specified by placing a jumper (supplied) across two terminals as described below:

(1)

(2) (3) (4) Remove the terminal cover from

the power supply module.

Remove the pair of terminal screw, (2) or (3), according to the supply voltage range (1) used.

(2): For the 100 VAC range.

(3): For the 200 VAC range.

Fit the jumper (4) and secure it with the terminal screw.

Fit the jumper in the direction shown in the figure at right.

(The figure at right shows an example when the supply line voltage is 100 VAC.)

POINT

If the setting differs from the supply line voltage, the following occurs: do not mis-set.

Supply Line Voltage

100VAC 200VAC Setting to 100VAC

(jumper fitted as indicated at (2)) ⎯

The power supply module is damaged. (The CPU module is not damaged.)

Setting to 200VAC

(jumper fitted as indicated at (3))

No error occurs in the module. However, the CPU module does not operate.

No setting (jumper not fitted) No error occurs in the module.

However, the CPU module does not operate.

4.3.3 Wiring instructions

Instructions for wiring the power supply cable and I/O cable.

DANGER z Be sure to shut off all phases of the external power supply used by the system before wiring.

Failure to do so may result in an electric shock or damage of the product.

z Before energizing and operating the system after wiring, be sure to attach the terminal cover supplied with the product.

Failure to do so may cause an electric shock.

CAUTION z Always ground the FG and LG terminals to the protective ground conductor.

Failure to do so may cause an electric shock or malfunctions.

z Wire the module correctly after confirming the rated voltage and terminal layout.

Connecting a power supply of a different voltage rating or incorrect wiring may cause a fire or failure.

z Do not connect multiple power supply modules to one module in parallel. The power supply modules may be heated, resulting in a fire or failure.

z Press, crimp or properly solder the connector for external connection with the specified tool.

Incomplete connection may cause a short circuit, fire or malfunctions.

z Tighten terminal screws within the specified torque range. If the screw is too loose, it may cause a short circuit, fire or malfunctions.

If too tight, it may damage the screw and/or the module, resulting in a short circuit or malfunctions.

z Carefully prevent foreign matter such as dust or wire chips from entering the module.

Failure to do so may cause a fire, failure or malfunctions.

z Install our PLC in a control panel for use.

Wire the main power supply to the power supply module installed in a control panel through a distribution terminal block.

Furthermore, the wiring and replacement of a power supply module have to be performed by a maintenance worker who acquainted with shock protection.

(For the wiring methods, refer to Type A1N/A2N(S1)/A3NCPU User’s Manual.)

(1) Power Supply Connection

(a) When voltage fluctuations are larger than the specified value, connect a constant-voltage transformer.

Constant voltage transformer

PLC

(b) Use a power supply which generates minimal noise between wires and between the PLC and ground. If excessive noise is generated, connect an insulating transformer.

PLC Insulating

transformer

I/O equipment Insulating

transformer

(c) When a power transformer or insulating transformer is employed to reduce the voltage from 200 VAC to 100 VAC, use one with a capacity greater than those indicated in the following table.

Power Supply Module Transformer Capacity

A61P, A61P 160VA n

A62P 155VA n

A65P 110VA n

A66P 95VA n

n: Stands for the number of power supply modules.

(d) Provide separate wiring systems for the PLC power, I/O devices, and operating devices as shown below.

If the wiring is influenced by excessive noise, connect an isolation transformer.

(e) Taking rated current or inrush current into consideration when wiring the power supply, be sure to connect a breaker or an external fuse that have proper blown and detection.

When using a single PLC, a 10A breaker or an external fuse are recommended for wiring protection.

200VAC

T1 Main

power supply Relay terminal block

PLCpower supply

Insulation Transformer

I/O power supply

I/O equipment

On a control panel

Main circuit power supply

Main circuit equipment PLC

(f) Note on using the 24 VDC output of the A62P, A65P and A66P power supply module.

CAUTION z Do not connect multiple power supply modules to one

module in parallel. The power supply modules may be

heated, resulting in a fire or failure.

If the 24 VDC output capacity is insufficient for one power supply module, supply 24 VDC from the external 24 VDC power supply as shown below:

I/O module

24VDC

24VDC 24VDC

External power supply

Power supply modulePower supply module Power supply module I/O module

(g) 100VAC, 200VAC, and 24VDC wires should be twisted as tightly as possible, and connect the modules at the shortest distance between them.

To minimize voltage drop, use thick wires (MAX. 2mm

2

) where possible.

(h) Do not bind 100VAC and 24VDC wires together with main circuit (high tension and large current) wires or I/O signal lines (including common line) nor place them near each other. Provide 100mm (3.94 inch) clearance between the wires if possible.

(i) As a measure against surges caused by lightning, insert a lightning surge absorber as shown below.

E1 E1 AC

E1

E2

Surge absorber for lightning PLC

I/O devices

POINT

(1) Provide separate grounding for the lightning surge absorber (E1) and the PLC (E2).

(2) Select a lightning surge absorber whose maximum allowable circuit voltage is higher than the circuit voltage at the maximum power supply voltage.

(2) Wiring to I/O device

(a) The solderless terminal with insulation sleeve is inapplicable to a terminal block.

It is advisable to cover the wire connection part of a terminal with a

mark tube or insulation tube.

(b) Install wiring to a terminal block using the cable of core diameter 0.3 to 0.75mm

2

, and outside diameter 2.8mm or less.

(c) Run the I/O line and output line away from each other.

(d) When the main circuit line and power line cannot be separated, use a shielding cable and ground it on the PLC side.

However, ground it on the opposite side in some cases.

PLC Input Output

DC

Shielded cable

Shield jacket RA

(e) When cables are run through pipes, securely ground the pipes.

(f) Run the 24VDC input line away from the 100VAC and 200 VAC lines.

(g) The cabling of 200m (656.2ft.) or longer distance may produce

leakage current depending on the capacity between lines and result in an accident.

(h) As a countermeasure against the power surge due to lightning,

separate the AC wiring and DC wiring and connect a surge absorber for lightning as shown in (i) of item (1).

Failure to do so increases the risk of I/O device failure due to lightning.

(3) Grounding

CAUTION z Be sure to ground the FG terminals and LG terminals to the protective ground conductor. Not doing so could result in electric shock or erroneous operation.

(a) Carry out the independent grounding if possible. (Grounding resistance 100 or less.)

(b) If the independent grounding is impossible, carry out the shared grounding (2) as shown below.

PLC Other

device Class 3 grounding

(1) Independent grounding...Best (2) Shared grounding...Good (3) Common grounding...Not allowed

PLC Other

device

PLC Other

device Class 3 grounding

(c) Use the cable of 2mm

2

or more for grounding.

Set the grounding point closer to the PLC to make the grounding cable short as possible.

(d) If a malfunction occurs due to earthling, separate either LG or FG of

4.3.4 Wiring to module terminals

The following is an example of wiring of power supply and grounding wires to main base unit and extension base units.

AC

Main base unit (A38B)

A62P CPU

Extension base unit (A58B) I/O I/O

24 VDC OUTPUT 24 GDC FG LG

SHORT 200 VAC SHORT 100 VAC 100/200 VAC

SHORT 100 VAC 100/200 VAC

SHORT 200 VAC LG FG

Extension base (A68B)

A61P I/O

FG 100/110 VAC

Fuse ACDC

24 VDC

24 VDC

Connect to the 24 VDC terminals of an I/O module that requires 24 VDC internally.

5 VDC line

100/110 VAC

Ground Grounding line

5 VDC line

POINT (1) Use the thickest possible (max. 2 mm

2

(14 AWG)) wires for the 100/200

VAC and 24 VDC power cables. Be sure to twist these wires starting at the connection terminals. For wiring a terminal block, be sure to use a solderless terminal. To prevent short-circuit due to loosening screws, use the solderless terminals with insulation sleeves of 0.8 mm (0.03 inch) or less thick. The number of the solderless terminals to be connected for one terminal block are limited to 2.

Terminal block Solderless terminals

with insulation sleeves

(2) When the LG and FG terminals are connected, they must be grounded.

If they are not grounded, the operations will be easily influenced by

noise. Be aware not to touch the LG terminal since it has potential of half the input voltage.

4.4 Precaution when Connecting the Uninterruptive Power Supply (UPS) Be sure of the following terms when connecting the PLC system to the

uninterruptive power supply (abbreviated as UPS hereafter):

As for UPS, use the online power system or online interactive system with a voltage distortion rate of 5% or less.

For the UPS of the commercial online power system, use Mitsubishi Electric's F Series UPS (serial number P or later) (Ex.: FW-F10-0.3K/0.5K).

Do not use any UPS of the commercial online power system other than the F

series mentioned above.

4.5 Part names and settings

This section gives the names of each part of the CPU module.

4.5.1 Part names of AnNCPU, AnACPU, and AnUCPU

(5) (1)

(2)

(3)

(4)

(5) (6) (7) (8) (9) (10)

(11)

(A)

(B)

(C) (D) (E) (F)

(5) (8)

(6) (7)

(9)

(12)

(11)

(13) (8)

(14) (7)

(9)

(12)

(11)

A1NCPU Detail of A1NCPU terminals

A2NCPU(S1) A2ACPU(S1) A2UCPU(S1)

A3NCPU A3ACPU A3U, A4UCPU

(1) "POWER" LED

The "POWER" LED lights when the AC power is switched on and the 5/24 VDC output is normal.

(2) Fuse holder

Holder for the fuse that protects the AC side (3) Spare fuse box

A spare fuse for the power supply is stored on the rear face of the cover (4) Power terminal block

(A) Power input terminal

The power input terminal used to connect the 100VAC or 200VAC power supply.

(B) Operating voltage switching terminal

It is possible to use either a 100VAC or 200VAC power supply.

When 100VAC is used, short-circuit the "SHORT 100VAC"

terminals with the shorting strip supplied. When 200VAC is used, short-circuit the "SHORT 200VAC" terminals.

(C) LG terminal

Used to ground power filter.

Has potential half the input voltage.

(D) FG terminal

The grounding terminal connected to the shielding pattern on the printed wiring board.

(E) 24VDC, 24GDC terminals

Used to supply 24V to output modules that require an internal 24V source (supplied to modules through external wiring).

(F) Terminal screws

M4 x 0.7 x 6

POINT

Discrepancies between the voltage setting and the actual power supply voltage will have the following consequences:

Power Supply Voltage

100VAC 200VAC Set to 100VAC (shorting

strip connected at (2)) ⎯

The power supply module is destroyed (no abnormality in the CPU)

Set to 200VAC (shorting strip connected at (3))

There is no abnormality in the module. However, the CPU does not operate.

No setting (shorting strip not used)

There is no abnormality in the module. However, the CPU does not operate.

(5) "RUN" LED

The "RUN" LED indicates the operating condition of the CPU.

ON : When the key switch is turned to RUN or STEP RUN and the sequence program is being executed.

OFF : When the key switch is turned to STOP, PAUSE or STEP RUN and the sequence program is not being executed.

Flashing : When an error has been detected by the self-diagnosis function (operation will continue if the error detected has been specified in the parameter settings). When the key switch is set to the LATCH CLEAR position, the LED flashes rapidly for about two seconds.

(6) "ERROR" LED

ON : Indicates that a WDT or internal fault check error has occurred due to a hardware fault.

OFF : Indicates that the annunciator (F) has been switched ON by the sequence program.

(7) RUN/STOP key switch

RUN/STOP : Used to start/stop sequence program execution.

PAUSE : Sequence program operation stops with the output statuses immediately before the PAUSE condition was established

retained.

STEP RUN : The sequence program is run step by step or scan by scan.

(8) RESET key switch

RESET : Hardware reset. Used to reset the CPU after an operation error and to initialize operation.

LATCH : Sets all data in the latch area defined in the parameter CLEAR settings to "OFF" or "0" (valid only when the RUN/STOP key

switch is turned to STOP).

(1) Turn the RUN/STOP switch from STOP to L.CLR several times.

(2) Clear by means of a program.

(9) I/O control switch (AnNCPU only)

This switch is used to set the Direct/Refresh mode.

Switch Setting Input (X) Output (Y) D9014

OFF ON

(Factory setting)

Direct mode Direct mode 0

OFF ON

Refresh mode Direct mode 1

OFF ON

Refresh mode Refresh mode 3

POINTS (1) Perform switch setting while the power is switched OFF.

(2) After the switches have been set, the CPU checks the status of the switches at power on or at reset. Note that if the direct mode is set for input and the refresh mode for output, the CPU will execute processing in the refresh mode for both input and output.

(3) Since a binary code corresponding to the I/O control mode is stored in special register D9014, the mode can be monitored using a peripheral device.

Latch Clearing Method

(10) Memory card area

This is the section where the memory card is installed and the memory protect setting is made. It is provided with a cover.

(11) RS-422 connector

The connector for peripheral device connection.

Fitted with a cover when not in use.

(12) Memory cassette loading connector

Used to connect the memory cassette to the CPU.

(13) LED Display

Capable of displaying up to 16 alphanumeric characters. Displays self diagnosis error comments, and the F number comments of annunciators in accordance with OUT F and SET F

(14) LED display reset switch

Used to clear the LED display and display the next display data if there is

any.

4.5.2 Part identification of AnNCPUP21/R21, AnACPUP21/R21

This section gives the names of those parts of the AnNCPUP21/R21 and AnACPUP21/R21 that relate to the data link function. For the names of other parts, such as the RUN/STOP key switch, refer to Section 4.5.1.

(18) (19)

(18) (19)

(16)

(16) (15)

(17)

(15) (17)

A1NCPUP21(-S3) A1NCPUR21

A2NCPU(S1)P21(-S4) A3NCPUP21(-S3) A2ACPU(S1)P21(-S4) A3ACPUP21(-S3)

A2NCPU(S1)R21 A3NCPUR21 A2ACPU(S1)R21 A3ACPUR21

(15) LEDs for indicating operation status and errors

LED Name Description LED

Name Description

RUN Comes ON when the data link

is normal. S0

SD Remains ON while data is

sent. S1

RD Remains ON while data is

received. S2

Not used (always OFF) S3 CRC Comes ON when a code

check error occurs. S4 OVER Comes ON when a data entry S5

delay error occurs. S6 AB. IF Comes ON when data is all

"1". S7

Not used

(These LEDs flash during execution of data link. This is not an abnormal condition)

TIME Comes ON when a time-out occurs.

DATA Comes ON when a receive data error occurs.

F.LOOP

Comes ON when the forward loop serves as the data receiving line, or goes OFF when the reverse loop is used for it.

UNDER Comes ON when a send data

error occurs. CPU R/W Comes ON during communications with the PC CPU.

F. LOOP Comes ON when a forward

loop receive data error occurs. Not used (always OFF) Not used (always OFF) R..

LOOP

Comes ON when a reverse

loop receive data error occurs. 10

1 20 2 40

Indicate the figures at the ten's digit of the station numbers in BCD codes.

4 Not used (always OFF)

8

Indicate the figures at the one's digit of the station numbers in BCD.

(16) Station number setting switches

z Station numbers from 00 to 64 can be set.

z The "X10" switch is to set the ten's digit of a station number.

z The "X1" switch is to set the one's digit of a station number.

z To use a station as the master station, set "00".

z To use a station as a local station, set between "01" and "64".

(17) Mode select switch

By switching mode, the following functions are available:

Setting

Number Name Description

0 Online Automatic return is set during normal operation.

1 Online Automatic return is not set during normal operation.

2 Online The host station is disconnected.

3 Forward loop test mode

Used to perform a line check on the optical fiber cables or coaxial cables in the forward loop (for normal data link) throughout the entire data link system.

4 Reverse loop test mode

Used to perform a line check on the optical fiber cables or coaxial cables in the reverse loop (for loopback when an error occurs) throughout the entire data link system.

5

Station-to-sta tion test mode (master station) 6

Station-to-sta tion test mode (slave station)

Used to check the line between two stations.

The line is checked with the station with the smaller station number set as the master station and the other station set as a slave station.

7 Self-loopback test mode

Used to check the hardware, including the send/receive circuits of the communications system, of one data link module in isolation.

8 to F ⎯ Unusable

(18) Connectors for connecting opeical fiber cables Connect the cables as illustrated below:

OUT Forward loop send Reverse loop receive

IN Reverse loop send Forward loop receive

OUT IN ← Front OUT IN ← Front OUT IN ← Front

Master station Equipment No. 1 Equipment No. 2

Front IN OUT

IN : To be connected to the OUT connector of the previous station.

OUT : To be connected to the IN connector of the next station.

(19) Connectors for connecting coaxial cables Connect the cables as illustrated below:

Front

OUT R-RD IN

F-RD OUT F-SD

IN

R-SD OUT

R-RD IN F-RD OUT F-SD

IN

R-SD OUT

R-RD IN F-RD OUT F-SD

IN R-SD OUT R-RD

Receive loop reverse

IN R-SD Reverse loop send OUT F-SD

Forward loop send

IN F-RD Forward loop receive

R-SD F-RD F-SD R-RD IN

OUT

Master station Equipment No. 1 Equipment No. 2

IN R-SD : To be connected to the OUT R-RD connector of the previous station.

IN F-RD : To be connected to the OUT F-SD connector of the previous station.

OUT F-SD : To be connected to the IN F-RD connector of the next station.

OUT R-RD : To be connected to the IN R-SD connector of the next station.

Front Front Front

5. I/O MODULE SPECIFICATIONS AND CONNECTIONS

This section presents the specifications and wiring drawings for each of the A series I/O modules.

5.1 Input Modules

5.1.1 Input module specifications

Operating Voltage Model Input Type

Numbe r of Points/

Module

Rated Input Voltage

Input

Current ON Voltage

OFF Voltage

Maximum Simultaneous ON

Input Point (Percentage Simultaneous ON)

AX10 16

points 100%

AX11

10mA 80VAC or higher

AX11EU

32 points

100V to 120VAC

12mA 79VAC or higher

40VAC

AX21EU

AC input

32 points

200V to 240VAC

12mA

160VAC or higher

70VAC

or lower 60%

AX40 16

points 100%

AX41 AX41-S1

32 points

4/10mA

60%

AX42 *1

DC input (sink type)

AX42-S1

*1 DC input

64 points

12/24 VDC

3/7mA

9.5VDC or higher

6VDC or lower

60% *3

AX50 DC input (sink type) AX50-S1 DC input (sink/source

48VDC 4mA 34VDC

or higher

10VDC or lower

AX60 DC input (sink type) AX60-S1 DC input

(sink/source type)

100/110/

125VDC 2mA 80VDC or higher

20VDC or higher

1.1VDC

AX70 Sensor input

(sink/source type)

16 points

24VDC 4.5mA (TYP)

5VDC

or higher 2VDC or lower

100%

Input Response Time

OFF to ON ON to OFF

External Connections

Common Terminal Arrangement

Internal Current Consumption

Number of Occupied I/O Points 20 terminal block

connector 16 points/

common 0.055A 16 points

0.11A 38 terminal block

connector

32 points/

common

0.15A

32 points

20 terminal block

connector 16 points/

common 0.055A 16 points

0.11A 15ms or less 25ms or less

38 terminal block

connector 32 points/

common

0.15A

32 points

20 terminal block

connector 0.055A 16 points

10ms or less 10ms or less 8 points/

common

0.1ms or less 0.2ms or less

38 terminal block

connector 32 points/

common

0.11A 32 points

10ms or less 10ms or less 64 point

0.5ms or less 0.5ms or less

40-pin connector

× 2 32 points/

common 0.12A

32 points

10ms or less 10ms or less

10ms or less 20ms or less

1.5ms or less 3ms or less

20 terminal block

connector 8 points/

common 0.055A 16 points

(To next page)

(From front page)

Operating Voltage Model Input Type

Number of Points/

Module

Rated Input Voltage

Input

Current ON Voltage

OFF Voltage

Maximum Simultaneous ON

Input Point (Percentage Simultaneous ON) 5VDC

or higher 1.1VDC or lower 12VDC

(SW OFF)

2mA (TYP) 3mA (MAX) AX71 Sensor input

(sink/source type) 32 points

24VDC

or higher 2VDC or lower

AX80

or higher 6VDC or lower

AX81-S1 DC input

12/24 VDC

2.5/5mA 5.6VDC

or higher 2.4VDC or lower AX81-S2 DC input (source type) 48/60

VDC 3/4mA 31VDC

or higher 10VDC or lower AX81-S3 DC input

32 points

12/24

VDC 4/10mA 9.5VDC

or higher 6VDC or lower At normal input 21VDC

or higher 6VDC or lower When disconnection detected

AX81B DC input

(sink/source type) 32

points 24VDC 7mA

1VDC

or higher 6VDC or lower AX82 *1 DC Input

(source type) 64

points 12/24

VDC 3/7mA 9.5VDC

or higher 6VDC or lower

60% higher

2.5VAC /VDC or

lower 100%

Input Response Time

OFF to ON ON to OFF

External Connections

Common Terminal Arrangement

Internal Current Consumption

Number of Occupied I/O Points

1.5ms or less 3ms or less 38 terminal block

connector 0.11A 32 points

10ms or less 10ms or less 20 terminal block connector [TYP]

5.5ms 6.0ms [High-speed mode]

0.5ms or less 1.0ms or less

0.055A 16 points

0.11A 10ms or less 10ms or less

0.105A 20ms or less 20ms or less

0.1ms or less 0.2ms or less

38 terminal block connector

8points/

common

0.11A

32 points

10ms or less 10ms or less 38 terminal block connector 8 points/

common 0.125A 64 points

10ms or less 10ms or less 37-pin D subconnector × 2 0.12A 64 points 25ms or less

20ms or less

20ms or less 38 terminal block connector

32 points/

common

0.11A 32 points

The following specifications apply to all modules:

Isolation method : Photocoupler Input indication : LEDs

*1 : The ON/OFF status of the first or latter half is indicated by the LEDs in accordance with the setting of the selector switch on the front panel of the module:

FH setting: First half (X00 to X1F), LH setting: Latter half (X20 to X3F)

*2 : It is possible to select high speed or low speed for the upper eight points only using the DIP switch:

HIGH setting: high-speed, LOW setting: low-speed

*3: The number of simultaneous input points is 40% (13 inputs/common)

simultaneously ON when the unit is used adjacent to the power supply module.

5.1.2 Input module connections

Model Rated Input Voltage Model Rated Input Voltage

AX10 100-120 VAC AX11

(1)

AX20 200-240 VAC AX11EU 100-120 VAC

AX21

(2)

AX21EU 200-240 VAC

1 connected internally.

Model Rated Input Voltage Model Rated Input Voltage

AX40 12/24 VDC AX41

12/24 VDC

+

12/24 VDC

+

12/24 VDC

12/24 VDC

+ − + −

Model Rated Input Voltage AX42

(5)

AX42-S1 12/24 VDC

X00 X10

X01 X11

X02 X12

X03 X13

X04 X14

X05 X15

X06 X16

X07 X17

X08 X18

X09 X19

X0A X1A

X0B X1B

X0C X1C

X0D X1D

X0E X1E

X0F X1F

Vacant Vacant COM COM

B20 B19 B18 B17 B16 B15 B14 B13 B12 B11 B10 B9 B8 B7 B6 B5 B4 B3 B2 B1

A11 A20 A19 A18 A17 A16 A15 A14 A13 A12

A10 A9 A8 A7 A6 A5 A4 A3 A2 A1

Vacant Vacant

Vacant +

− Vacant

* The figure above indicates F (the first half 32 points).

The connections for L (the latter half 32 points) are the same as for F (regard X00 to X1F as X20 to X3F).

B1 and B2 are connected internally.

Model Rated Input Voltage Model Rated Input Voltage

(6) AX50-S1 48 VDC (8)

AX60-S1 100/110/125 VAC 1

Model Rated Input Voltage Model Rated Input Voltage

(7) AX60 100/110/125 VDC (9)

12/24 VDC

• Sensor (source)

+

• Open collector (sink)

• TTL • 5 VDC

LS-TTL

C-MOS buffer (sink)

open collector (sink)

• Can be used in any combination in units of 8 points per common.

When using the COMS source type, only CMOSs with a 5 VDC rating as shown

Model Rated Input Voltage Model Rated Input Voltage COM4Vacant 12/24 VDC

5 VDC 12/24 VDC

5 VDC

• Sensor (source)

+−

• Open collector (sink)

• TTL, LS-TTL C-MOS buffer (sink)

+−

+− +−

• Open collector (sink)

• Can be used in any combination in units of 8 points per common.

When using the COMS source type, only CMOSs with a 5 VDC rating as shown above can be used (e.g. HCMOS).

1 12/24 VDC 0V

12/24 VDC + −

+ −

Model Rated Input Voltage Model Rated Input Voltage

AX81 (13)

DC5 LED

24 VDC

Model Rated Input Voltage (14)

AX82 12/24 VDC

X01 1 X03 X05 X07 X09 X0B X0D X0F X11 X13 X15 X17 X19 X1B X1D

X02 X04 X06 X08 X0A X0C X0E X10 X12 X14 X16 X18 X1A X1C X1E

Vacant 20

21 2 22 3 23 4 24 5 25 6 26 7 27 8 28 9 29 10 30 11 31 12 32 13 33 14 34 15 35 16 36 17 37 18

19 X1F

COM COM

COM Vacant

X00

+

− + −

* The figure above indicates F (the first half 35 points).

The connections for L (the latter half 32 points) are the same as for F (regard X00 to X1F as X20 to X3F).

17 , 18 , and 36 are connected internally.

Model Rated Input Voltage (15)

AX31 12/24 VAC 12/24 VDC

X03 2 X05 X07 X08 X0A X0C X0E COM X11 X13 X15 X17 X18 X1A X1C X1E

Vacant 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 COM

1 X02 X04 X06 COM X09 X0B X0F X10 X12 X14 X16 COM X19 X1B X1D

Vacant 3

5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37

X0D

X1F

X01 X00

+

− + −

* 9 and 18 , and 27 and 36 are connected internally.

5.2 Output Modules

5.2.1 Output module specifications

Max. Load Current Output Response Time Model Output Type

No. of Points/

Module

Rated Load Voltage

Per Point Per

Contact output (All points independent)

16A/all points

AY11 Contact output 8A

AY11A

240VAC 24VDC

AY11AEU

Contact output (All points independent)

24VDC 24VAC

16A/all points

AY11E 240VAC

24VAC AY11EEU

16 points

AY13EEU 24VDC

24VAC AY13E

32 points

240VAC 24VAC

5A

AY15EU

Contact output

24 points 24VDC 240VAC

2A

Triac output

32 points

AY40 Transistor output

(sink type) 0.1A 0.8A

AY40A

Transistor output (all points

independent sink type) (resistive load)

External Power Supply (TYP 24VDC) External

Connections

Common Terminal Arrangement

Surge Suppression

Fuse Rating

Error Display

Current

Internal Current Consumption

Number of Occupied I/O Points

20 terminal block connector

8 points/

common 38 terminal

block connector

No common (all points independent)

None

20 terminal block connector

8 points/

common 38 terminal

block connector

No common (all points independent)

None

20 terminal block connector

Varistor

8A

common

None

None

None

0.22A 0.15A

32 points 38 terminal

block connector

4 points/

common CR absorber 3.2A 0.40A

20 terminal block connector

CR absorber

varistor 7A *6

Display

*10 0.305A

16 points

38 terminal block connector

Absorber 3.2A *6

0.59A 32 points

20 terminal block connector

8 points/

common

Clamp diode 0.008A 0.115A

38 terminal block connector

No common (all points independent)

Surge absorbing diode

⎯ 0.19A

20 terminal block connector

8 points/

common Cramp diode

None

None

0.015A 0.115A

16 points

(To next page)

(From front page)

Max. Load Current Output Response Time Model Output Type

No. of Points/

Module

Rated Load Voltage

Per Point Per AY41 1.6A

AY41P 32 points (resistive load)

AY42-S1

12/24VDC

0.1ms or less

0.3ms or less (resistive load)

AY42-S3

*1 0.1A *5 2A

AY42-S4

*1 AY51-S1

32 points

12/24VDC

0.3A 2A AY60

Transistor output (sink type)

2A 5A

AY60E

24VDC (12/48V) *2

12/24 (resistive load)

12VDC

2A 9.6A

AY60EP

Transistor output (source type)

12/24VDC

24VDC

AY60S Transistor output (sink type)

16 points

24/48VDC

(12V) *3 2A 6.4A 1ms or

less

3ms or less (resistive load)

AY70 16 points 0.016A 0.128A

AY71

Transistor output (for TTL. COMOS) (sink type)

32 points

5/12VDC

0.016A 0.256A

1ms or less

1ms or less

External Power Supply (TYP 24VDC) External

Connections

Common Terminal Arrangement

Surge Suppression

Fuse Rating

Error Display

Current

Internal Current Consumption

Number of Occupied I/O Points

0.02A 38 terminal

block connector

16 points/ Cramp diode

1.6A *7 Display

*11

0.04A

0.29A 40-pin

connector × 2

32 points/

common

Photo coupler Built-in Zener diode

None None ⎯ 0.5A

64 points

20 terminal block connector

8 points/

common 2A *6 Display

*10 0.065A 0.115A 16 points Varistor

None None 0.05A 0.023A 38 terminal

block connector

16 points/

common Transistor Built-in Zener diode

1A *8 Display

*10 0.1A 0.31A

32 points

Varistor 3.2A *9 0.065A

5A *9 Display

0.065A Surge

absorbing diode

None 0.11A 0.115A

Varistor 5A *9 0.003A 0.075A

16 points 20 terminal

block connector

8 points/

common

*12

0.055A 0.1A 16 points

38 terminal block connector

16 points/

common

None None

None

*12

0.1A 0.2A 32 points

(To next page)

(From front page)

Max. Load Current Output Response Time Model Output Type

No. of Points/

Module

Rated Load Voltage

Per Point Per Common

OFF to ON

ON to OFF AY72 *1

Transistor output (for TTL. COMOS) (sink type)

64 points 5/12VDC 0.016A 0.512A 1ms or less

1ms or less

AY80 0.5A 2A 2mc of

less

2ms of less (resistive load) AY80EP

16 points

0.8A 3.84A 0.5ms or less

1.5ms or less

AY81 0.5A 4A 2ms of

less

2ms of less (resistive load) 12VDC

0.8A 7.68A AY81EP

32 points

24VDC

0.4A 3.84A 12VDC

0.1A 1.92A

*1 AY82EP

Transistor output (source type)

64 points

12/24VDC

24VDC

0.04A 0.758A

0.5ms or less

1.5ms or less

External Power Supply (TYP 24VDC) External

Connections

Common Terminal Arrangement

Surge Suppression

Fuse Rating

Error Display

Current

Internal Current Consumption

Number of Occupied I/O Points

40-pin connector

× 2

32 points/

common None None None *12

0.3A 0.3A 64 points

Varistor 2A *6 Display

*10 0.06A 20 terminal

block connector

8 points/

common

Surge absorbing diode

0.11A

0.115A 16 points

Varistor 0.05A 38 terminal

block connector

16 points/

common

0.22A

0.23A 32 points

40-pin connector

× 2

32 points/

common

Surge absorbing diode

None None

0.05A 0.29A 64 points

The following specifications apply to all modules:

Isolation method : Photocoupler Input indication : LEDs

*1 : The ON/OFF status of the first or latter half is indicated by the LEDs in accordance with the setting of the selector switch on the front panel of the module:

FH setting: First half (Y00 to Y1F), LH setting: Latter half (Y20 to Y3F)

*2 : When 12/48 VDC is used as the load power supply, a separate 24 VDC power supply must be used as an external power supply.

*3 : When 12 VDC is used as the load power supply, a separate 24/48 VDC power supply must be used as an external power supply.

*4 : When the module is installed adjacent to the power supply module, the value indicated in parentheses applies.

*5 : The maximum load current differs depending on the number of simultaneously ON points.

*6 : Fast-melting fuse (one per common)

*7 : Normal fuse (two per common)

*8 : Fast-melting fuse (two per 8-per-common unit)

*9 : Fast-melting fuse (two per common)

*10 : LED comes on when a fuse blows or the external power supply is turned off.

*11 : Since this is a built-in fuse directly fixed to the module, replace the entire module if it blows.

*12 : TYP. 12 VDC

5.2.2 Output module connections

Model Rated Input Voltage Model Rated Input Voltage

AY10 AY10A

AY11 AY11A

AY11E

(2)

AY11AEU

24 VDC/240 VAC (1)

AY11EEU

24 VDC/240 VAC

100/200 VAC

100/200 VAC 24 VDC

Y00 Y00

Vacant Vacant

0V + −

Model Rated Input Voltage Model Rated Input Voltage

AY13 (4)

AY15EU 24VDC/240 VAC AY13E (3)

AY13EU

12 VDC/240 VAC

Y01 Y00

L L

Y1E Y1D COM4 Y1F

0V 100/200 VAC

100/200 VAC 100/200 VAC

100/200 VAC + −

Y01 Y00

L

Model Rated Input Voltage Model Rated Input Voltage

100/200 VAC

100/200 VAC

Vacant Vacant

Model Rated Input Voltage Model Rated Input Voltage

(7) AY23 100/240 VAC AY40

Y01 Y00

L L

Y1E Y1D COM4 Y1F

L

100/200 VAC

100/200 VAC 100/200 VAC

100/200 VAC Vacant

Vacant

12/24 VDC 12/24 VDC

+

+

Model Rated Input Voltage Model Rated Input Voltage

(9) AY40A 12/24 VDC (10) AY41

AY41P 12/24 VDC

12/24 VDC

Y01

Y1F Y1E L

12/24 VDC

12/24 VDC

12/24 VDC

12/24 VDC + −

+ −

Model Rated Input Voltage Model Rated Input Voltage

AY42 (12)

Y00 Y10

Y01 Y11

Y02 Y12

Y03 Y13

Y04 Y14

Y05 Y15

Y06 Y16

Y07 Y17

Y08 Y18

Y09 Y19

Y0A Y1A

Y0B Y1B

Y0C Y1C

Y0D Y1D

Y0E Y1E

Y0F Y1F

Vacant Vacant

Vacant Vacant

12/24 VDC 0V

12/24 VDC 0V +

* The figure above indicates F (the first half 32 points).

The connections for L (the latter half 32 points) are the same as for F (regard Y00 to Y1F as Y20 to Y3F).

B1 and B2 , and A1 and A2 are connected internally.

L

Y00 Y10

Y01 Y11

Y02 Y12

Y03 Y13

Y04 Y14

Y05 Y15

Y06 Y16

Y07 Y17

Y08 Y18

Y09 Y19

Y0A Y1A

Y0B Y1B

Y0C Y1C

Y0D Y1D

Y0E Y1E

Y0F Y1F

Vacant Vacant

Vacant Vacant

5/12/24 VDC 0V

5/12/24 VDC 0V − +

Model Rated Input Voltage Model Rated Input Voltage

Y00 Y10

Y01 Y11

Y02 Y12

Y03 Y13

Y04 Y14

Y05 Y15

Y06 Y16

Y07 Y17

Y08 Y18

Y09 Y19

Y0A Y1A

Y0B Y1B

Y0C Y1C

Y0D Y1D

Y0E Y1E

Y0F Y1F

Vacant Vacant

Vacant Vacant

COM1 COM1 Vacant

Vacant +

* The figure above indicates F (the first half 32 points).

The connections for L (the latter half 32 points) are the same as for F (regard Y00 to Y1F as Y20 to Y3F).

Regard COM1 as COM2.

B1 and B2 , and A1 and A2 are connected internally.

B1 and B2 , and A1 and A2 are connected internally.