• 沒有找到結果。

System performance and economic analysis of solar-assisted cooling/heating system

N/A
N/A
Protected

Academic year: 2021

Share "System performance and economic analysis of solar-assisted cooling/heating system"

Copied!
9
0
0

加載中.... (立即查看全文)

全文

(1)

System performance and economic analysis of solar-assisted

cooling/heating system

B.J. Huang

a,⇑

, J.H. Wu

a

, R.H. Yen

a

, J.H. Wang

a

, H.Y. Hsu

a

, C.J. Hsia

a

, C.W. Yen

a

,

J.M. Chang

b

aDepartment of Mechanical Engineering, National Taiwan University, Taipei, Taiwan

bDepartment of Refrigeration, Air Conditioning and Energy Engineering, National Chin-Yi University of Technology, Taichung, Taiwan

Received 20 November 2010; received in revised form 2 August 2011; accepted 15 August 2011 Available online 13 September 2011

Communicated by: Associate Editor Yanjun Dai

Abstract

The long-term system simulation and economic analysis of solar-assisted cooling/heating system (SACH-2) was carried out in order to find an economical design. The solar heat driven ejector cooling system (ECS) is used to provide part of the cooling load to reduce the energy consumption of the air conditioner installed as the base-load cooler. A standard SACH-2 system for cooling load 3.5 kW (1 RT) and daily cooling time 10 h is used for case study. The cooling performance is assumed only in summer seasons from May to October. In winter season from November to April, only heat is supplied. Two installation locations (Taipei and Tainan) were examined.

It was found from the cooling performance simulation that in order to save 50% energy of the air conditioner, the required solar

col-lector area is 40 m2in Taipei and 31 m2in Tainan, for COPj= 0.2. If the solar collector area is designed as 20 m2, the solar ejector cooling

system will supply about 17–26% cooling load in Taipei in summer season and about 21–27% cooling load in Tainan. Simulation for long-term performance including cooling in summer (May–October) and hot water supply in winter (November–April) was carried

out to determine the monthly-average energy savings. The corresponding daily hot water supply (with 40°C temperature rise of water)

for 20 m2solar collector area is 616–858 L/day in Tainan and 304–533 L/day in Taipei.

The economic analysis shows that the payback time of SACH-2 decreases with increasing cooling capacity. The payback time is 4.8 years in Tainan and 6.2 years in Taipei when the cooling capacity >10 RT. If the ECS is treated as an additional device used as a protective equipment to avoid overheating of solar collectors and to convert the excess solar heat in summer into cooling to reduce the energy consumption of air conditioner, the payback time is less than 3 years for cooling capacity larger than 3 RT.

Ó 2011 Elsevier Ltd. All rights reserved.

Keywords: Ejector cooling; Solar ejector cooling; Economic analysis of solar cooling

1. Introduction

The ejector cooling system (ECS) using low boiling point refrigerant is suitable for solar cooling application due to its simple design and low cost.Huang et al. (1998, 1999) has shown that the COP of an ECS using R141b, with a proper design of ejector and system structure, can reach 0.54 at generator temperature 84°C, condenser

temperature 28°C, and evaporator temperature 8 °C. This makes the ECS become competitive to the sorption (absorption or adsorption) system that is much more com-plicated in design and more expensive (Arbel and Sokolov, 2004; Nguyen et al., 2001; Sokolov and Hershgal, 1990a, b, 1991; Sun, 1997).

If the ECS was driven by solar energy, it always requires a back-up system to make up the heat to keep a constant cooling capacity for space cooling during cloudy or rainy periods (Fig. 1). Heat supplied by fossil fuel or electricity was generally adopted. This however causes a problem of

0038-092X/$ - see front matterÓ 2011 Elsevier Ltd. All rights reserved. doi:10.1016/j.solener.2011.08.011

⇑ Corresponding author.

E-mail address:[email protected](B.J. Huang).

www.elsevier.com/locate/solener Solar Energy 85 (2011) 2802–2810

(2)

additional investment of heaters and low efficiency in heat supply.

Another problem has been noted recently that a solar heating system installed essentially for space heating in winter seasons will produce too much heat in summer while cooling is required. ECS can thus provide a promising solu-tion to convert the excess heat into cooling in summer.

Huang et al. (2010) proposed a solar-assisted heating/ cooling system (SACH) to cope with the above problems. The solar ejector cooling system is used as the boosting cooling device to provide part of the cooling load to reduce the energy consumption of the air conditioner.

The solar-assisted ejector cooling/heating system (SACH-2) was studied in the present research, in which a conventional inverter-type air conditioner (heat pump) made of variable-speed compressor are connected in paral-lel with a solar ejector cooling system as shown inFig. 2. When solar irradiation is high enough to drive ECS, the cooling load is directly supplied by the ECS and the energy consumption of the compressor can be reduced by regulat-ing the rotational speed of the inverter-type air conditioner.

During cloudy or rainy periods or at night, SACH-2 will provide the entire cooling load from the inverter-type air conditioner (heat pump) as usual. SACH-2 can also pro-duce hot water from the solar collector.

Extensive research on the engineering design, optimal control, and performance test of SACH-2 was carried out byHuang et al. (2010). Since ejector is a simple device which can be easily and cheaply manufactured, it seems that the solar ejector cooling system can be competitive to other solar cooling technologies such as absorption or adsorption systems. However, the coefficient of performance (COP) of ejector cooling system is still not very high. So, there may be an optimal system design of SACH-2 which is most eco-nomical. The present research continues to study this prob-lem through the system simulation and economic analysis. 2. Analytical model

The system performance of SACH-2 can be carried out from the input of solar radiation data and given design parameters of SACH-2. The long-term system performance Nomenclature

Ac solar collector area (m2)

Bt the value of yearly energy saving at t year, NTD

(1 USD = 30 NTD)

E the present value of the total energy saving in N years, NTD

C total installation cost, NTD

COPj coefficient of performance of the ejector cooling

system (ECS) (dimensionless)

COPo coefficient of performance of the air conditioner

alone (dimensionless)

Cv heat capacity of water (kJ kg1°C1)

i interest rate

IT solar incident radiation upon the collector slope

(W m2)

Qe cooling capacity of the air conditioner (kW)

Qg heat input to the generator of ejector cooling

system (kW)

Qj cooling capacity of ejector cooling system (kW)

Qjmax designed maximum cooling capacity of ECS

(kW)

Qload designed cooling load of the cooling space (kW)

rloss Qj/Qload, fraction of system heat loss

(dimen-sionless)

ti initial time of daily solar heating process (h)

tf final time of daily solar heating process (h)

Vw daily hot water supply at DTw(L day1)

Wco input power of air conditioner alone (kW)

Wc2 input power of air conditioner in SACH-2 (kW)

DWc2 Wco–Wc2, energy saving of SACH-2 in cooling

performance (kW)

DTw water temperature rise in heating performance

of SACH-2 (°C) qw water density (kg m3)

g solar collector efficiency

(3)

can be simulated using a physical model derived from the principle of energy balance.

2.1. Physical model of SACH-2

SACH-2 is designed in parallel configuration as shown in Fig. 2. The solar ejector cooling system (ECS) is con-nected in parallel with an inverter-type air conditioner (heat pump). From the conservation of energy, the instan-taneous energy collected by the solar heating system can be expressed as the following equation:

QgðtÞ ¼ ITðtÞ  Ac g  ð1  rlossÞ ð1Þ

where IT is the solar incident radiation upon the collector

slope, Ac is total absorbing area, g is the collector

effi-ciency, rloss is the fraction of system heat loss.

Applying energy balance to the ejector cooling system, we obtain the cooling capacity supplied by the ejector cool-ing system, Qj, as the following equation

Qj¼ Qg COPj ð2Þ

where COPjis the coefficient of performance of the ejector

cooling system (ECS). COPjis among 0.2–0.5 for SACH-2

which operates independently.

For air conditioning, the fraction of cooling capacity supplied by SACH-2 is

rc¼ Qj=Qload ð3Þ

For SACH-2, the designed maximum cooling capacity of ECS, Qjmax, should be equal to the designed cooling load

of the cooling space Qload. The input power of air

condi-tioner alone is Wco¼

Qe COPo

ð4Þ where Qeis the cooling capacity of the air conditioner and

COPo is the coefficient of performance of the air

condi-tioner alone. The input power of air condicondi-tioner in SACH-2 is

Wc2¼

ð1  rcÞQe

COPo

ð5Þ The energy saving of SACH-2 in cooling performance is

DWc2¼ Wco Wc2 ð6Þ

SACH-2 will also supply heat simultaneously. The heating load depends on seasons. In winter, the solar energy col-lected Qg will be used to supply heat for a building. For

hot water supply, the amount of daily hot water supply at 40°C temperature rise (DTw) is Vw ¼ Rtf ti ITðtÞAcgð1  rlossÞdt qwCvDTw ;L=day ð7Þ

Fig. 3is the analytical procedure of SACH-2 system perfor-mance. For given instantaneous solar radiation data I which is obtained from long-term hourly meteorological record by local weather stations, the solar irradiation on tilted collector surface ITcan be converted. The total energy

saving of SACH-2 can be calculated by integrating the hourly performance.

A computer simulation program was developed in the present study for the thermal performance simulation of SACH-2 with various system design parameters.

2.2. Meteorological data processing

In the present study, we adopt the hourly meteorological data recorded in local weather station of Taipei (northern Taiwan) and Tainan (southern Taiwan) from 2003 to 2008.Fig. 4 is the monthly-average daily total horizontal solar irradiation for every month.Fig. 5 is the daily total horizontal solar irradiation. It is seen that the solar irradi-ation in Tainan is about 27% higher than Taipei.

3. Results of system performance analysis

3.1. Cooling performance simulation results of SACH-2 SACH-2 is designed in parallel configuration as shown inFig. 2. The solar collector efficiency g is taken as 0.615 at temperature 100°C for a commercial high-performance vacuum-tube collector. The fraction of system heat loss rloss

is taken as 0.2.

The system performance of SACH can be simulated for a specific system design. For easy understanding, a stan-dard SACH design which is suitable for an ordinary family

(4)

or a small office space with floor area 30–50 m2is taken in the present study with the following conditions:

– cooling load: 3.5 kW (1 RT)

– daily operation time for cooling: 10 h

– total daily cooling load: 35 kW h (10 RT h).

The design of solar collector area depends on the mete-orological data, the fraction of solar energy contribution, and the cooling load etc. Since solar cooling from SACH-2 is provided only in summer season from May to October, the month having the lowest solar irradiation was selected as the design baseline or lower bound. That is October as seen fromFig. 4. This can give a quick answer of the required solar collector area for a given performance (COPj) of ECS.

Figs. 6 and 7shows the variation of daily cooling capac-ity supply by ECS with the installed collector area in Taipei and Tainan, respectively. Since the cooling load is set as 1 RT for operating time 10 h/day, i.e. total daily cooling energy is 10 RT h/day, 100% cooling load is supplied by solar ECS and there is no power consumption of the air conditioner. For 5 RT h/day cooling energy it means that 50% cooling load is supplied by solar ECS and 50% power consumption of the air conditioner is saved. It is seen that for 50% energy saving of the air conditioner, the required

Fig. 3. Analytical procedure of SACH-2 system performance.

0 2 4 6 8 10 12 14 16 18 20 1 2 3 4 5 6 7 8 9 10 11 12

monthly-average daily solar irradiation

(MJ/m

2day)

month

Taipei Tainan

Fig. 4. Monthly-average daily total horizontal solar irradiation.

(5)

solar collector area is 40 m2in Taipei, and 31 m2in Tainan, for COPj= 0.2 which can be easily achieved using the

pres-ent technology of ECS (Huang et al., 1998, 1999).

To see how much solar ejector cooling can contribute the cooling load (1 RT), we further assume that the solar collector area is 20 m2which can be easily installed in most houses and run the simulation for COPj= 0.2, the

conser-vative value. Fig. 8 indicates that for solar collector area 20 m2, the solar ejector cooling system will supply about 17–26% cooling load rc (i.e. saving 17–26% energy of the

air conditioner, from Eq.(3)) in Taipei in summer season. For the same solar collector area 20 m2, the solar ejector cooling system will supply about 21–27% cooling load (i.e. saving 21–27% energy of the air conditioner) in Tainan (Fig. 9). The energy saving is linearly proportional to the solar collector area and COPj of the ECS. The above

results can be used to calculate the energy saving of a SACH-2 with different collector area and COPj by

multi-plying the ratio of the real collector area with respect to the reference value (20 m2) or the ratio of real COPj with

respect to the reference value (0.2).

3.2. Overall cooling and heating performance of SACH-2 Assume that the solar collector area is 20 m2. Simulation for long-term performance from 2003 to 2008 including

cooling in summer (May–October) and heating in winter (November–April) was carried out for SACH-2 in Taipei and Tainan. COPj of ECS is still taken as 0.2 for

SACH-2. The monthly average energy savings are shown in

Fig. 10. The energy saving is linearly proportional to the solar collector area and the COPjof the ECS. The results

ofFig. 10thus can be used to calculate the energy saving of a SACH with different collector area and COPjby

mul-tiplying the ratio of the real collector area with respect to the reference value (20 m2) or the ratio of real COPj with respect to the reference value (0.2).

SACH-2 will supply hot water in winter season to save the heating energy as shown in Fig. 10. Table 1 shows the corresponding daily hot water supply (with 40°C tem-perature rise of water) for the 20 m2 solar collector. It is seen that SACH-2 can supply daily hot water 616–858 L/day in Tainan and 304–533 L/day in Taipei. This can satisfy the requirement of about 12–16 residents (average hot water consumption 50 L/day per person) in Tainan, and 6–10 residents in Taipei.

4. Economic analysis of SACH-2

The long-term performance and energy saving of SACH-2 for various designs has been analyzed previously. Based on these simulation results, the economic analysis can be carried out in order to answer the question: what

0 5 10 15 20 25 30 35 0 20 40 60 80 100 120

daily total cooling capacity supply by solar

ejector cooling (RT-h/day)

Solar collector area (m2)

COPj=0.2 COPj=0.5 COPj=0.4 COPj=0.3 SACH-2 (parallel) Taipei cooling capacity 1RT

based on solar irradiation in October

Fig. 6. Daily cooling capacity supplied by ECS (Taipei).

0 5 10 15 20 25 30 35 40 45 0 20 40 60 80 100 120

daily total cooling capacity supply by solar

ejector cooling (RT-h/day)

Solar collector area (m2)

COPj=0.2 COPj=0.5 COPj=0.4 COPj=0.3 SACH-2 (parallel) cooling capacity 1RT Tainan

based on solar irradiation in October

Fig. 7. Daily ejector cooling capacity supply (Tainan).

Fig. 8. Fraction of cooling load supplied by solar ECS (Taipei).

(6)

is the proper size (cooling capacity) of ECS in the design of SACH-2.

4.1. Net present value and installation cost of SACH-2 The method of Net Present Value (NPV) is used in the present study. Eq. (8) is the formula to calculate the NPV where E is the present value of the total energy saving in N years as expressed in Eq. (9), C is the total installation cost and i is the interest rate which is taken as 2.1%.

NPV ¼ E  C ð8Þ E¼X N t¼1 Bt ð1 þ iÞt ð9Þ

where Btis the value of yearly energy saving at t year. The

NPV is calculated for N = 20 years.

The electricity price adopted in the present analysis is based on Taiwan system which charges electricity in low season (November–April) at NTD 3.97/kW h for monthly total power consumption >700 kW h/month and NTD 3.55/kW h for <700 kW h/month. [30 NTD = 1 USD].

For high season (May–October), the electricity price is NTD5.1/kW h for monthly total power consumption >700 kW h/month and NTD 4.51/kW h for <700 kW h/ month.

We assume that COPj= 0.3 which is achievable for an

ECS based on the state-of-the-art technology (Petrenko and Huang, 2010). Table 2 shows the mass production price estimation of 1 RT (3.5 kW) ejector cooling system only. For ECS lager than 1 RT, the cost increase will be about NTD 20,000 per RT.Table 3shows the price estima-tion of ejector cooling system from 1–10 RT.

For SACH-2, the designed cooling capacity of ECS, Qjmax, should be equal to the cooling load of the cooling

space Qload. Similar to the simulation process of SACH-2

shown inFig. 3, for a given cooling load Qloadand COPj,

the required solar collector area can be calculated. The installation cost of solar heating system includes solar collector modules which is NTD 10,000 m2and aux-iliary equipments (piping and insulation, storage tank and

Fig. 10. Performance of SACH-2.

Table 1

Daily hot water supply in winter season for collector area 20 m2. Hot water supply @40°C rise (L/day)

Month Tainan Taipei

1 616 304 2 736 382 3 743 422 4 858 533 11 646 389 12 646 316 Table 2

Price estimation of 1 RT ejector cooling system.

Item NTD (1USD = 30 NTD) Ejector 10,000 Condenser 10,000 Evaporator 10,000 Generator 25,000 Refrigerant pump 15,000 Receiver 7000 Piping 6000 Cooling tower 8000 Control system 15,000 Frame 9700 Total 115,700

(7)

pump, installation labor, control systems) which is NTD 380,000 per RT of ECS. From manufacturer, there is 5% discount per increase of 42 m2 solar collector area and 6% discount in auxiliary equipment per increase of 42 m2 solar collector area. Fig. 11 shows the total solar heating system installation cost.

Fig. 12is the variation of total SACH-2 system installa-tion cost with the ejector cooling capacity (or the space cooling load) which is the summation of the ejector cooling system cost and the solar heating system cost. The cost of the existing air conditioner is not included since it is the common equipment.

4.2. Economic analysis of SACH-2 for cooling and heating The NPV of the SACH-2 for N = 20 years can be calcu-lated using the yearly total energy saving (including cooling and heating) and the electricity price using Eq.(8). Assume that the thermal energy saving in heating from SACH-2 is to replace the electricity consumption since electric heaters are widely used for hot water supply. Fig. 13 shows the total NPV of SACH-2 for 20 year. It is seen that the higher installed capacity, the larger the NPV.

The payback time of SACH-2 can be calculated from Eq. (8) by determining NPBat NPV = 0, i.e.

E¼X

NPB

t¼1

Bt

ð1 þ iÞt¼ C ð10Þ

Fig. 14 shows that the payback time of SACH-2 decreases with increasing cooling capacity and approaches a constant. In Tainan, the payback time is 4.8 years when the cooling capacity >10 RT. In Taipei, the payback time is 6.2 years when the cooling capacity >10 RT.

4.3. Economic analysis of SACH-2 for cooling only In some cold regions, many large solar heating systems are installed for house heating purpose. But there is serious problem of overheating in summer season due very low heating load. The ECS can be used to protect the solar heating system in summer. Therefore, the ECS can be trea-ted as an additional device in SACH-2 used to convert the excess solar heat in summer into cooling to reduce the energy consumption of air conditioner. Only the installa-tion cost of ECS needs to be considered. The NPV is lower as shown inFig. 15, but the payback time of the ECS is less than 3 years for cooling capacity larger than 3 RT as shown inFig. 16.

5. Discussion and conclusion

The present research develops a system analysis model of SACH-2 and a computer simulation program to analyze the system performance and economic effectiveness of

Price estimation of ejector cooling system of various capacity.

Ejector cooling system size (RT) Price (NTD) 1 USD = 30 NTD

1 115,700 2 135,700 3 155,700 4 175,700 5 195,700 6 215,700 7 235,700 8 255,700 9 275,700 10 295,700 0 1,000,000 2,000,000 3,000,000 4,000,000 5,000,000 6,000,000 0 50 100 150 200 250 300 350 400 450

solar collector area, m2

total solar system installation cost, NTD

Fig. 11. Total solar heating system installation cost.

0 1,000,000 2,000,000 3,000,000 4,000,000 5,000,000 6,000,000 7,000,000 0 2 4 6 8 10 12 cooling load, RT

total SACH system installation cost, NTD

0 100 200 300 400 500 600 700 800

solar collector area (m

2 )

Tainan

SACH-2

(8)

SACH-2 at different designs. A standard design is taken in the present study for the study of system performance of SACH-2 with the following conditions:

– cooling load: 3.5 kW (1 RT)

– daily operation time for cooling: 10 h – total daily cooling load: 35 kW h (10 RT h).

The cooling performance of SACH-2 is assumed only in summer seasons from May to October (6 months a year). In winter season from November to April, only heat is sup-plied by SACH. Two installation locations (Taipei and Tai-nan) were studied.

The system simulation for the cooling performance of SACH-2 is used to calculate the required solar collector area. It was found that in order to save 50% energy of the air conditioner, the required solar collector area is 40 m2in Taipei and 31 m2in Tainan, for COPj= 0.2 which

can be easily achieved using the present technology of ECS. If the solar collector area is designed as 20 m2, the solar ejector cooling system will supply about 17–26% cooling load (i.e. saving 17–26% energy of the air conditioner) in Taipei in summer season and about 21–27% cooling load (i.e. saving 21–27% energy of the air conditioner) in Tai-nan. The energy saving is linearly proportional to the solar collector area and the COPj of the ECS. The results thus

can be used to calculate the energy saving of a SACH-2 with different collector area and COPj.

Simulation for long-term performance from 2003 to 2008 including cooling in summer (May–October) and heating in winter (November–April) was carried out for SACH-2 in Taipei and Tainan to determine the monthly-average energy savings. COPj of ECS is still

taken as 0.2. SACH-2 will supply hot water in winter sea-son to save the heating energy. The corresponding daily hot water supply (with 40°C temperature rise of water) for 20 m2solar collector area is 616–858 L/day in Tainan and 304–533 L/day in Taipei. This can satisfy the daily requirement of about 12–16 residents (average hot water consumption 50 L/day per person) in Tainan, and 6–10 residents in Taipei. The energy saving of cooling and heating is linearly proportional to the solar collector area

Fig. 14. Payback time of SACH-2.

Fig. 15. NPV of SACH-2 for 20 year used in summer cooling only.

Fig. 16. Payback time of SACH-2 for 20 year used in summer cooling only.

(9)

and the COPjof the ECS. The results can be used to

cal-culate the energy saving of a SACH-2 with different col-lector area and COPj.

The economic analysis shows that the higher installed capacity, the larger NPV. The payback time of SACH-2 decreases with increasing cooling capacity and approaches a constant. In Tainan, the payback time is 4.8 years when the cooling capacity >10 RT. In Taipei, the payback time is 6.2 years when the cooling capacity >10 RT.

In some cold regions, many large solar heating systems are installed for house heating purpose. But there is serious problem of overheating in summer season due to very low heating load. The ECS can be used to protect the solar heating system in summer by consuming the solar heat and converting it into cooling. Therefore, the ECS can be treated as an additional device in SACH-2 used to convert the excess solar heat in summer into cooling to reduce the energy consumption of air conditioner. Only the installa-tion cost of ECS needs to be considered. In this case, the payback time of the ECS is less than 3 years for cooling capacity larger than 3 RT.

The system simulation and economic analysis of SACH-2 takes a conservative estimation using COPj= 0.2.

Actu-ally, the COPj can be further improved to be higher than

0.4 if the system design of SACH-2 is improved. The sys-tem performance can be improved by raising the evapora-tor temperature of the ECS, or using an advanced control technology (Huang et al., 2010). The present results can be treated as a lower bound of the system performance.

Although the COPjof the ECS is relatively low as

com-pared with that of absorption systems, the manufacturing cost of ECS is low, especially for small-size machine (<10 RT). It seems that SACH-2 is more suitable for small solar cooling systems (<10 RT).

Acknowledgment

This publication is based on work supported by Award No. KUK-C1-014-12, made by King Abdullah University of Science and Technology (KAUST), Saudi Arabia. References

Arbel, A., Sokolov, M., 2004. Revisiting solar-powered ejector air conditioner-the greener the better. Solar Energy 77, 57–66.

Huang, B.J., Chang, J.M., Petrenko, V.A., Zhuk, K.B., 1998. A solar ejector cooling system using refrigerant R141b. Solar Energy 64 (4–6), 223–226.

Huang, B.J., Chang, J.M., Wang, C.P., Petrenko, V.A., 1999. A 1D analysis of ejector performance. International Journal of. Refrigera-tion 22, 354–364.

Huang, B.J., Yen, C.W., Wu, J.H., Liu, J.H., Hsu, H.Y., Petrenko, V.O., Chang, J.M., Lu, C.W., 2010. Optimal control and performance test of solar-assisted cooling system. Applied Thermal Engineering 30, 2243– 2252.

Nguyen, V.M., Riffat, S.B., Doherty, P.S., 2001. Development of a solar-powered passive ejector cooling system. Applied Thermal Engineering 21, 157–168.

Petrenko, V.O., Huang, B.J., 2010. Advanced ejector air conditioners and chillers utilizing solar energy and waste heat, in: International Conference on Engineering Solutions for Sustainable Development, 17–18 April, 2010, American University in Cairo, Cairo, Egypt. Sokolov, M., Hershgal, D., 1990a. Enhanced ejector refrigeration cycles

powered by low grade heat. Part 1. Systems characterization. Inter-national Journal of. Refrigeration 12, 351–356.

Sokolov, M., Hershgal, D., 1990b. Enhanced ejector refrigeration cycles powered by low grade heat. Part 2. Design procedures. International Journal of. Refrigeration 12, 357–363.

Sokolov, M., Hershgal, D., 1991. Enhanced ejector refrigeration cycles powered by low grade heat. Part 3. Experimental results. International Journal of. Refrigeration 14, 24–31.

Sun, D.W., 1997. Solar powered combined ejector-vapour compression cycle for air conditioning and refrigeration. Energy Conversion and Management 38, 479–491.

數據

Fig. 1. Conventional solar cooling system.
Fig. 3 is the analytical procedure of SACH-2 system perfor- perfor-mance. For given instantaneous solar radiation data I which is obtained from long-term hourly meteorological record by local weather stations, the solar irradiation on tilted collector surf
Fig. 3. Analytical procedure of SACH-2 system performance.
Fig. 6. Daily cooling capacity supplied by ECS (Taipei).
+4

參考文獻

相關文件

The quantity of landscape planting in campus was evaluated and used as an indicator to divide the campus into different landscape zones where the air anions

Without making any improvement in the surface treatment of the solar cell, due to the refractive index of incident medium refractive index and different, which led to the

Failure Mode and Effects Analysis (Failure Modes and Effects Analysis, FMEA) is used to analyze the product / system, the potential failure modes, identify potential trouble spots

A digital color image which contains guide-tile and non-guide-tile areas is used as the input of the proposed system.. In RGB model, color images are very sensitive

In order to use the solar rays more efficient and improve the conversion efficiency of solar cell, it is necessary to use antireflection layer to reduce the losses of

However, the information mining system has already been a trend of the current epoch, if it is possible to obtain an effective management system to integrate data that relates to

Investigating the effect of learning method and motivation on learning performance in a business simulation system context: An experimental study. Four steps to

Kim, “Improvement on surface texturing of single crystalline silicon for solar cells by saw-damage etching using an acidic solution,” Solar Energy Materials and